Siemens · HVAC controller
Climatix POL638 / POL687 with AHU application V3.3x Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 1-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1 | 1 | General status (word 1) 3x0001. Bit 0 alarm class danger (A), 1 alarm class critical (A), 2 alarm class low (B), 3 alarm class warning (C), 8 manual control active, 9 summer mode, 10 communication test pulse, 11 preheating heating register, 12 preheating extra heating register, 14 actual control mode temperature room, 15 actual control mode temperature exhaust. | Binary | - | 1 | R |
| 2 | 1 | General status (word 2) 3x0002. Bit 0/1 actual control mode humidity room/supply; the remaining bits are reserved. | Binary | - | 1 | R |
| 3 | 1 | General status (word 3) 3x0003. Reserved bits of the general status block. | Binary | - | 1 | R |
| 4 | 1 | General status (word 4) 3x0004. Reserved bits of the general status block. | Binary | - | 1 | R |
| 5 | 1 | Digital inputs (word 1) 3x0005. Bit 0 emergency stop, 1 external control 1, 2 external control 2, 3 summer/winter changeover, 4 alarm acknowledge, 8 auxiliary input. | Binary | - | 1 | R |
| 6 | 1 | Digital inputs (word 2) 3x0006. Bit 0 dampers open, 1 fire dampers open, 2 fire dampers closed, 4 supply fan feedback, 5 exhaust fan feedback. | Binary | - | 1 | R |
| 7 | 1 | Digital inputs (word 3) 3x0007. Reserved bits of the digital-input block. | Binary | - | 1 | R |
| 8 | 1 | Digital inputs (word 4) 3x0008. Reserved bits of the digital-input block. | Binary | - | 1 | R |
| 9 | 1 | Digital outputs (word 1) 3x0009. Bit 0 supply damper, 1 extract damper, 2 fire damper, 4 supply fan running, 5 supply fan off, 6/7/8 supply fan stage 1/2/3, 9 exhaust fan running, 10 exhaust fan off, 11/12/13 exhaust fan stage 1/2/3. | Binary | - | 1 | R |
| 10 | 1 | Digital outputs (word 2) 3x0010. Bit 0 cooling pump, 1 cooling DX off, 2/3/4 cooling DX stage 1/2/3, 6 heating recovery pump/command, 8 heating pump, 10 electrical heating off, 11/12/13 electrical heating stage 1/2/3. | Binary | - | 1 | R |
| 11 | 1 | Digital outputs (word 3) 3x0011. Bit 0 extra cooling (2) pump, 1 extra cooling (2) DX off, 2/3/4 extra cooling (2) DX stage 1/2/3, 6 extra heating (2) pump, 8 extra electrical heating (2) off, 9/10/11 extra electrical heating (2) stage 1/2/3. | Binary | - | 1 | R |
| 12 | 1 | Digital outputs (word 4) 3x0012. Reserved bits of the digital-output block. | Binary | - | 1 | R |
| 13 | 1 | Alarms (word 1) 3x0013. Alarm bits of the AHU application (0 = normal, 1 = alarm). | Binary | - | 1 | R |
| 14 | 1 | Alarms (word 2) 3x0014. Alarm bits of the AHU application (0 = normal, 1 = alarm). | Binary | - | 1 | R |
| 15 | 1 | Alarms (word 3) 3x0015. Alarm bits of the AHU application (0 = normal, 1 = alarm). | Binary | - | 1 | R |
| 16 | 1 | Alarms (word 4) 3x0016. Alarm bits of the AHU application (0 = normal, 1 = alarm). | Binary | - | 1 | R |
| 38 | 1 | Heat recovery damper output signal 3x0038. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 39 | 1 | Heat recovery damper recovery 3x0039. Actual recovery degree 0...100 %. | UInt16 | % | 1 | R |
| 40 | 1 | Heating output signal 3x0040. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 41 | 1 | Heating pump command 3x0041. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 42 | 1 | Electrical heating output signal 3x0042. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 43 | 1 | Electrical heating command 3x0043. 0 = off, 1 = stage 1, 2 = stage 2, 3 = stage 3. | UInt16 | - | 1 | R |
