All devices

Schneider Electric · VFD

Altivar Machine ATV320 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
32011
ETA status word
Bit 0 ready, bit 1 switched on, bit 2 operation enabled, bit 3 fault, bit 6 switch-on inhibited.
Hex-1R
32021
RFR output frequency
Int16Hz0.1R
32031
FRH frequency reference before ramp
Int16Hz0.1R
32041
LCR motor current
UInt16A0.1R
32051
OTR motor torque
Int16%0.1R
32061
ETI extended status word
Hex-1R
32071
ULN mains voltage
UInt16V0.1R
32081
UOP motor voltage
UInt16V1R
32091
THD drive thermal state
UInt16%1R
32111
OPR motor power
Int16%1R
32311
RTH total motor operating time
UInt16h1R
32331
PTH total drive operating time
UInt16h1R
32351
TAC IGBT alarm time
UInt16s1R
32401
HMIS drive state
UInt16-1R
32411
NTJ transistor alarm counter
UInt16-1R
52021
IL1R logic input states
Hex-1R
52121
OL1R logic output states
Hex-1RW
52421
AI1C analog input 1 physical value
Int16V0.001R
52431
AI2C analog input 2 physical value
Int16V0.001R
52441
AI3C analog input 3 physical value
Int16mA0.001R
52711
AO1C analog output 1 physical value
Int16-1RW
60011
Modbus address
1 to 247, factory 1.
UInt16-1RW
60031
Modbus baud rate
24 = 4800, 28 = 9600, 32 = 19200, 36 = 38400.
UInt16-1RW
60041
Modbus format
2 = 8O1, 3 = 8E1, 4 = 8N1, 5 = 8N2.
UInt16-1RW
60051
Modbus timeout
1 to 300 = 0.1 to 30.0 s.
UInt16s0.1RW
71211
LFT last fault code
Hex-1R
71301
CIC incorrect configuration
Hex-1RW
71321
CNF network fault code
UInt16-1R
72001
DP0 fault code on last fault
Hex-1R
72101
EP0 status word on last fault
Hex-1R
72201
IP0 extended status word on last fault
Hex-1R
72301
CMP0 command word on last fault
Hex-1R
72401
LCP0 motor current on last fault
Int16A0.1R
72501
RFP0 output frequency on last fault
Int16Hz0.1R
72601
RTP0 motor operating time on last fault
UInt16h1R
72701
ULP0 supply voltage on last fault
UInt16V0.1R
72801
THP0 motor thermal state on last fault
UInt16%1R
73301
OTP0 estimated torque on last fault
Int16%0.1R
73401
TDP0 drive thermal state on last fault
UInt16%1R
73501
TJP0 estimated junction temperature on last fault
UInt16°C1R
73601
SFP0 switching frequency on last fault
UInt16Hz1R
73931
FNB fault counter
UInt16-1R
85011
CMD control word
CiA402 control word; 6 = shutdown, 15 = enable operation, 128 = fault reset.
Hex-1RW
85021
LFR frequency setpoint
Int16Hz0.1RW
86021
LFRD speed setpoint
Int16rpm1RW
86041
RFRD output speed
Int16rpm1R
86061
ERRD CiA402 fault code
Hex-1R
90011
ACC acceleration
UInt16s0.1RW
90021
DEC deceleration
UInt16s0.1RW
90211
FRO frequency reference after ramp
Int16Hz0.1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (address 1, 19200 bps, 8E1). All registers are holding registers (function code 03/06/16). The control word is 8501 (CMD) and the frequency setpoint 8502 (LFR); 9001/9002 are the acceleration and deceleration ramps. Status and measured values use the CiA402/Drivecom profile; the ETA status word bits are described in Schneider's Modbus manual.