ACS380 machinery drive (ACS380-04xS, ACS380-04xC with +L538), embedded Modbus RTU Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
Control word coil OFF1_CONTROL
OFF1 control: 1 = enter the OFF1 state. DCU profile: STOP. Coil reference 000001, which is the address on the wire.
Binary-1RW
21
Control word coil OFF2_CONTROL
OFF2 control: 0 = OFF2 active (coast to stop). DCU profile: START. Coil reference 000002, which is the address on the wire.
Binary-1RW
31
Control word coil OFF3_CONTROL
OFF3 control: 0 = OFF3 active (emergency ramp stop). DCU profile: Reserved. Coil reference 000003, which is the address on the wire.
Binary-1RW
41
Control word coil INHIBIT_OPERATION
0 = operation inhibited. DCU profile: Reserved. Coil reference 000004, which is the address on the wire.
Binary-1RW
51
Control word coil RAMP_OUT_ZERO
1 = force the ramp function generator output to zero. DCU profile: RESET. Coil reference 000005, which is the address on the wire.
Binary-1RW
61
Control word coil RAMP_HOLD
1 = halt ramping. DCU profile: EXT2. Coil reference 000006, which is the address on the wire.
Binary-1RW
71
Control word coil RAMP_IN_ZERO
1 = force the ramp function generator input to zero. DCU profile: RUN_DISABLE. Coil reference 000007, which is the address on the wire.
Binary-1RW
81
Control word coil RESET
1 = fault reset if an active fault exists. DCU profile: STOPMODE_RAMP. Coil reference 000008, which is the address on the wire.
Binary-1RW
91
Control word coil JOGGING_1
1 = run at jogging 1 speed. DCU profile: STOPMODE_EMERGENCY_RAMP. Coil reference 000009, which is the address on the wire.
Binary-1RW
101
Control word coil JOGGING_2
1 = run at jogging 2 speed. DCU profile: STOPMODE_COAST. Coil reference 000010, which is the address on the wire.
Binary-1RW
111
Control word coil REMOTE_CMD
0 = continue normal operation, 1 = fieldbus control enabled. DCU profile: Reserved. Coil reference 000011, which is the address on the wire.
Binary-1RW
121
Control word coil EXT_CTRL_LOC
Selects external control location EXT2 (1) or EXT1 (0). DCU profile: RAMP_OUT_ZERO. Coil reference 000012, which is the address on the wire.
Binary-1RW
131
Control word coil USER_0
Writable control bit for application logic. DCU profile: RAMP_HOLD. Coil reference 000013, which is the address on the wire.
Binary-1RW
141
Control word coil USER_1
Writable control bit for application logic. DCU profile: RAMP_IN_ZERO. Coil reference 000014, which is the address on the wire.
Binary-1RW
151
Control word coil USER_2
Writable control bit for application logic. DCU profile: Reserved. Coil reference 000015, which is the address on the wire.
Binary-1RW
161
Control word coil USER_3
Writable control bit for application logic. DCU profile: Reserved. Coil reference 000016, which is the address on the wire.
Binary-1RW
331
Control for RO1
1 = energise relay output RO1 (10.99 bit 0). Coil reference 000033, which is the address on the wire.
Binary-1RW
341
Control for RO2
1 = energise relay output RO2 (10.99 bit 1). Coil reference 000034, which is the address on the wire.
Binary-1RW
351
Control for RO3
1 = energise relay output RO3 (10.99 bit 2). Coil reference 000035, which is the address on the wire.
Binary-1RW
361
Control for RO4
1 = energise relay output RO4 (10.99 bit 3). Coil reference 000036, which is the address on the wire.
Binary-1RW
371
Control for RO5
1 = energise relay output RO5 (10.99 bit 4). Coil reference 000037, which is the address on the wire.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

The ACS380 has an embedded EIA-485 Modbus RTU interface on the BMIO-01 module of the standard variant ACS380-04xS and on the I/O and Modbus extension module (option +L538) of the configured variant ACS380-04xC; enable it with 58.01 Protocol enable = Modbus RTU. Factory settings of the embedded interface are node address 58.03 = 1, baud rate 58.04 = 19.2 kbps, parity/stop bits 58.05 = 8 EVEN 1, control profile 58.25 = ABB Drives, word order 58.34 = LO-HI (58.33 Addressing mode = Mode 0). The manual prints the holding registers as 4xxxx references, so 400001 (control word) is wire address 0; coils are printed as 1-based 0xxxx references that, as the manual states, match the address on the wire, so coil 000001 is wire address 1 and is stored as 1; discrete inputs are printed as 0-based 1xxxx references and are stored unchanged. Coils 17-31 are reserved in the ABB Drives profile (FB_LOCAL_CTL/REF and user bits in the DCU profile) and are left out. Holding registers 400007...400014 are Data in/out 7...14, routed to drive parameters with 58.107...58.114; drive parameters themselves are reached at 400101...465536 through 58.33 Addressing mode and are not listed because their addresses depend on that setting. Source: ABB 'ACS380 machinery control program firmware manual', code 3AXD50000029275 Rev E (EN), 2018-05-05, chapter 9 'Fieldbus control through the embedded fieldbus interface (EFB)' - parameter table pages 419-421, control/status words pages 426-431, Modbus holding register addresses page 435, function codes page 436, coils and discrete inputs pages 438-440, error code registers pages 440-441; PDF (mirror of the ABB-hosted file) at https://cdn.logic-control.com/docs/abb-drives/acs380/ACS380%20Firmware%20Manual.pdf, SHA-256 997707c980f0b515e59fd287143a8b17149778c66f87308b89a31b6e7edf92ce.