| 44 | 1 | Cooling 2 output signal 3x0044. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 45 | 1 | Cooling 2 pump command 3x0045. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 46 | 1 | Cooling 2 DX command 3x0046. 0 = off, 1...3 = stage 1...3. | UInt16 | - | 1 | R |
| 47 | 1 | Heating 2 output signal 3x0047. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 48 | 1 | Heating 2 pump command 3x0048. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 49 | 1 | Electrical heating 2 output signal 3x0049. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 50 | 1 | Electrical heating 2 command 3x0050. 0 = off, 1...3 = stage 1...3. | UInt16 | - | 1 | R |
| 52 | 1 | Humidifier output signal 3x0052. Output signal 0...100 %. | UInt16 | % | 1 | R |
| 53 | 1 | Humidifier command 3x0053. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 54 | 1 | Humidifier pump command 3x0054. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 55 | 1 | Actual dehumidity value 3x0055. 0...100 %. | UInt16 | % | 1 | R |
| 57 | 1 | Auxiliary operation mode output 3x0057. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 58 | 1 | Auxiliary time switch program output 3x0058. 0 = off, 1 = on. | UInt16 | - | 1 | R |
| 59 | 1 | Auxiliary analog output fan 3x0059. 0...100 %. | UInt16 | % | 1 | R |
| 60 | 1 | Alarm output 1 3x0060. 0 = normal, 1 = alarm. | UInt16 | - | 1 | R |
| 61 | 1 | Alarm output 2 3x0061. 0 = normal, 1 = alarm. | UInt16 | - | 1 | R |
| 62 | 1 | Supply filter pressure 3x0062. Supply filter differential pressure in Pa. | UInt16 | Pa | 1 | R |
| 63 | 1 | Exhaust filter pressure 3x0063. Exhaust filter differential pressure in Pa. | UInt16 | Pa | 1 | R |
| 64 | 1 | Actual air quality compensation 3x0064. 0...100 %. | UInt16 | % | 1 | R |
| 65 | 1 | Actual fan cooling value 3x0065. 0...100 %. | UInt16 | % | 1 | R |
| 66 | 1 | Actual fan heating value 3x0066. 0...100 %. | UInt16 | % | 1 | R |
| 67 | 1 | Actual fan compensation temperature 3x0067. 0...100 %. | UInt16 | % | 1 | R |
| 68 | 1 | Actual fan compensation humidity 3x0068. 0...100 %. | UInt16 | % | 1 | R |
| 69 | 1 | Actual summer compensation fan 3x0069. 0...100 %. | UInt16 | % | 1 | R |
| 70 | 1 | Actual winter compensation fan 3x0070. 0...100 %. | UInt16 | % | 1 | R |
| 71 | 1 | Actual operating state 3x0071. 0 = not used, 1 = configuration, 2 = fire, 3 = alarm class 0, 4 = emergency stop, 5 = alarm class 1, 6 = fire-damper test, 7 = manual control, 8 = external control, 9 = room unit, 10 = OSSTP, 11 = unoccupied heating/cooling, 12 = free cooling, 13 = BMS control, 14 = TSP control, 15 = temperature test, 16 = calendar. | UInt16 | - | 1 | R |
| 72 | 1 | Outside air temperature 3x0072. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 73 | 1 | Supply air temperature 3x0073. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 74 | 1 | Heating frost temperature 3x0074. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 75 | 1 | Actual room temperature 3x0075. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 76 | 1 | Exhaust air temperature 3x0076. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 77 | 1 | Extract air temperature 3x0077. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 78 | 1 | Heat recovery supply air temperature 3x0078. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 79 | 1 | Heat recovery water temperature 3x0079. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 80 | 1 | Supply air temperature 2 3x0080. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 81 | 1 | Heating 2 frost temperature 3x0081. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 82 | 1 | Auxiliary temperature 3x0082. Signed word, factor 10. | Int16 | °C | 0.1 | R |
