  "spec_version": 1,
  "slug": "abb-pstx",
  "manufacturer": "ABB",
  "model": "PSTX softstarter (built-in Modbus RTU)",
  "category": "Soft starter",
  "supplier_url": "https://new.abb.com/low-voltage/products/softstarters/pstx",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [
    {
      "address": 0,
      "count": 1,
      "name": "Digital input telegram: Auto mode status",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = softstarter control through Modbus disabled, 1 = enabled. Protocol address 0000h, read with function code 01."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Digital input telegram: Event status",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = no active fault/warning/protection, 1 = active fault/warning/protection. Protocol address 0001h, read with function code 01."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Digital input telegram: Ready to start",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = a start will probably cause a fault, 1 = a start will probably not cause a fault. Protocol address 0002h, read with function code 01."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Digital input telegram: FBT response 0",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Fieldbus task response bit 0. Protocol address 0003h, read with function code 01."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Digital input telegram: FBT response 1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Fieldbus task response bit 1. Protocol address 0004h, read with function code 01."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Digital input telegram: FBT toggle bit",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Fieldbus task toggle bit. Protocol address 0005h, read with function code 01."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 1. Protocol address 0006h, read with function code 01."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 2. Protocol address 0007h, read with function code 01."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 3",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 3. Protocol address 0008h, read with function code 01."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 4",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 4. Protocol address 0009h, read with function code 01."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 5",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 5. Protocol address 000Ah, read with function code 01."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 6",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 6. Protocol address 000Bh, read with function code 01."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 7",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 7. Protocol address 000Ch, read with function code 01."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 8",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 8. Protocol address 000Dh, read with function code 01."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 9",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 9. Protocol address 000Eh, read with function code 01."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Digital input telegram: Programmable digital input 10",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status of the function set with Fieldbus DI 10. Protocol address 000Fh, read with function code 01."
    },
    {
      "address": 256,
      "count": 1,
      "name": "Digital output telegram: Start",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Commence a start when the signal is set. Protocol address 0100h, written with function code 15 or as control word bits."
    },
    {
      "address": 257,
      "count": 1,
      "name": "Digital output telegram: Stop",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Commence a stop when the signal is negated. Protocol address 0101h, written with function code 15 or as control word bits."
    },
    {
      "address": 258,
      "count": 1,
      "name": "Digital output telegram: Fault reset",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Reset signal for possible events. Protocol address 0102h, written with function code 15 or as control word bits."
    },
    {
      "address": 259,
      "count": 1,
      "name": "Digital output telegram: Auto mode",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Must be set for controlling the motor from the fieldbus. Protocol address 0103h, written with function code 15 or as control word bits."
    },
    {
      "address": 260,
      "count": 1,
      "name": "Digital output telegram: Slow speed reverse",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform slow speed reverse when the signal is set. Protocol address 0104h, written with function code 15 or as control word bits."
    },
    {
      "address": 261,
      "count": 1,
      "name": "Digital output telegram: Slow speed forward",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform slow speed forward when the signal is set. Protocol address 0105h, written with function code 15 or as control word bits."
    },
    {
      "address": 262,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 0106h, written with function code 15 or as control word bits."
    },
    {
      "address": 263,
      "count": 1,
      "name": "Digital output telegram: Start 1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Start 1 if sequence start. Protocol address 0107h, written with function code 15 or as control word bits."
    },
    {
      "address": 264,
      "count": 1,
      "name": "Digital output telegram: Start 2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Start 2 if sequence start. Protocol address 0108h, written with function code 15 or as control word bits."
    },
    {
      "address": 265,
      "count": 1,
      "name": "Digital output telegram: Start 3",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Start 3 if sequence start. Protocol address 0109h, written with function code 15 or as control word bits."
    },
    {
      "address": 266,
      "count": 1,
      "name": "Digital output telegram: Motor heating",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform motor heating when the signal is set. Protocol address 010Ah, written with function code 15 or as control word bits."
    },
    {
      "address": 267,
      "count": 1,
      "name": "Digital output telegram: Stand still brake",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform stand still brake when the signal is set. Protocol address 010Bh, written with function code 15 or as control word bits."
    },
    {
      "address": 268,
      "count": 1,
      "name": "Digital output telegram: Start reverse",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Commence a reverse start when the signal is set. Protocol address 010Ch, written with function code 15 or as control word bits."
    },
    {
      "address": 269,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 010Dh, written with function code 15 or as control word bits."
    },
    {
      "address": 270,
      "count": 1,
      "name": "Digital output telegram: Emergency mode",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Set to 1 to enable emergency mode. Protocol address 010Eh, written with function code 15 or as control word bits."
