A1000 (CIMR-A) high performance vector control drive Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 31
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1 | 1 | Operation commands and multi-function inputs 0001H. bit 0 forward run (H5-12 = 0) or run (H5-12 = 1), bit 1 reverse run (H5-12 = 0) or forward/reverse (H5-12 = 1), bit 2 external fault EF0, bit 3 fault reset, bits 4-11 multi-function inputs 1-8, bits 12-15 reserved. Set unused bits to 0. | Hex | - | 1 | RW |
| 2 | 1 | Frequency reference 0002H. Units are determined by o1-03: 0.01 Hz at o1-03 = 0 (the factory default in V/f, V/f w/PG, OLV, CLV and OLV/PM), 0.01 % of the maximum output frequency at o1-03 = 1, min-1 at o1-03 = 2 and user-set units at o1-03 = 3 (o1-10/o1-11). The factor shown assumes o1-03 = 0. | UInt16 | Hz | 0.01 | RW |
| 3 | 1 | Output voltage gain 0003H. 20 to 2000 (2.0 % to 200.0 %), default when powered on 1000 (100.0 %). | UInt16 | % | 0.1 | RW |
| 4 | 1 | Torque reference / torque limit 0004H. 0.1 % units, signed; usable only if torque control is enabled. | Int16 | % | 0.1 | RW |
| 5 | 1 | Torque compensation 0005H. 0.1 % units, signed; usable only if torque control is enabled. | Int16 | % | 0.1 | RW |
| 6 | 1 | PID target 0006H. 0.01 % units, signed. | Int16 | % | 0.01 | RW |
| 7 | 1 | Analog output terminal FM setting 0007H. 10 V / 4000H, i.e. the value 4000 corresponds to 10 V at terminal FM. | UInt16 | - | 1 | RW |
| 8 | 1 | Analog output terminal AM setting 0008H. 10 V / 4000H, i.e. the value 4000 corresponds to 10 V at terminal AM. | UInt16 | - | 1 | RW |
| 9 | 1 | Settings for multi-function digital outputs 0009H. bit 0 M1-M2, bit 1 M3-M4, bit 2 M5-M6, bits 3-5 reserved, bit 6 enables the function in bit 7, bit 7 fault contact output MA/MB-MC, bits 8-15 reserved. | Hex | - | 1 | RW |
| 10 | 1 | Pulse output terminal MP setting 000AH. 1 Hz units, setting range 0 to 32000. | UInt16 | Hz | 1 | RW |
| 15 | 1 | Control selection setting 000FH. bit 1 PID setpoint input, bit 2 torque reference/torque limit input, bit 3 torque compensation input, bits 12-15 enable terminal S5-S8 input for broadcast data; other bits reserved. | Hex | - | 1 | RW |
| 27 | 1 | Analog monitor option AO-A3 output 1 001BH. 10 V / 4000H. | UInt16 | - | 1 | RW |
| 28 | 1 | Analog monitor option AO-A3 output 2 001CH. 10 V / 4000H. | UInt16 | - | 1 | RW |
| 29 | 1 | Digital output option DO-A3 output 001DH. Binary output pattern of the DO-A3 option card. | Hex | - | 1 | RW |
| 32 | 1 | Drive status 1 0020H. bit 0 during run, bit 1 during reverse, bit 2 drive ready, bit 3 fault, bit 4 data setting error, bit 5 M1-M2, bit 6 M3-M4, bit 7 M5-M6, bit E ComRef enabled, bit F ComCtrl enabled. | Hex | - | 1 | R |
| 33 | 1 | Fault contents 1 0021H. Grouped active faults: bit 0 overcurrent/ground fault, bit 1 drive overheat warning, bit 2 drive overload, bit 3 overheat 1/2, bit 4 braking fault, bit 6 PID feedback loss, bit 7 external fault, bit 8 CPF hardware fault, bit 9 motor overload/overtorque/undertorque, bit A PG/overspeed/deviation, bit B main circuit undervoltage, bit C DC bus undervoltage, bit D phase loss, bit E communication error, bit F operator connection fault. | Hex | - | 1 | R |
| 34 | 1 | Data link status 0022H. bit 0 writing data or switching motors, bit 3 upper or lower limit error, bit 4 data conformity error, bit 5 writing to EEPROM, bit 6 0 = write into EEPROM / 1 = write in RAM only (only when H5-17 = 1). | Hex | - | 1 | R |
| 35 | 1 | Frequency reference (monitor) 0023H. Units are determined by o1-03 (0.01 Hz at o1-03 = 0, which is the factory default in the usual control modes). | UInt16 | Hz | 0.01 | R |