| 84 | 1 | Outside air relative humidity 3x0084. 0...100 %rH. | UInt16 | % | 1 | R |
| 85 | 1 | Outside air absolute humidity 3x0085. Factor 10. | Int16 | g/kg | 0.1 | R |
| 86 | 1 | Outside air enthalpy 3x0086. Factor 10. | Int16 | kJ/kg | 0.1 | R |
| 87 | 1 | Supply air relative humidity 3x0087. 0...100 %rH. | UInt16 | % | 1 | R |
| 88 | 1 | Supply air absolute humidity 3x0088. Factor 10. | Int16 | g/kg | 0.1 | R |
| 89 | 1 | Supply air enthalpy 3x0089. Factor 10. | Int16 | kJ/kg | 0.1 | R |
| 90 | 1 | Room relative humidity 3x0090. 0...100 %rH. | UInt16 | % | 1 | R |
| 91 | 1 | Room absolute humidity 3x0091. Factor 10. | Int16 | g/kg | 0.1 | R |
| 92 | 1 | Room enthalpy 3x0092. Factor 10. | Int16 | kJ/kg | 0.1 | R |
| 93 | 1 | Dew point 3x0093. Factor 10. | Int16 | °C | 0.1 | R |
| 95 | 1 | Supply air flow 3x0095. Supply air flow in l/s. | UInt16 | l/s | 1 | R |
| 96 | 1 | Exhaust air flow 3x0096. Exhaust air flow in l/s. | UInt16 | l/s | 1 | R |
| 97 | 1 | Supply air pressure 3x0097. Supply duct pressure in Pa. | UInt16 | Pa | 1 | R |
| 98 | 1 | Exhaust air pressure 3x0098. Exhaust duct pressure in Pa. | UInt16 | Pa | 1 | R |
| 99 | 1 | Heat recovery frost pressure 3x0099. Heat-recovery frost protection pressure in Pa. | UInt16 | Pa | 1 | R |
| 101 | 1 | Air quality 3x0101. Air-quality sensor value in ppm. | UInt16 | ppm | 1 | R |
| 102 | 1 | External setpoint 3x0102. External setpoint, factor 10. | Int16 | °C | 0.1 | R |
| 104 | 1 | Actual heating setpoint, main 3x0104. Depends on the actual control mode; factor 10. | Int16 | °C | 0.1 | R |
| 105 | 1 | Actual cooling setpoint, main 3x0105. Depends on the actual control mode; factor 10. | Int16 | °C | 0.1 | R |
| 106 | 1 | Actual supply heating setpoint 3x0106. Used with cascade control; factor 10. | Int16 | °C | 0.1 | R |
| 107 | 1 | Actual supply cooling setpoint 3x0107. Used with cascade control; factor 10. | Int16 | °C | 0.1 | R |
| 108 | 1 | Actual humidity setpoint, main 3x0108. Factor 10; %rH or g/kg depending on configuration. | UInt16 | % | 0.1 | R |
| 109 | 1 | Actual dehumidity setpoint, main 3x0109. Factor 10; %rH or g/kg depending on configuration. | UInt16 | % | 0.1 | R |
| 110 | 1 | Actual supply humidity setpoint 3x0110. Cascade control; factor 10. | UInt16 | % | 0.1 | R |
| 111 | 1 | Actual supply dehumidity setpoint 3x0111. Cascade control; factor 10. | UInt16 | % | 0.1 | R |
| 112 | 1 | Actual supply fan setpoint 3x0112. %, Pa or l/s depending on the configured engineering unit. | UInt16 | % | 1 | R |
| 113 | 1 | Actual exhaust fan setpoint 3x0113. %, Pa or l/s depending on the configured engineering unit. | UInt16 | % | 1 | R |
| 115 | 1 | Actual summer compensation temperature 3x0115. Factor 10. | Int16 | °C | 0.1 | R |
| 116 | 1 | Actual winter compensation temperature 3x0116. Factor 10. | Int16 | °C | 0.1 | R |
| 117 | 1 | Heat recovery efficiency 3x0117. 0...100 %. | UInt16 | % | 1 | R |
| 118 | 1 | Cooling recovery (MECH) active 3x0118. 0 = passive, 1 = active. | UInt16 | - | 1 | R |
| 120 | 1 | Energy actual power 3x0120. Factor 10. | Int16 | W | 0.1 | R |
| 121 | 1 | Energy average power 3x0121. Factor 10. | Int16 | W | 0.1 | R |
| 122 | 1 | Energy operating hours 3x0122. Factor 10. | Int16 | h | 0.1 | R |
