All devices

Siemens · Energy meter

SENTRON PAC2200 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
12
Voltage L1-N
Float32V1R
32
Voltage L2-N
Float32V1R
52
Voltage L3-N
Float32V1R
72
Voltage L1-L2
Float32V1R
92
Voltage L2-L3
Float32V1R
112
Voltage L3-L1
Float32V1R
132
Current L1
Float32A1R
152
Current L2
Float32A1R
172
Current L3
Float32A1R
192
Apparent power L1
Float32VA1R
212
Apparent power L2
Float32VA1R
232
Apparent power L3
Float32VA1R
252
Active power L1
Float32W1R
272
Active power L2
Float32W1R
292
Active power L3
Float32W1R
312
Reactive power L1
Float32var1R
332
Reactive power L2
Float32var1R
352
Reactive power L3
Float32var1R
372
Power factor L1
Float32-1R
392
Power factor L2
Float32-1R
412
Power factor L3
Float32-1R
552
Frequency
Float32Hz1R
572
Average voltage L-N
Float32V1R
592
Average voltage L-L
Float32V1R
612
Average current
Float32A1R
632
Total apparent power
Float32VA1R
652
Total active power
Float32W1R
672
Total reactive power
Float32var1R
692
Total power factor
Float32-1R
712
Neutral current
Float32A1R
2052
Device diagnostics and device status
Byte 0 = global state, byte 1 = local state, byte 2 = global diagnostics.
UInt32-1R
2072
Status of the digital outputs
Bit 0 = output 0.
UInt32-1R
2092
Status of the digital inputs
Bit 0 = input 0.
UInt32-1R
2112
Active tariff
0 = tariff 1, 1 = tariff 2.
UInt32-1R
2152
Universal counter
0 to 999999999.
UInt32-1RW
8014
Active energy imported, tariff 1
Float64kWh0.001R
8054
Active energy imported, tariff 2
Float64kWh0.001R
8094
Active energy exported, tariff 1
Float64kWh0.001R
8134
Active energy exported, tariff 2
Float64kWh0.001R
9614
Secondary total of active energy imported (MID register)
Float64kWh0.001R
9654
Secondary total of active energy exported (MID register)
Float64kWh0.001R
5012
Cumulated average active power import
Float32W1R
5032
Cumulated average reactive power import
Float32var1R
5052
Cumulated average active power export
Float32W1R
5072
Cumulated average reactive power export
Float32var1R

Notes

Source: Siemens 'SENTRON 7KM PAC2200 - Equipment Manual', 12/2022, L1V30415167B-06, freely downloadable from Siemens Industry Online Support (document 109746835). Register 71 'Neutral current' is table A-3 on printed page 106; the energy counters 801/805/809/813 are on page 107 and the MID secondary totals 961/965 on page 108. The offsets in those tables are the wire addresses used here. All measured variables can be read with function code 03 as well as 04, so they are listed as holding registers. Values are IEEE-754 floats (32 bit) except the energy counters, which are 64-bit floats in Wh and are scaled to kWh. The 801-813 counters are marked read/write in the 03/2017 B-01 edition of the manual and read-only in the 09/2021 B-04 and 12/2022 B-06 editions; the access column follows the current B-06 marking (R). The PAC2200 is available with an Ethernet interface (Modbus TCP, modelled here) or with an RS-485 interface (Modbus RTU); for the RS-485 variant use the same register map through a gateway. The manual also documents a separate bank of 32-bit float energy counters from offset 2801.