ABB · VFD
ACS380 machinery drive (ACS380-04xS, ACS380-04xC with +L538), embedded Modbus RTU Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- Low word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1 | 1 | Control word coil OFF1_CONTROL OFF1 control: 1 = enter the OFF1 state. DCU profile: STOP. Coil reference 000001, which is the address on the wire. | Binary | - | 1 | RW |
| 2 | 1 | Control word coil OFF2_CONTROL OFF2 control: 0 = OFF2 active (coast to stop). DCU profile: START. Coil reference 000002, which is the address on the wire. | Binary | - | 1 | RW |
| 3 | 1 | Control word coil OFF3_CONTROL OFF3 control: 0 = OFF3 active (emergency ramp stop). DCU profile: Reserved. Coil reference 000003, which is the address on the wire. | Binary | - | 1 | RW |
| 4 | 1 | Control word coil INHIBIT_OPERATION 0 = operation inhibited. DCU profile: Reserved. Coil reference 000004, which is the address on the wire. | Binary | - | 1 | RW |
| 5 | 1 | Control word coil RAMP_OUT_ZERO 1 = force the ramp function generator output to zero. DCU profile: RESET. Coil reference 000005, which is the address on the wire. | Binary | - | 1 | RW |
| 6 | 1 | Control word coil RAMP_HOLD 1 = halt ramping. DCU profile: EXT2. Coil reference 000006, which is the address on the wire. | Binary | - | 1 | RW |
| 7 | 1 | Control word coil RAMP_IN_ZERO 1 = force the ramp function generator input to zero. DCU profile: RUN_DISABLE. Coil reference 000007, which is the address on the wire. | Binary | - | 1 | RW |
| 8 | 1 | Control word coil RESET 1 = fault reset if an active fault exists. DCU profile: STOPMODE_RAMP. Coil reference 000008, which is the address on the wire. | Binary | - | 1 | RW |
| 9 | 1 | Control word coil JOGGING_1 1 = run at jogging 1 speed. DCU profile: STOPMODE_EMERGENCY_RAMP. Coil reference 000009, which is the address on the wire. | Binary | - | 1 | RW |
| 10 | 1 | Control word coil JOGGING_2 1 = run at jogging 2 speed. DCU profile: STOPMODE_COAST. Coil reference 000010, which is the address on the wire. | Binary | - | 1 | RW |
| 11 | 1 | Control word coil REMOTE_CMD 0 = continue normal operation, 1 = fieldbus control enabled. DCU profile: Reserved. Coil reference 000011, which is the address on the wire. | Binary | - | 1 | RW |
| 12 | 1 | Control word coil EXT_CTRL_LOC Selects external control location EXT2 (1) or EXT1 (0). DCU profile: RAMP_OUT_ZERO. Coil reference 000012, which is the address on the wire. | Binary | - | 1 | RW |
| 13 | 1 | Control word coil USER_0 Writable control bit for application logic. DCU profile: RAMP_HOLD. Coil reference 000013, which is the address on the wire. | Binary | - | 1 | RW |
| 14 | 1 | Control word coil USER_1 Writable control bit for application logic. DCU profile: RAMP_IN_ZERO. Coil reference 000014, which is the address on the wire. | Binary | - | 1 | RW |
| 15 | 1 | Control word coil USER_2 Writable control bit for application logic. DCU profile: Reserved. Coil reference 000015, which is the address on the wire. | Binary | - | 1 | RW |
| 16 | 1 | Control word coil USER_3 Writable control bit for application logic. DCU profile: Reserved. Coil reference 000016, which is the address on the wire. | Binary | - | 1 | RW |
| 33 | 1 | Control for RO1 1 = energise relay output RO1 (10.99 bit 0). Coil reference 000033, which is the address on the wire. | Binary | - | 1 | RW |
| 34 | 1 | Control for RO2 1 = energise relay output RO2 (10.99 bit 1). Coil reference 000034, which is the address on the wire. | Binary | - | 1 | RW |
| 35 | 1 | Control for RO3 1 = energise relay output RO3 (10.99 bit 2). Coil reference 000035, which is the address on the wire. | Binary | - | 1 | RW |
| 36 | 1 | Control for RO4 1 = energise relay output RO4 (10.99 bit 3). Coil reference 000036, which is the address on the wire. | Binary | - | 1 | RW |
| 37 | 1 | Control for RO5 1 = energise relay output RO5 (10.99 bit 4). Coil reference 000037, which is the address on the wire. | Binary | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
The ACS380 has an embedded EIA-485 Modbus RTU interface on the BMIO-01 module of the standard variant ACS380-04xS and on the I/O and Modbus extension module (option +L538) of the configured variant ACS380-04xC; enable it with 58.01 Protocol enable = Modbus RTU. Factory settings of the embedded interface are node address 58.03 = 1, baud rate 58.04 = 19.2 kbps, parity/stop bits 58.05 = 8 EVEN 1, control profile 58.25 = ABB Drives, word order 58.34 = LO-HI (58.33 Addressing mode = Mode 0). The manual prints the holding registers as 4xxxx references, so 400001 (control word) is wire address 0; coils are printed as 1-based 0xxxx references that, as the manual states, match the address on the wire, so coil 000001 is wire address 1 and is stored as 1; discrete inputs are printed as 0-based 1xxxx references and are stored unchanged. Coils 17-31 are reserved in the ABB Drives profile (FB_LOCAL_CTL/REF and user bits in the DCU profile) and are left out. Holding registers 400007...400014 are Data in/out 7...14, routed to drive parameters with 58.107...58.114; drive parameters themselves are reached at 400101...465536 through 58.33 Addressing mode and are not listed because their addresses depend on that setting. Source: ABB 'ACS380 machinery control program firmware manual', code 3AXD50000029275 Rev E (EN), 2018-05-05, chapter 9 'Fieldbus control through the embedded fieldbus interface (EFB)' - parameter table pages 419-421, control/status words pages 426-431, Modbus holding register addresses page 435, function codes page 436, coils and discrete inputs pages 438-440, error code registers pages 440-441; PDF (mirror of the ABB-hosted file) at https://cdn.logic-control.com/docs/abb-drives/acs380/ACS380%20Firmware%20Manual.pdf, SHA-256 997707c980f0b515e59fd287143a8b17149778c66f87308b89a31b6e7edf92ce.