| 123 | 1 | Energy partial 3x0123. Factor 10. | Int16 | kWh | 0.1 | R |
| 124 | 1 | Energy total 3x0124. Factor 10. | Int16 | kWh | 0.1 | R |
| 125 | 1 | Modbus communication alarm 3x0125. 0 = OK, 1 = alarm. | UInt16 | - | 1 | R |
| 200 | 1 | Actual room unit mode 3x0200. 0 = auto, 1 = comfort, 2 = standby, 3 = economy, 4 = off. | UInt16 | - | 1 | R |
| 210 | 1 | Actual room unit setpoint 3x0210. Factor 10. | Int16 | °C | 0.1 | R |
| 211 | 1 | Room unit temperature 3x0211. Factor 10. | Int16 | °C | 0.1 | R |
| 212 | 1 | Room unit 2 temperature 3x0212. Factor 10. | Int16 | °C | 0.1 | R |
| 213 | 1 | Room temperature 3x0213. Factor 10. | Int16 | °C | 0.1 | R |
| 214 | 1 | Room 2 temperature 3x0214. Factor 10. | Int16 | °C | 0.1 | R |
| 220 | 1 | Time switch type 3x0220. 0 = none, 1 = step, 2 = step + temperature. | UInt16 | - | 1 | R |
| 221 | 1 | Time switch number of steps 3x0221. 0 = 1 step, 1 = 2 steps, 2 = 3 steps. | UInt16 | - | 1 | R |
| 222 | 1 | Fan control mode 3x0222. 0 = direct, 1 = direct variable, 2 = fix speed, 3 = pressure, 4 = flow, 5 = supply slave, 6 = exhaust slave. | UInt16 | - | 1 | R |
| 223 | 1 | Supply engineering unit 3x0223. 0 = %, 1 = Pa, 2 = l/s. | UInt16 | - | 1 | R |
| 224 | 1 | Exhaust engineering unit 3x0224. 0 = %, 1 = Pa, 2 = l/s. | UInt16 | - | 1 | R |
| 225 | 1 | Temperature control mode 3x0225. 0 = supply, 1 = room cascade, 2 = return cascade, 3 = room/supply changeover, 4 = return/supply changeover, 5 = room, 6 = return. | UInt16 | - | 1 | R |
| 226 | 1 | Temperature setpoint selector 3x0226. 0 = heating + dead zone, 1 = heating/cooling, 2 = setpoint + half dead zone, 3 = cooling - dead zone. | UInt16 | - | 1 | R |
| 227 | 1 | Summer/winter compensation temperature 3x0227. 0 = no, 1 = yes. | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Siemens "Climatix - Modbus communication, slave mode - Reference addresses for Climatix AHU application V3.3x", CB1Y3961en, 2017-11-17 (Building Technologies). Copy read: covent.no/wp-content/uploads/2021/05/climatix_ahu_modbus_reference-addresses_y3961en.pdf, SHA-256 1f822b6d736ed28f8173ebdc6d9d87949df7d3cf8d0287cf2564e90d6e26b948. The device is a Climatix POL638/POL687 controller running the standard AHU application V3.3x, the controller inside many OEM air handling units; the map is the application's, so it is fixed per application version, not per installation. Transport: Modbus TCP, port 502 - the companion integration guide CB1J3960en 2.5 states "Modbus TCP in Climatix uses the TCP port 502. This port number is not changeable", and its 3.3 (Commission internal Modbus TCP, step 2: "This has no influence for Modbus TCP") is why the unit id here is only a placeholder. Register numbers are the document's reference addresses (3x0072, 4x0020...); 3.1 states that all address types start at 1 and that a master starting at 0 must subtract 1, so the seed is one_based and stores the printed numbers. Rows marked "(factor 10)" carry scale 0.1. All ranges are printed as "-x.y - +x.y", so no min/max is transcribed as a value. Omitted by scope: the coil status block, the input states 1x0001...1x0053 (duplicated by 3x0005...3x0008), the bit legends of 3x0017...3x0037, the bit-coded 4x0001 and 4x0015...4x0019, the setpoint rows 4x0060...4x0089 and 4x0092...4x0109, 4x0111/4x0112, the trend rows 4x0120...4x0129, the PID tables from 4x0219, the manual-override block 4x0911 and up, and input registers 3x0229 plus the factor-1 energy copies 3x0240...3x0248 and the supply/exhaust fan blocks 3x0251...3x0280.