ABB · Soft starter
PSTX softstarter (built-in Modbus RTU) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Digital input telegram: Auto mode status 0 = softstarter control through Modbus disabled, 1 = enabled. Protocol address 0000h, read with function code 01. | Binary | - | 1 | R |
| 1 | 1 | Digital input telegram: Event status 0 = no active fault/warning/protection, 1 = active fault/warning/protection. Protocol address 0001h, read with function code 01. | Binary | - | 1 | R |
| 2 | 1 | Digital input telegram: Ready to start 0 = a start will probably cause a fault, 1 = a start will probably not cause a fault. Protocol address 0002h, read with function code 01. | Binary | - | 1 | R |
| 3 | 1 | Digital input telegram: FBT response 0 Fieldbus task response bit 0. Protocol address 0003h, read with function code 01. | Binary | - | 1 | R |
| 4 | 1 | Digital input telegram: FBT response 1 Fieldbus task response bit 1. Protocol address 0004h, read with function code 01. | Binary | - | 1 | R |
| 5 | 1 | Digital input telegram: FBT toggle bit Fieldbus task toggle bit. Protocol address 0005h, read with function code 01. | Binary | - | 1 | R |
| 6 | 1 | Digital input telegram: Programmable digital input 1 Status of the function set with Fieldbus DI 1. Protocol address 0006h, read with function code 01. | Binary | - | 1 | R |
| 7 | 1 | Digital input telegram: Programmable digital input 2 Status of the function set with Fieldbus DI 2. Protocol address 0007h, read with function code 01. | Binary | - | 1 | R |
| 8 | 1 | Digital input telegram: Programmable digital input 3 Status of the function set with Fieldbus DI 3. Protocol address 0008h, read with function code 01. | Binary | - | 1 | R |
| 9 | 1 | Digital input telegram: Programmable digital input 4 Status of the function set with Fieldbus DI 4. Protocol address 0009h, read with function code 01. | Binary | - | 1 | R |
| 10 | 1 | Digital input telegram: Programmable digital input 5 Status of the function set with Fieldbus DI 5. Protocol address 000Ah, read with function code 01. | Binary | - | 1 | R |
| 11 | 1 | Digital input telegram: Programmable digital input 6 Status of the function set with Fieldbus DI 6. Protocol address 000Bh, read with function code 01. | Binary | - | 1 | R |
| 12 | 1 | Digital input telegram: Programmable digital input 7 Status of the function set with Fieldbus DI 7. Protocol address 000Ch, read with function code 01. | Binary | - | 1 | R |
| 13 | 1 | Digital input telegram: Programmable digital input 8 Status of the function set with Fieldbus DI 8. Protocol address 000Dh, read with function code 01. | Binary | - | 1 | R |
| 14 | 1 | Digital input telegram: Programmable digital input 9 Status of the function set with Fieldbus DI 9. Protocol address 000Eh, read with function code 01. | Binary | - | 1 | R |
| 15 | 1 | Digital input telegram: Programmable digital input 10 Status of the function set with Fieldbus DI 10. Protocol address 000Fh, read with function code 01. | Binary | - | 1 | R |
| 256 | 1 | Digital output telegram: Start Commence a start when the signal is set. Protocol address 0100h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 257 | 1 | Digital output telegram: Stop Commence a stop when the signal is negated. Protocol address 0101h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 258 | 1 | Digital output telegram: Fault reset Reset signal for possible events. Protocol address 0102h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 259 | 1 | Digital output telegram: Auto mode Must be set for controlling the motor from the fieldbus. Protocol address 0103h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 260 | 1 | Digital output telegram: Slow speed reverse Perform slow speed reverse when the signal is set. Protocol address 0104h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 261 | 1 | Digital output telegram: Slow speed forward Perform slow speed forward when the signal is set. Protocol address 0105h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 262 | 1 | Digital output telegram: Spare Spare. Protocol address 0106h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 263 | 1 | Digital output telegram: Start 1 Start 1 if sequence start. Protocol address 0107h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 264 | 1 | Digital output telegram: Start 2 Start 2 if sequence start. Protocol address 0108h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 265 | 1 | Digital output telegram: Start 3 Start 3 if sequence start. Protocol address 0109h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 266 | 1 | Digital output telegram: Motor heating Perform motor heating when the signal is set. Protocol address 010Ah, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 267 | 1 | Digital output telegram: Stand still brake Perform stand still brake when the signal is set. Protocol address 010Bh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 268 | 1 | Digital output telegram: Start reverse Commence a reverse start when the signal is set. Protocol