Siemens · HVAC controller
RDF302 / RDF302.B / RDF302/VB room thermostats Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 1-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1001 | 1 | Room operating mode: state Object 2. 1 = Comfort, 3 = Economy, 4 = Protection. | UInt16 | - | 1 | R |
| 1002 | 1 | Fan output Object 3. 0 = fan off, 33 = low, 66 = mid, 100 = high. | UInt16 | - | 1 | R |
| 1003 | 1 | Room temperature Object 4. Value x 50; 0xFFFF = out of service. | Int16 | °C | 0.02 | R |
| 1004 | 1 | Room temperature: current setpoint Object 5. Value x 50; range 5...40 degC, 4 = OFF. | Int16 | °C | 0.02 | R |
| 1005 | 1 | Heating output Object 6. 0...100. | UInt16 | % | 1 | R |
| 1006 | 1 | Cooling output Object 7. 0...100. | UInt16 | % | 1 | R |
| 1007 | 1 | Electric heater output Object 8. 0...100. | UInt16 | % | 1 | R |
| 1008 | 1 | X1 input (temperature) Object 10. Value x 50; 0...49 degC, 0xFFFF = out of service. | Int16 | °C | 0.02 | R |
| 1009 | 1 | X2 input (temperature) Object 11. Value x 50; 0...49 degC, 0xFFFF = out of service. | Int16 | °C | 0.02 | R |
| 1010 | 1 | Fan operation (0 = auto / 1 = manual) Object 12. | UInt16 | - | 1 | R |
| 1011 | 1 | X1 input (digital) Object 13. 0 = OFF, 1 = ON. | UInt16 | - | 1 | R |
| 1012 | 1 | X2 input (digital) Object 14. 0 = OFF, 1 = ON. | UInt16 | - | 1 | R |
| 1100 | 10 | Fault information Object 9. 10 registers, max 20 characters; the default fault text is selected by the active alarm (condensation, fault input 1/2, dirty filter). | Ascii | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Siemens "RDF302, RDF302/VB, RDF302.B - Flush-mounted room thermostats with RS485 Modbus communications - Basic documentation", CE1P3079en, edition 1.5, 2020-12-01, 66 pages. Copy read: mekonsis.com.tr/class/INNOVAEditor/assets/pdf/RDF302.pdf, SHA-256 d26920751e9aebd2fd74b81b06492ca2e9faa16acd97b4c5a4366e48983bc63a; the sipatec.rs mirror formerly cited here now serves only the 18-page data sheet CE1N3079en. The RDF302 is a room thermostat that also drives fan coil and heat pump plants (2-pipe, 2-pipe with electric heater, 4-pipe, compressor applications). Factory frame, 3.11: device address 1 (P81), baud rate 19200 bps (P68) and parity even (P70); 3.11 states the device uses "Modbus RTU mode as per the Modbus specification", which fixes 8 data bits and one stop bit at that parity. Register numbers are the "Address (Decimal)" column of the communication-object table 3.12.2, printed per area starting at 1 (object 28 "P01" at 0001, the first input object at 1001); the document states no address base, so one_based is the declared convention and the client subtracts one for the PDU address (a 0-based master reads P01 at wire address 0). The "Special Process" column prints x50 for every temperature row, the 0.02 factor used here. Objects 1 (system time, four packed registers) and 24...27 (four 10-register Ascii fault texts) are omitted as packed or text-only blocks. The expert-level parameters are omitted by scope, not by doubt: 3.12.2 pairs each of them with an address (object 41 "P30" at 0030 through object 74 "P81" at 0081, with P46 at 0182), while the descriptive table 3.13.4 is the one whose name column drifts, so no description is carried from it. That is where P68 (0068), P70 (0070) and P81 (0081) appear in the document.