    },
    {
      "address": 271,
      "count": 1,
      "name": "Digital output telegram: FBT toggle bit",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Fieldbus task toggle bit. Protocol address 010Fh, written with function code 15 or as control word bits."
    },
    {
      "address": 272,
      "count": 1,
      "name": "Digital output telegram: User defined trip",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Set to 1 to trigger the user defined protection. Protocol address 0110h, written with function code 15 or as control word bits."
    },
    {
      "address": 273,
      "count": 1,
      "name": "Digital output telegram: Switch to remote control",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Switch to remote control when the signal is set (rising edge triggered). Protocol address 0111h, written with function code 15 or as control word bits."
    },
    {
      "address": 274,
      "count": 1,
      "name": "Digital output telegram: Pump cleaning automatic",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform automatic pump cleaning when the signal is set. Protocol address 0112h, written with function code 15 or as control word bits."
    },
    {
      "address": 275,
      "count": 1,
      "name": "Digital output telegram: Pump cleaning forward",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform forward pump cleaning when the signal is set. Protocol address 0113h, written with function code 15 or as control word bits."
    },
    {
      "address": 276,
      "count": 1,
      "name": "Digital output telegram: Pump cleaning reverse",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Perform reverse pump cleaning when the signal is set. Protocol address 0114h, written with function code 15 or as control word bits."
    },
    {
      "address": 277,
      "count": 1,
      "name": "Digital output telegram: K4 relay command",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Set to 1 to activate the internal K4 output relay; parameter 10.4 K4 function must be Fieldbus. Protocol address 0115h, written with function code 15 or as control word bits."
    },
    {
      "address": 278,
      "count": 1,
      "name": "Digital output telegram: K5 relay command",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Set to 1 to activate the internal K5 output relay; parameter 10.5 K5 function must be Fieldbus. Protocol address 0116h, written with function code 15 or as control word bits."
    },
    {
      "address": 279,
      "count": 1,
      "name": "Digital output telegram: K6 relay command",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Set to 1 to activate the internal K6 output relay; parameter 10.6 K6 function must be Fieldbus. Protocol address 0117h, written with function code 15 or as control word bits."
    },
    {
      "address": 280,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 0118h, written with function code 15 or as control word bits."
    },
    {
      "address": 281,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 0119h, written with function code 15 or as control word bits."
    },
    {
      "address": 282,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Ah, written with function code 15 or as control word bits."
    },
    {
      "address": 283,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Bh, written with function code 15 or as control word bits."
    },
    {
      "address": 284,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Ch, written with function code 15 or as control word bits."
    },
    {
      "address": 285,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Dh, written with function code 15 or as control word bits."
    },
    {
      "address": 286,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Eh, written with function code 15 or as control word bits."
    },
    {
      "address": 287,
      "count": 1,
      "name": "Digital output telegram: Spare",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Spare. Protocol address 011Fh, written with function code 15 or as control word bits."
    }
  ],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 511,
      "count": 1,
      "name": "Status word",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Protocol address 01FFh (Modicon 30512). Bits: 0 auto mode status, 1 event status, 2 ready to start, 3 FBT response 0, 4 FBT response 1, 5 FBT toggle bit, 6-15 programmable digital inputs 1-10 (see section 3.4 of the manual)."
    },
    {
      "address": 512,
      "count": 1,
      "name": "FBT return value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Protocol address 0200h (Modicon 30513). Fieldbus task return value."
    },
    {
      "address": 513,
      "count": 1,
      "name": "Programmable analog input 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 1. The value and its scaling follow the function selected for this input with Fieldbus AI 1: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 514,
      "count": 1,
      "name": "Programmable analog input 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 2. The value and its scaling follow the function selected for this input with Fieldbus AI 2: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 515,
      "count": 1,
      "name": "Programmable analog input 3",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 3. The value and its scaling follow the function selected for this input with Fieldbus AI 3: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 516,
      "count": 1,
      "name": "Programmable analog input 4",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 4. The value and its scaling follow the function selected for this input with Fieldbus AI 4: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 517,
      "count": 1,
      "name": "Programmable analog input 5",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 5. The value and its scaling follow the function selected for this input with Fieldbus AI 5: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 518,
      "count": 1,
      "name": "Programmable analog input 6",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 6. The value and its scaling follow the function selected for this input with Fieldbus AI 6: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 519,
      "count": 1,
      "name": "Programmable analog input 7",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 7. The value and its scaling follow the function selected for this input with Fieldbus AI 7: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 520,
      "count": 1,
      "name": "Programmable analog input 8",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 8. The value and its scaling follow the function selected for this input with Fieldbus AI 8: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 521,
      "count": 1,
      "name": "Programmable analog input 9",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 9. The value and its scaling follow the function selected for this input with Fieldbus AI 9: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 522,
      "count": 1,
      "name": "Programmable analog input 10",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Programmable analog input 10. The value and its scaling follow the function selected for this input with Fieldbus AI 10: for example phase/motor current 1000 = 100 A (0.1 A per count), active power 1000 = 10 kW, mains voltage 1000 = 100 V, power factor 100 = 1.00, motor voltage 100 = 100 %, motor temperature 100 = 100 %. As the scale depends on that setting, no fixed factor is applied here."
