  "spec_version": 1,
  "slug": "siemens-rdf302",
  "manufacturer": "Siemens",
  "model": "RDF302 / RDF302.B / RDF302/VB room thermostats",
  "category": "HVAC controller",
  "supplier_url": "https://support.industry.siemens.com/cs/document/109789179",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "one_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [
    {
      "address": 1001,
      "count": 1,
      "name": "Room operating mode: state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 2. 1 = Comfort, 3 = Economy, 4 = Protection."
    },
    {
      "address": 1002,
      "count": 1,
      "name": "Fan output",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 3. 0 = fan off, 33 = low, 66 = mid, 100 = high."
    },
    {
      "address": 1003,
      "count": 1,
      "name": "Room temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "R",
      "description": "Object 4. Value x 50; 0xFFFF = out of service."
    },
    {
      "address": 1004,
      "count": 1,
      "name": "Room temperature: current setpoint",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "R",
      "description": "Object 5. Value x 50; range 5...40 degC, 4 = OFF."
    },
    {
      "address": 1005,
      "count": 1,
      "name": "Heating output",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 6. 0...100."
    },
    {
      "address": 1006,
      "count": 1,
      "name": "Cooling output",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 7. 0...100."
    },
    {
      "address": 1007,
      "count": 1,
      "name": "Electric heater output",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 8. 0...100."
    },
    {
      "address": 1008,
      "count": 1,
      "name": "X1 input (temperature)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "R",
      "description": "Object 10. Value x 50; 0...49 degC, 0xFFFF = out of service."
    },
    {
      "address": 1009,
      "count": 1,
      "name": "X2 input (temperature)",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "R",
      "description": "Object 11. Value x 50; 0...49 degC, 0xFFFF = out of service."
    },
    {
      "address": 1010,
      "count": 1,
      "name": "Fan operation (0 = auto / 1 = manual)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 12."
    },
    {
      "address": 1011,
      "count": 1,
      "name": "X1 input (digital)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 13. 0 = OFF, 1 = ON."
    },
    {
      "address": 1012,
      "count": 1,
      "name": "X2 input (digital)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 14. 0 = OFF, 1 = ON."
    },
    {
      "address": 1100,
      "count": 10,
      "name": "Fault information",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Object 9. 10 registers, max 20 characters; the default fault text is selected by the active alarm (condensation, fault input 1/2, dirty filter)."
    }
  ],
  "holding_registers": [
    {
      "address": 101,
      "count": 1,
      "name": "Room operating mode: preselection",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 15. 1 = Comfort, 3 = Economy, 4 = Protection; default Comfort."
    },
    {
      "address": 102,
      "count": 1,
      "name": "Fan command value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 16. 0 = auto, 33 = low, 66 = mid, 100 = high; default 0."
    },
    {
      "address": 103,
      "count": 1,
      "name": "Room temperature: comfort setpoint",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 17. Value x 50; 5...40 degC."
    },
    {
      "address": 104,
      "count": 1,
      "name": "Outside temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 18. Value x 50; 0...49 degC."
    },
    {
      "address": 105,
      "count": 1,
      "name": "Room operating mode: window state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 19. 0 = close (default), 1 = open."
    },
    {
      "address": 106,
      "count": 1,
      "name": "Enable electric heater",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 20. 0 = disable, 1 = enable."
    },
    {
      "address": 107,
      "count": 1,
      "name": "Heating/cooling changeover",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 21. 0 = cooling, 1 = heating."
    },
    {
      "address": 108,
      "count": 1,
      "name": "Button lock command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 22. 0 = unlock, 1 = lock buttons (+/-) only, 2 = lock fan button only, 3 = lock operating button only, 4 = lock all buttons."
    },
    {
      "address": 109,
      "count": 1,
      "name": "Plant type application",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 23. 0 = NONE, 1 = 2P, 2 = 2P3P, 3 = 2PEL, 4 = 4P."
    },
    {
      "address": 1,
      "count": 1,
      "name": "P01 control sequence",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 28. 0 = heating only, 1 = cooling only, 2 = manual heating or cooling, 3 = auto changeover, 4 = heating and cooling."