address 010Ch, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 269 | 1 | Digital output telegram: Spare Spare. Protocol address 010Dh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 270 | 1 | Digital output telegram: Emergency mode Set to 1 to enable emergency mode. Protocol address 010Eh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 271 | 1 | Digital output telegram: FBT toggle bit Fieldbus task toggle bit. Protocol address 010Fh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 272 | 1 | Digital output telegram: User defined trip Set to 1 to trigger the user defined protection. Protocol address 0110h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 273 | 1 | Digital output telegram: Switch to remote control Switch to remote control when the signal is set (rising edge triggered). Protocol address 0111h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 274 | 1 | Digital output telegram: Pump cleaning automatic Perform automatic pump cleaning when the signal is set. Protocol address 0112h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 275 | 1 | Digital output telegram: Pump cleaning forward Perform forward pump cleaning when the signal is set. Protocol address 0113h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 276 | 1 | Digital output telegram: Pump cleaning reverse Perform reverse pump cleaning when the signal is set. Protocol address 0114h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 277 | 1 | Digital output telegram: K4 relay command Set to 1 to activate the internal K4 output relay; parameter 10.4 K4 function must be Fieldbus. Protocol address 0115h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 278 | 1 | Digital output telegram: K5 relay command Set to 1 to activate the internal K5 output relay; parameter 10.5 K5 function must be Fieldbus. Protocol address 0116h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 279 | 1 | Digital output telegram: K6 relay command Set to 1 to activate the internal K6 output relay; parameter 10.6 K6 function must be Fieldbus. Protocol address 0117h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 280 | 1 | Digital output telegram: Spare Spare. Protocol address 0118h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 281 | 1 | Digital output telegram: Spare Spare. Protocol address 0119h, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 282 | 1 | Digital output telegram: Spare Spare. Protocol address 011Ah, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 283 | 1 | Digital output telegram: Spare Spare. Protocol address 011Bh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 284 | 1 | Digital output telegram: Spare Spare. Protocol address 011Ch, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 285 | 1 | Digital output telegram: Spare Spare. Protocol address 011Dh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 286 | 1 | Digital output telegram: Spare Spare. Protocol address 011Eh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
| 287 | 1 | Digital output telegram: Spare Spare. Protocol address 011Fh, written with function code 15 or as control word bits. | Binary | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Built-in Modbus RTU on terminal pair 23/24 (the DX111/DX112 expansion module shares them). Set 12.01 Com3 function = Modbus RTU slave, 12.02 FB interface connector = Modbus RTU and 12.03 Fieldbus control = On; the factory values of the communication parameters are 12.04 Fieldbus address = 0, 12.09 FB baud rate = 19200, 12.10 FB parity = Even and 12.11 FB stop bits = 1, which is the serial block above. The factory value 0 is the broadcast address, so no factory slave address in 1-247 exists to seed: unit ID 1 is a placeholder to be verified and set on site (12.04, 1-247); a change needs a power cycle or 12.02 to None and back. The document prints each address as protocol address (on the wire) and as Modicon address; protocol addresses are stored here: input telegram 0000h, status word 01FFh, control words 02FEh/02FFh, output telegram 0100h. Coils 0000h-000Fh are read with function code 01, coils 0100h-011Fh are written with function code 15 (or through the control words), holding registers are read with 03/04 and written with 06/16. Manual parameter read/write uses the fieldbus tasks and the Fieldbus AO registers, so no parameter list is included. Sources: ABB 'Fieldbus communication - Built-in Modbus RTU' 1SFC132089M0201 Rev E (2019), sections 2 (addressing), 3 (PSTX data: digital input telegram page 5, status word pages 8-9, analog input telegram page 8, digital output telegram page 11, analog output telegram page 12, control words pages 12-13); PDF at https://library.e.abb.com/public/2e8c2f04460f4143baabdfa0690de37d/1SFC132089M0201_PSTX_Internal_Modbus_RTU.pdf. The factory serial settings are from ABB 'PSTX Softstarters Installation and commissioning manual' 1SFC132081M0201 Rev Q, parameters 12.01-12.11 on pages 97-98; PDF at https://library.e.abb.com/public/18446de6f1594ca08cb3437f5dd8bdbe/1SFC132081M0201_Rev_Q.pdf.