| 36 | 1 | Output frequency (monitor) 0024H. Units are determined by o1-03 (0.01 Hz at o1-03 = 0). | UInt16 | Hz | 0.01 | R |
| 37 | 1 | Output voltage reference 0025H. 0.1 V units; the displayed units are determined by H5-10. | UInt16 | V | 0.1 | R |
| 38 | 1 | Output current 0026H. 0.1 A units. | UInt16 | A | 0.1 | R |
| 41 | 1 | Fault contents 2 0029H. bit 0 output short circuit or IGBT fault, bit 1 ground fault, bit 2 input phase loss, bit 3 output phase loss, bit 4 braking resistor overheat, bit 6 motor overheat (PTC input). | Hex | - | 1 | R |
| 42 | 1 | Alarm contents 1 002AH. bit 2 forward/reverse run command input error, bit 3 baseblock, bit 4 overtorque detection 1, bit 5 heatsink overheat, bit 6 drive overheat warning, bit 7 undervoltage, bit 8 internal fan fault, bit 9 communication error, bit A option communication error, bit B undertorque detection, bit C motor overheat, bit D PID feedback loss, bit F serial communication transmission error. | Hex | - | 1 | R |
| 43 | 1 | Input terminal status 002BH. bit 0 terminal S1 closed through bit 7 terminal S8 closed. | Hex | - | 1 | R |
| 44 | 1 | Drive status 2 002CH. bit 0 during run, bit 1 zero speed, bit 2 speed agree, bit 3 user speed agree, bit 4 frequency detection 1, bit 5 frequency detection 2, bit 6 drive ready, bit 7 during undervoltage, bit 8 during baseblock, bit 9 frequency reference from operator, bit A run command from operator, bit B over/undertorque detection, bit C frequency reference loss, bit D during fault restart, bit E fault, bit F communication timeout. | Hex | - | 1 | R |
| 45 | 1 | Output terminal status 002DH. bit 0 M1-M2, bit 1 M3-M4, bit 2 M5-M6, bit 7 fault contact output MA/MB-MC. | Hex | - | 1 | R |
| 47 | 1 | Frequency reference bias (Up/Down 2) 002FH. 0.1 % units. | Int16 | % | 0.1 | R |
| 49 | 1 | DC bus voltage 0031H. 1 Vdc units. | UInt16 | V | 1 | R |
| 50 | 1 | Torque reference (U1-09) 0032H. 1 % units. | Int16 | % | 1 | R |
| 52 | 1 | Product code 1 0034H. ASCII product type, A0 for A1000. | Ascii | - | 1 | R |
| 53 | 1 | Product code 2 0035H. ASCII region code. | Ascii | - | 1 | R |
| 56 | 1 | PID feedback 0038H. 0.1 % units, unsigned; 100 % corresponds to the maximum output frequency. | UInt16 | % | 0.1 | R |
| 57 | 1 | PID input 0039H. 0.1 % units, signed; 100 % corresponds to the maximum output frequency. | Int16 | % | 0.1 | R |
| 61 | 1 | Communications error contents 003DH. bit 0 CRC error, bit 1 data length error, bit 3 parity error, bit 4 overrun error, bit 5 framing error, bit 6 timeout. The contents are saved until the fault is reset. | Hex | - | 1 | R |
| 62 | 1 | Output frequency in min-1 003EH. Output frequency in min-1; the correct motor pole count must be set in E2-04, E4-04 or E5-04 for the value to be correct. | UInt16 | rpm | 1 | R |
| 63 | 1 | Output frequency in percent 003FH. 0.01 % units, 100 % = maximum output frequency. | UInt16 | % | 0.01 | R |
| 75 | 1 | Drive status (U1-12) 004BH. bit 0 during run, bit 1 during zero speed, bit 2 during reverse run, bit 3 during fault reset signal input, bit 4 during speed agree, bit 5 drive ready, bit 6 minor fault, bit 7 fault, bit 8 during operation error, bit 9 during momentary power loss, bit A motor 2 selected, bit E ComRef/NetRef status, bit F ComCtrl/NetCtrl status. | Hex | - | 1 | R |
| 127 | 1 | Minor fault code 007FH. Code of the active minor fault, see the alarm register contents in the manual. | UInt16 | - | 1 | R |
| 152 | 1 | Cumulative operation time, high part (U4-01) 0098H. High part of U4-01: the example in the manual shows 12345 h stored as 0098H = 1234 and 0099H = 5, so hours = 0098H * 10 + 0099H. | UInt16 | h | 10 | R |