    },
    {
      "address": 766,
      "count": 1,
      "name": "Control word 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Protocol address 02FEh (Modicon 40767). Bits: 0 start, 1 stop, 2 fault reset, 3 auto mode, 4 slow speed reverse, 5 slow speed forward, 6 spare, 7 start1, 8 start2, 9 start3, 10 motor heating, 11 stand still brake, 12 start reverse, 13 spare, 14 emergency mode, 15 FBT toggle bit."
    },
    {
      "address": 767,
      "count": 1,
      "name": "Control word 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Protocol address 02FFh (Modicon 40768). Bits: 0 switch to remote control, 1 pump cleaning automatic, 2 pump cleaning forward, 3 pump cleaning reverse, 4 K4 relay command, 5 K5 relay command, 6 K6 relay command, 7-15 spare."
    },
    {
      "address": 768,
      "count": 1,
      "name": "FBT control word",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Protocol address 0300h (Modicon 40769). Fieldbus task control word."
    },
    {
      "address": 769,
      "count": 1,
      "name": "Fieldbus AO 1 (FBT argument 2 or internal analog output)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Protocol address 0301h (Modicon 40770). Use is set by 12.37 Fieldbus AO1: as FBT argument 2 it writes parameters and set values, as internal analog output it drives the internal analog output (parameter 10.8 AO type must be Fieldbus [%])."
    },
    {
      "address": 770,
      "count": 1,
      "name": "Fieldbus AO 2 (FBT argument 3 or external analog output)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Protocol address 0302h (Modicon 40771). Use is set by 12.38 Fieldbus AO2: as FBT argument 3 it writes parameters and set values, as external analog output it drives the external analog output (parameter 11.14 1AO0 type must be Fieldbus [%])."
    }
  ],
  "combined_registers": [],
  "notes": "Built-in Modbus RTU on terminal pair 23/24 (the DX111/DX112 expansion module shares them). Set 12.01 Com3 function = Modbus RTU slave, 12.02 FB interface connector = Modbus RTU and 12.03 Fieldbus control = On; the factory values of the communication parameters are 12.04 Fieldbus address = 0, 12.09 FB baud rate = 19200, 12.10 FB parity = Even and 12.11 FB stop bits = 1, which is the serial block above. The factory value 0 is the broadcast address, so no factory slave address in 1-247 exists to seed: unit ID 1 is a placeholder to be verified and set on site (12.04, 1-247); a change needs a power cycle or 12.02 to None and back. The document prints each address as protocol address (on the wire) and as Modicon address; protocol addresses are stored here: input telegram 0000h, status word 01FFh, control words 02FEh/02FFh, output telegram 0100h. Coils 0000h-000Fh are read with function code 01, coils 0100h-011Fh are written with function code 15 (or through the control words), holding registers are read with 03/04 and written with 06/16. Manual parameter read/write uses the fieldbus tasks and the Fieldbus AO registers, so no parameter list is included. Sources: ABB 'Fieldbus communication - Built-in Modbus RTU' 1SFC132089M0201 Rev E (2019), sections 2 (addressing), 3 (PSTX data: digital input telegram page 5, status word pages 8-9, analog input telegram page 8, digital output telegram page 11, analog output telegram page 12, control words pages 12-13); PDF at https://library.e.abb.com/public/2e8c2f04460f4143baabdfa0690de37d/1SFC132089M0201_PSTX_Internal_Modbus_RTU.pdf. The factory serial settings are from ABB 'PSTX Softstarters Installation and commissioning manual' 1SFC132081M0201 Rev Q, parameters 12.01-12.11 on pages 97-98; PDF at https://library.e.abb.com/public/18446de6f1594ca08cb3437f5dd8bdbe/1SFC132081M0201_Rev_Q.pdf."
}