Climatix POL638 / POL687 with AHU application V3.3x Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
11
General status (word 1)
3x0001. Bit 0 alarm class danger (A), 1 alarm class critical (A), 2 alarm class low (B), 3 alarm class warning (C), 8 manual control active, 9 summer mode, 10 communication test pulse, 11 preheating heating register, 12 preheating extra heating register, 14 actual control mode temperature room, 15 actual control mode temperature exhaust.
Binary-1R
21
General status (word 2)
3x0002. Bit 0/1 actual control mode humidity room/supply; the remaining bits are reserved.
Binary-1R
31
General status (word 3)
3x0003. Reserved bits of the general status block.
Binary-1R
41
General status (word 4)
3x0004. Reserved bits of the general status block.
Binary-1R
51
Digital inputs (word 1)
3x0005. Bit 0 emergency stop, 1 external control 1, 2 external control 2, 3 summer/winter changeover, 4 alarm acknowledge, 8 auxiliary input.
Binary-1R
61
Digital inputs (word 2)
3x0006. Bit 0 dampers open, 1 fire dampers open, 2 fire dampers closed, 4 supply fan feedback, 5 exhaust fan feedback.
Binary-1R
71
Digital inputs (word 3)
3x0007. Reserved bits of the digital-input block.
Binary-1R
81
Digital inputs (word 4)
3x0008. Reserved bits of the digital-input block.
Binary-1R
91
Digital outputs (word 1)
3x0009. Bit 0 supply damper, 1 extract damper, 2 fire damper, 4 supply fan running, 5 supply fan off, 6/7/8 supply fan stage 1/2/3, 9 exhaust fan running, 10 exhaust fan off, 11/12/13 exhaust fan stage 1/2/3.
Binary-1R
101
Digital outputs (word 2)
3x0010. Bit 0 cooling pump, 1 cooling DX off, 2/3/4 cooling DX stage 1/2/3, 6 heating recovery pump/command, 8 heating pump, 10 electrical heating off, 11/12/13 electrical heating stage 1/2/3.
Binary-1R
111
Digital outputs (word 3)
3x0011. Bit 0 extra cooling (2) pump, 1 extra cooling (2) DX off, 2/3/4 extra cooling (2) DX stage 1/2/3, 6 extra heating (2) pump, 8 extra electrical heating (2) off, 9/10/11 extra electrical heating (2) stage 1/2/3.
Binary-1R
121
Digital outputs (word 4)
3x0012. Reserved bits of the digital-output block.
Binary-1R
131
Alarms (word 1)
3x0013. Alarm bits of the AHU application (0 = normal, 1 = alarm).
Binary-1R
141
Alarms (word 2)
3x0014. Alarm bits of the AHU application (0 = normal, 1 = alarm).
Binary-1R
151
Alarms (word 3)
3x0015. Alarm bits of the AHU application (0 = normal, 1 = alarm).
Binary-1R
161
Alarms (word 4)
3x0016. Alarm bits of the AHU application (0 = normal, 1 = alarm).
Binary-1R
381
Heat recovery damper output signal
3x0038. Output signal 0...100 %.
UInt16%1R
391
Heat recovery damper recovery
3x0039. Actual recovery degree 0...100 %.
UInt16%1R
401
Heating output signal
3x0040. Output signal 0...100 %.
UInt16%1R
411
Heating pump command
3x0041. 0 = off, 1 = on.
UInt16-1R
421
Electrical heating output signal
3x0042. Output signal 0...100 %.
UInt16%1R
431
Electrical heating command
3x0043. 0 = off, 1 = stage 1, 2 = stage 2, 3 = stage 3.
UInt16-1R
441
Cooling 2 output signal
3x0044. Output signal 0...100 %.
UInt16%1R
451
Cooling 2 pump command
3x0045. 0 = off, 1 = on.
UInt16-1R
461
Cooling 2 DX command
3x0046. 0 = off, 1...3 = stage 1...3.
UInt16-1R
471
Heating 2 output signal
3x0047. Output signal 0...100 %.
UInt16%1R
481
Heating 2 pump command
3x0048. 0 = off, 1 = on.
UInt16-1R
491
Electrical heating 2 output signal
3x0049. Output signal 0...100 %.
UInt16%1R
501
Electrical heating 2 command
3x0050. 0 = off, 1...3 = stage 1...3.
UInt16-1R
521
Humidifier output signal
3x0052. Output signal 0...100 %.
UInt16%1R
531
Humidifier command
3x0053. 0 = off, 1 = on.
UInt16-1R
541
Humidifier pump command
3x0054. 0 = off, 1 = on.
UInt16-1R
551
Actual dehumidity value
3x0055. 0...100 %.
UInt16%1R
571
Auxiliary operation mode output
3x0057. 0 = off, 1 = on.
UInt16-1R
581
Auxiliary time switch program output
3x0058. 0 = off, 1 = on.
UInt16-1R
591
Auxiliary analog output fan
3x0059. 0...100 %.