| 153 | 1 | Cumulative operation time, low digit (U4-01) 0099H. Last digit of U4-01; hours = 0098H * 10 + 0099H. | UInt16 | h | 1 | R |
| 154 | 1 | Cooling fan operation time, high part (U4-03) 009AH. High part of U4-03; hours = 009AH * 10 + 009BH (same split as U4-01). | UInt16 | h | 10 | R |
| 155 | 1 | Cooling fan operation time, low digit (U4-03) 009BH. Last digit of U4-03; hours = 009AH * 10 + 009BH. | UInt16 | h | 1 | R |
| 171 | 1 | Drive rated current 00ABH. The unit depends on the model: 0.01 A for CIMR-A2A0004 to 2A0040 and A4A0002 to 4A0023, 0.1 A for A2A0056 to 2A0312 and A4A0031 to 4A0675, 1 A for A4A0930 to 4A1200. No single factor is applied. | UInt16 | A | 1 | R |
| 172 | 1 | Motor speed in min-1 (U1-05) 00ACH. Motor speed in min-1; the correct motor pole count must be set in E2-04, E4-04 or E5-04. | UInt16 | rpm | 1 | R |
| 173 | 1 | Motor speed in percent (U1-05) 00ADH. 0.01 % units, 100 % = maximum output frequency. | UInt16 | % | 0.01 | R |
| 176 | 1 | Option code connected to CN5-A 00B0H. ASCII option code, for example AI-A3 = 0003H, AO-A3 = 0004H, DI-A3 = 0001H, DO-A3 = 0002H, PG-B3 = 0011H, PG-X3 = 0012H, SI-N3 = 534EH, SI-P3 = 5350H, SI-ET3 = 1004H. | Hex | - | 1 | R |
| 178 | 1 | Option code connected to CN5-B 00B2H. ASCII option code, same encoding as CN5-A. | Hex | - | 1 | R |
| 179 | 1 | Option code connected to CN5-C 00B3H. ASCII option code, same encoding as CN5-A. | Hex | - | 1 | R |
| 181 | 1 | Frequency reference after soft-starter in min-1 (U1-16) 00B5H. Output of the accel/decel ramp generator in min-1. | UInt16 | rpm | 1 | R |
| 182 | 1 | Frequency reference after soft-starter in percent (U1-16) 00B6H. 0.01 % units, 100 % = maximum output frequency. | UInt16 | % | 0.01 | R |
| 183 | 1 | Frequency reference in min-1 00B7H. Frequency reference in min-1. | UInt16 | rpm | 1 | R |
| 184 | 1 | Frequency reference in percent 00B8H. 0.01 % units, 100 % = maximum output frequency. | UInt16 | % | 0.01 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
MEMOBUS/Modbus RTU on the RS-422/RS-485 port; the protocol is RTU only, the data length is fixed at 8 bits and the stop bit at 1 bit, and parity is selectable. Factory settings are H5-01 Drive Slave Address = 1F (31), H5-02 Communication Speed = 3 (9600 bps), H5-03 parity = 0 (none) and H5-06 Drive Transmit Wait Time = 5 ms; a changed baud rate, parity or slave address takes effect after a power cycle. H5-04 stopping method after a communication error defaults to 3 (alarm only). Command data 0001H-001FH is read/write, monitor data 0020H-00C3H is read-only; unused command bits must be set to 0 and reserved registers must not be written. Frequency values (0023H, 0024H, 002FH and the command frequency reference 0002H) follow o1-03: 0.01 Hz at o1-03 = 0, which is the factory default in V/f, V/f w/PG, OLV, CLV and OLV/PM control modes, 0.01 % of the maximum output frequency at o1-03 = 1, min-1 at o1-03 = 2 and user-set units at o1-03 = 3. The 0.01 Hz factors stored here assume o1-03 = 0. Register 0027H output power is left out because the manual lists no unit for it, as is 0028H torque reference (no unit given); 0032H torque reference in 1 % units is included instead. Source: Yaskawa 'AC Drive A1000 Technical Manual', manual no. SIEP C710616 27J, chapter C.1 MEMOBUS/Modbus Communication Specifications (page 553), C.4 MEMOBUS/Modbus Setup Parameters H5-01 to H5-06 (pages 555-556), C.9 MEMOBUS/Modbus Data Table - command data (page 565) and monitor data (pages 566-569), and o1-03 (page 314); PDF at https://www.yaskawa.eu.com/_downloads/download_d5120.