SENTRON PAC3200 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
2001
Digital input 0
Status of digital input 0, read with function code 02 (single bit).
Binary-1R
3001
Digital output 0
Status of digital output 0, read with function code 02 (single bit).
Binary-1R

Combined registers

  • Active power L1 + L2 (calculated)Holding registers 25 + Holding registers 27 (W)
  • Active power, all phases (calculated)Active power L1 + L2 (calculated) + Holding registers 29 (W)Sum of the three phase values, next to the device's own total at 65.
  • Active energy imported, both tariffs (calculated)Holding registers 801 + Holding registers 805 (Wh)
  • Active energy exported, both tariffs (calculated)Holding registers 809 + Holding registers 813 (Wh)

Notes

Addresses are the "Offset" values in the SENTRON PAC3200 product manual (A5E01168664, chapter 3.9) and are used as wire addresses; address 0 is not used by the measured values. The manual states that all measured values can be read with function code 03 and with function code 04, so the entries below work as holding registers and, on the same addresses, as input registers. Measured values are IEEE 754 single precision (2 registers), the energy counters are IEEE 754 double precision (4 registers, Wh/varh/VAh). Energy counters and settings are writable; writing an energy counter resets or preloads it. Status bits, limit states and the digital input/output are available as discrete inputs (function code 02) at bit offsets 0-5, 50, 108-127, 200 and 300. Only the measured values, demand, energy and the transformer/demand settings are listed here; the min/max, limit and communication parameter blocks (offsets 75-201, 63001-63025) follow the same pattern in the manual.