UInt16%1R
601
Alarm output 1
3x0060. 0 = normal, 1 = alarm.
UInt16-1R
611
Alarm output 2
3x0061. 0 = normal, 1 = alarm.
UInt16-1R
621
Supply filter pressure
3x0062. Supply filter differential pressure in Pa.
UInt16Pa1R
631
Exhaust filter pressure
3x0063. Exhaust filter differential pressure in Pa.
UInt16Pa1R
641
Actual air quality compensation
3x0064. 0...100 %.
UInt16%1R
651
Actual fan cooling value
3x0065. 0...100 %.
UInt16%1R
661
Actual fan heating value
3x0066. 0...100 %.
UInt16%1R
671
Actual fan compensation temperature
3x0067. 0...100 %.
UInt16%1R
681
Actual fan compensation humidity
3x0068. 0...100 %.
UInt16%1R
691
Actual summer compensation fan
3x0069. 0...100 %.
UInt16%1R
701
Actual winter compensation fan
3x0070. 0...100 %.
UInt16%1R
711
Actual operating state
3x0071. 0 = not used, 1 = configuration, 2 = fire, 3 = alarm class 0, 4 = emergency stop, 5 = alarm class 1, 6 = fire-damper test, 7 = manual control, 8 = external control, 9 = room unit, 10 = OSSTP, 11 = unoccupied heating/cooling, 12 = free cooling, 13 = BMS control, 14 = TSP control, 15 = temperature test, 16 = calendar.
UInt16-1R
721
Outside air temperature
3x0072. Signed word, factor 10.
Int16°C0.1R
731
Supply air temperature
3x0073. Signed word, factor 10.
Int16°C0.1R
741
Heating frost temperature
3x0074. Signed word, factor 10.
Int16°C0.1R
751
Actual room temperature
3x0075. Signed word, factor 10.
Int16°C0.1R
761
Exhaust air temperature
3x0076. Signed word, factor 10.
Int16°C0.1R
771
Extract air temperature
3x0077. Signed word, factor 10.
Int16°C0.1R
781
Heat recovery supply air temperature
3x0078. Signed word, factor 10.
Int16°C0.1R
791
Heat recovery water temperature
3x0079. Signed word, factor 10.
Int16°C0.1R
801
Supply air temperature 2
3x0080. Signed word, factor 10.
Int16°C0.1R
811
Heating 2 frost temperature
3x0081. Signed word, factor 10.
Int16°C0.1R
821
Auxiliary temperature
3x0082. Signed word, factor 10.
Int16°C0.1R
841
Outside air relative humidity
3x0084. 0...100 %rH.
UInt16%1R
851
Outside air absolute humidity
3x0085. Factor 10.
Int16g/kg0.1R
861
Outside air enthalpy
3x0086. Factor 10.
Int16kJ/kg0.1R
871
Supply air relative humidity
3x0087. 0...100 %rH.
UInt16%1R
881
Supply air absolute humidity
3x0088. Factor 10.
Int16g/kg0.1R
891
Supply air enthalpy
3x0089. Factor 10.
Int16kJ/kg0.1R
901
Room relative humidity
3x0090. 0...100 %rH.
UInt16%1R
911
Room absolute humidity
3x0091. Factor 10.
Int16g/kg0.1R
921
Room enthalpy
3x0092. Factor 10.
Int16kJ/kg0.1R
931
Dew point
3x0093. Factor 10.
Int16°C0.1R
951
Supply air flow
3x0095. Supply air flow in l/s.
UInt16l/s1R
961
Exhaust air flow
3x0096. Exhaust air flow in l/s.
UInt16l/s1R
971
Supply air pressure
3x0097. Supply duct pressure in Pa.
UInt16Pa1R
981
Exhaust air pressure
3x0098. Exhaust duct pressure in Pa.
UInt16Pa1R
991
Heat recovery frost pressure
3x0099. Heat-recovery frost protection pressure in Pa.
UInt16Pa1R
1011
Air quality
3x0101. Air-quality sensor value in ppm.
UInt16ppm1R
1021
External setpoint
3x0102. External setpoint, factor 10.
Int16°C0.1R
1041
Actual heating setpoint, main
3x0104. Depends on the actual control mode; factor 10.
Int16°C0.1R
1051
Actual cooling setpoint, main
3x0105. Depends on the actual control mode; factor 10.
Int16°C0.1R
1061
Actual supply heating setpoint
3x0106. Used with cascade control; factor 10.
Int16°C0.1R
1071
Actual supply cooling setpoint
3x0107. Used with cascade control; factor 10.
Int16°C0.1R
1081
Actual humidity setpoint, main
3x0108. Factor 10; %rH or g/kg depending on configuration.
UInt16%0.1R
1091
Actual dehumidity setpoint, main
3x0109. Factor 10; %rH or g/kg depending on configuration.
UInt16%0.1R
1101
Actual supply humidity setpoint
3x0110. Cascade control; factor 10.