    },
    {
      "address": 2,
      "count": 1,
      "name": "P02 operating mode button function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 29. 1 = Comfort/Protection, 2 = Comfort/Economy/Protection; factory setting 1."
    },
    {
      "address": 4,
      "count": 1,
      "name": "P04 unit of the temperature display",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 30 (the document lists no P03 object). 0 = degC, 1 = degF; factory setting 0 (degC)."
    },
    {
      "address": 5,
      "count": 1,
      "name": "P05 sensor calibration of the built-in sensor",
      "data_type": "Int16",
      "units": "K",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 31. Value x 50; -3...3 K, factory setting 0."
    },
    {
      "address": 6,
      "count": 1,
      "name": "P06 standard temperature display",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 32. 0 = room temperature, 1 = setpoint; factory setting 0."
    },
    {
      "address": 7,
      "count": 1,
      "name": "P07 additional user information",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 33. 0 = no display, 1 = temperature in degC/degF, 2 = outside temperature, 3 = time of day (12 h), 4 = time of day (24 h); factory setting 0."
    },
    {
      "address": 8,
      "count": 1,
      "name": "P08 comfort basic setpoint",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 34. Value x 50; factory setting 21 degC."
    },
    {
      "address": 9,
      "count": 1,
      "name": "P09 minimum setpoint limitation in Comfort",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 35. Value x 50; 5...40 degC, factory setting 5 degC."
    },
    {
      "address": 10,
      "count": 1,
      "name": "P10 maximum setpoint limitation in Comfort",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 36. Value x 50; 5...40 degC, factory setting 35 degC."
    },
    {
      "address": 11,
      "count": 1,
      "name": "P11 setpoint of heating in Economy",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 37. Value x 50; OFF or 5 degC...cooling economy setpoint, factory setting 15 degC."
    },
    {
      "address": 12,
      "count": 1,
      "name": "P12 setpoint of cooling in Economy",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.02,
      "offset": 0,
      "access": "RW",
      "description": "Object 38. Value x 50; OFF or heating economy setpoint...40 degC, factory setting 30 degC."
    },
    {
      "address": 13,
      "count": 1,
      "name": "P13 electrical heater in cooling mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 39. 0 = disabled, 1 = enabled; factory setting ON."
    },
    {
      "address": 14,
      "count": 1,
      "name": "P14 key lock",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Object 40. 0 = disabled (factory setting), 1 = auto lock, 2 = manual lock."
    }
  ],
  "combined_registers": [],
  "notes": "Source: Siemens \"RDF302, RDF302/VB, RDF302.B - Flush-mounted room thermostats with RS485 Modbus communications - Basic documentation\", CE1P3079en, edition 1.5, 2020-12-01, 66 pages. Copy read: mekonsis.com.tr/class/INNOVAEditor/assets/pdf/RDF302.pdf, SHA-256 d26920751e9aebd2fd74b81b06492ca2e9faa16acd97b4c5a4366e48983bc63a; the sipatec.rs mirror formerly cited here now serves only the 18-page data sheet CE1N3079en. The RDF302 is a room thermostat that also drives fan coil and heat pump plants (2-pipe, 2-pipe with electric heater, 4-pipe, compressor applications). Factory frame, 3.11: device address 1 (P81), baud rate 19200 bps (P68) and parity even (P70); 3.11 states the device uses \"Modbus RTU mode as per the Modbus specification\", which fixes 8 data bits and one stop bit at that parity. Register numbers are the \"Address (Decimal)\" column of the communication-object table 3.12.2, printed per area starting at 1 (object 28 \"P01\" at 0001, the first input object at 1001); the document states no address base, so one_based is the declared convention and the client subtracts one for the PDU address (a 0-based master reads P01 at wire address 0). The \"Special Process\" column prints x50 for every temperature row, the 0.02 factor used here. Objects 1 (system time, four packed registers) and 24...27 (four 10-register Ascii fault texts) are omitted as packed or text-only blocks. The expert-level parameters are omitted by scope, not by doubt: 3.12.2 pairs each of them with an address (object 41 \"P30\" at 0030 through object 74 \"P81\" at 0081, with P46 at 0182), while the descriptive table 3.13.4 is the one whose name column drifts, so no description is carried from it. That is where P68 (0068), P70 (0070) and P81 (0081) appear in the document."
}