PSTX softstarter (built-in Modbus RTU) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Digital input telegram: Auto mode status
0 = softstarter control through Modbus disabled, 1 = enabled. Protocol address 0000h, read with function code 01.
Binary-1R
11
Digital input telegram: Event status
0 = no active fault/warning/protection, 1 = active fault/warning/protection. Protocol address 0001h, read with function code 01.
Binary-1R
21
Digital input telegram: Ready to start
0 = a start will probably cause a fault, 1 = a start will probably not cause a fault. Protocol address 0002h, read with function code 01.
Binary-1R
31
Digital input telegram: FBT response 0
Fieldbus task response bit 0. Protocol address 0003h, read with function code 01.
Binary-1R
41
Digital input telegram: FBT response 1
Fieldbus task response bit 1. Protocol address 0004h, read with function code 01.
Binary-1R
51
Digital input telegram: FBT toggle bit
Fieldbus task toggle bit. Protocol address 0005h, read with function code 01.
Binary-1R
61
Digital input telegram: Programmable digital input 1
Status of the function set with Fieldbus DI 1. Protocol address 0006h, read with function code 01.
Binary-1R
71
Digital input telegram: Programmable digital input 2
Status of the function set with Fieldbus DI 2. Protocol address 0007h, read with function code 01.
Binary-1R
81
Digital input telegram: Programmable digital input 3
Status of the function set with Fieldbus DI 3. Protocol address 0008h, read with function code 01.
Binary-1R
91
Digital input telegram: Programmable digital input 4
Status of the function set with Fieldbus DI 4. Protocol address 0009h, read with function code 01.
Binary-1R
101
Digital input telegram: Programmable digital input 5
Status of the function set with Fieldbus DI 5. Protocol address 000Ah, read with function code 01.
Binary-1R
111
Digital input telegram: Programmable digital input 6
Status of the function set with Fieldbus DI 6. Protocol address 000Bh, read with function code 01.
Binary-1R
121
Digital input telegram: Programmable digital input 7
Status of the function set with Fieldbus DI 7. Protocol address 000Ch, read with function code 01.
Binary-1R
131
Digital input telegram: Programmable digital input 8
Status of the function set with Fieldbus DI 8. Protocol address 000Dh, read with function code 01.
Binary-1R
141
Digital input telegram: Programmable digital input 9
Status of the function set with Fieldbus DI 9. Protocol address 000Eh, read with function code 01.
Binary-1R
151
Digital input telegram: Programmable digital input 10
Status of the function set with Fieldbus DI 10. Protocol address 000Fh, read with function code 01.
Binary-1R
2561
Digital output telegram: Start
Commence a start when the signal is set. Protocol address 0100h, written with function code 15 or as control word bits.
Binary-1RW
2571
Digital output telegram: Stop
Commence a stop when the signal is negated. Protocol address 0101h, written with function code 15 or as control word bits.
Binary-1RW
2581
Digital output telegram: Fault reset
Reset signal for possible events. Protocol address 0102h, written with function code 15 or as control word bits.
Binary-1RW
2591
Digital output telegram: Auto mode
Must be set for controlling the motor from the fieldbus. Protocol address 0103h, written with function code 15 or as control word bits.
Binary-1RW
2601
Digital output telegram: Slow speed reverse
Perform slow speed reverse when the signal is set. Protocol address 0104h, written with function code 15 or as control word bits.
Binary-1RW
2611
Digital output telegram: Slow speed forward
Perform slow speed forward when the signal is set. Protocol address 0105h, written with function code 15 or as control word bits.
Binary-1RW
2621
Digital output telegram: Spare
Spare. Protocol address 0106h, written with function code 15 or as control word bits.
Binary-1RW
2631
Digital output telegram: Start 1
Start 1 if sequence start. Protocol address 0107h, written with function code 15 or as control word bits.
Binary-1RW
2641
Digital output telegram: Start 2
Start 2 if sequence start. Protocol address 0108h, written with function code 15 or as control word bits.
Binary-1RW
2651
Digital output telegram: Start 3
Start 3 if sequence start. Protocol address 0109h, written with function code 15 or as control word bits.
Binary-1RW
2661
Digital output telegram: Motor heating
Perform motor heating when the signal is set. Protocol address 010Ah, written with function code 15 or as control word bits.
Binary-1RW
2671
Digital output telegram: Stand still brake
Perform stand still brake when the signal is set. Protocol address 010Bh, written with function code 15 or as control word bits.
Binary-1RW
2681
Digital output telegram: Start reverse
Commence a reverse start when the signal is set. Protocol address 010Ch, written with function code 15 or as control word bits.
Binary-1RW
2691
Digital output telegram: Spare
Spare. Protocol address 010Dh, written with function code 15 or as control word bits.
Binary-1RW
2701
Digital output telegram: Emergency mode
Set to 1 to enable emergency mode. Protocol address 010Eh, written with function code 15 or as control word bits.