UInt16%0.1R
1111
Actual supply dehumidity setpoint
3x0111. Cascade control; factor 10.
UInt16%0.1R
1121
Actual supply fan setpoint
3x0112. %, Pa or l/s depending on the configured engineering unit.
UInt16%1R
1131
Actual exhaust fan setpoint
3x0113. %, Pa or l/s depending on the configured engineering unit.
UInt16%1R
1151
Actual summer compensation temperature
3x0115. Factor 10.
Int16°C0.1R
1161
Actual winter compensation temperature
3x0116. Factor 10.
Int16°C0.1R
1171
Heat recovery efficiency
3x0117. 0...100 %.
UInt16%1R
1181
Cooling recovery (MECH) active
3x0118. 0 = passive, 1 = active.
UInt16-1R
1201
Energy actual power
3x0120. Factor 10.
Int16W0.1R
1211
Energy average power
3x0121. Factor 10.
Int16W0.1R
1221
Energy operating hours
3x0122. Factor 10.
Int16h0.1R
1231
Energy partial
3x0123. Factor 10.
Int16kWh0.1R
1241
Energy total
3x0124. Factor 10.
Int16kWh0.1R
1251
Modbus communication alarm
3x0125. 0 = OK, 1 = alarm.
UInt16-1R
2001
Actual room unit mode
3x0200. 0 = auto, 1 = comfort, 2 = standby, 3 = economy, 4 = off.
UInt16-1R
2101
Actual room unit setpoint
3x0210. Factor 10.
Int16°C0.1R
2111
Room unit temperature
3x0211. Factor 10.
Int16°C0.1R
2121
Room unit 2 temperature
3x0212. Factor 10.
Int16°C0.1R
2131
Room temperature
3x0213. Factor 10.
Int16°C0.1R
2141
Room 2 temperature
3x0214. Factor 10.
Int16°C0.1R
2201
Time switch type
3x0220. 0 = none, 1 = step, 2 = step + temperature.
UInt16-1R
2211
Time switch number of steps
3x0221. 0 = 1 step, 1 = 2 steps, 2 = 3 steps.
UInt16-1R
2221
Fan control mode
3x0222. 0 = direct, 1 = direct variable, 2 = fix speed, 3 = pressure, 4 = flow, 5 = supply slave, 6 = exhaust slave.
UInt16-1R
2231
Supply engineering unit
3x0223. 0 = %, 1 = Pa, 2 = l/s.
UInt16-1R
2241
Exhaust engineering unit
3x0224. 0 = %, 1 = Pa, 2 = l/s.
UInt16-1R
2251
Temperature control mode
3x0225. 0 = supply, 1 = room cascade, 2 = return cascade, 3 = room/supply changeover, 4 = return/supply changeover, 5 = room, 6 = return.
UInt16-1R
2261
Temperature setpoint selector
3x0226. 0 = heating + dead zone, 1 = heating/cooling, 2 = setpoint + half dead zone, 3 = cooling - dead zone.
UInt16-1R
2271
Summer/winter compensation temperature
3x0227. 0 = no, 1 = yes.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Siemens "Climatix - Modbus communication, slave mode - Reference addresses for Climatix AHU application V3.3x", CB1Y3961en, 2017-11-17 (Building Technologies). Copy read: covent.no/wp-content/uploads/2021/05/climatix_ahu_modbus_reference-addresses_y3961en.pdf, SHA-256 1f822b6d736ed28f8173ebdc6d9d87949df7d3cf8d0287cf2564e90d6e26b948. The device is a Climatix POL638/POL687 controller running the standard AHU application V3.3x, the controller inside many OEM air handling units; the map is the application's, so it is fixed per application version, not per installation. Transport: Modbus TCP, port 502 - the companion integration guide CB1J3960en 2.5 states "Modbus TCP in Climatix uses the TCP port 502. This port number is not changeable", and its 3.3 (Commission internal Modbus TCP, step 2: "This has no influence for Modbus TCP") is why the unit id here is only a placeholder. Register numbers are the document's reference addresses (3x0072, 4x0020...); 3.1 states that all address types start at 1 and that a master starting at 0 must subtract 1, so the seed is one_based and stores the printed numbers. Rows marked "(factor 10)" carry scale 0.1. All ranges are printed as "-x.y - +x.y", so no min/max is transcribed as a value. Omitted by scope: the coil status block, the input states 1x0001...1x0053 (duplicated by 3x0005...3x0008), the bit legends of 3x0017...3x0037, the bit-coded 4x0001 and 4x0015...4x0019, the setpoint rows 4x0060...4x0089 and 4x0092...4x0109, 4x0111/4x0112, the trend rows 4x0120...4x0129, the PID tables from 4x0219, the manual-override block 4x0911 and up, and input registers 3x0229 plus the factor-1 energy copies 3x0240...3x0248 and the supply/exhaust fan blocks 3x0251...3x0280.