Binary-1RW
2711
Digital output telegram: FBT toggle bit
Fieldbus task toggle bit. Protocol address 010Fh, written with function code 15 or as control word bits.
Binary-1RW
2721
Digital output telegram: User defined trip
Set to 1 to trigger the user defined protection. Protocol address 0110h, written with function code 15 or as control word bits.
Binary-1RW
2731
Digital output telegram: Switch to remote control
Switch to remote control when the signal is set (rising edge triggered). Protocol address 0111h, written with function code 15 or as control word bits.
Binary-1RW
2741
Digital output telegram: Pump cleaning automatic
Perform automatic pump cleaning when the signal is set. Protocol address 0112h, written with function code 15 or as control word bits.
Binary-1RW
2751
Digital output telegram: Pump cleaning forward
Perform forward pump cleaning when the signal is set. Protocol address 0113h, written with function code 15 or as control word bits.
Binary-1RW
2761
Digital output telegram: Pump cleaning reverse
Perform reverse pump cleaning when the signal is set. Protocol address 0114h, written with function code 15 or as control word bits.
Binary-1RW
2771
Digital output telegram: K4 relay command
Set to 1 to activate the internal K4 output relay; parameter 10.4 K4 function must be Fieldbus. Protocol address 0115h, written with function code 15 or as control word bits.
Binary-1RW
2781
Digital output telegram: K5 relay command
Set to 1 to activate the internal K5 output relay; parameter 10.5 K5 function must be Fieldbus. Protocol address 0116h, written with function code 15 or as control word bits.
Binary-1RW
2791
Digital output telegram: K6 relay command
Set to 1 to activate the internal K6 output relay; parameter 10.6 K6 function must be Fieldbus. Protocol address 0117h, written with function code 15 or as control word bits.
Binary-1RW
2801
Digital output telegram: Spare
Spare. Protocol address 0118h, written with function code 15 or as control word bits.
Binary-1RW
2811
Digital output telegram: Spare
Spare. Protocol address 0119h, written with function code 15 or as control word bits.
Binary-1RW
2821
Digital output telegram: Spare
Spare. Protocol address 011Ah, written with function code 15 or as control word bits.
Binary-1RW
2831
Digital output telegram: Spare
Spare. Protocol address 011Bh, written with function code 15 or as control word bits.
Binary-1RW
2841
Digital output telegram: Spare
Spare. Protocol address 011Ch, written with function code 15 or as control word bits.
Binary-1RW
2851
Digital output telegram: Spare
Spare. Protocol address 011Dh, written with function code 15 or as control word bits.
Binary-1RW
2861
Digital output telegram: Spare
Spare. Protocol address 011Eh, written with function code 15 or as control word bits.
Binary-1RW
2871
Digital output telegram: Spare
Spare. Protocol address 011Fh, written with function code 15 or as control word bits.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Built-in Modbus RTU on terminal pair 23/24 (the DX111/DX112 expansion module shares them). Set 12.01 Com3 function = Modbus RTU slave, 12.02 FB interface connector = Modbus RTU and 12.03 Fieldbus control = On; the factory values of the communication parameters are 12.04 Fieldbus address = 0, 12.09 FB baud rate = 19200, 12.10 FB parity = Even and 12.11 FB stop bits = 1, which is the serial block above. The factory value 0 is the broadcast address, so no factory slave address in 1-247 exists to seed: unit ID 1 is a placeholder to be verified and set on site (12.04, 1-247); a change needs a power cycle or 12.02 to None and back. The document prints each address as protocol address (on the wire) and as Modicon address; protocol addresses are stored here: input telegram 0000h, status word 01FFh, control words 02FEh/02FFh, output telegram 0100h. Coils 0000h-000Fh are read with function code 01, coils 0100h-011Fh are written with function code 15 (or through the control words), holding registers are read with 03/04 and written with 06/16. Manual parameter read/write uses the fieldbus tasks and the Fieldbus AO registers, so no parameter list is included. Sources: ABB 'Fieldbus communication - Built-in Modbus RTU' 1SFC132089M0201 Rev E (2019), sections 2 (addressing), 3 (PSTX data: digital input telegram page 5, status word pages 8-9, analog input telegram page 8, digital output telegram page 11, analog output telegram page 12, control words pages 12-13); PDF at https://library.e.abb.com/public/2e8c2f04460f4143baabdfa0690de37d/1SFC132089M0201_PSTX_Internal_Modbus_RTU.pdf. The factory serial settings are from ABB 'PSTX Softstarters Installation and commissioning manual' 1SFC132081M0201 Rev Q, parameters 12.01-12.11 on pages 97-98; PDF at https://library.e.abb.com/public/18446de6f1594ca08cb3437f5dd8bdbe/1SFC132081M0201_Rev_Q.pdf.