  "spec_version": 1,
  "slug": "abb-acs380",
  "manufacturer": "ABB",
  "model": "ACS380 machinery drive (ACS380-04xS, ACS380-04xC with +L538), embedded Modbus RTU",
  "category": "VFD",
  "supplier_url": "https://new.abb.com/drives/low-voltage-ac/industrial-drives/acs380",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "LowFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [
    {
      "address": 1,
      "count": 1,
      "name": "Control word coil OFF1_CONTROL",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "OFF1 control: 1 = enter the OFF1 state. DCU profile: STOP. Coil reference 000001, which is the address on the wire."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Control word coil OFF2_CONTROL",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "OFF2 control: 0 = OFF2 active (coast to stop). DCU profile: START. Coil reference 000002, which is the address on the wire."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Control word coil OFF3_CONTROL",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "OFF3 control: 0 = OFF3 active (emergency ramp stop). DCU profile: Reserved. Coil reference 000003, which is the address on the wire."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Control word coil INHIBIT_OPERATION",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = operation inhibited. DCU profile: Reserved. Coil reference 000004, which is the address on the wire."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Control word coil RAMP_OUT_ZERO",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = force the ramp function generator output to zero. DCU profile: RESET. Coil reference 000005, which is the address on the wire."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Control word coil RAMP_HOLD",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = halt ramping. DCU profile: EXT2. Coil reference 000006, which is the address on the wire."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Control word coil RAMP_IN_ZERO",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = force the ramp function generator input to zero. DCU profile: RUN_DISABLE. Coil reference 000007, which is the address on the wire."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Control word coil RESET",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = fault reset if an active fault exists. DCU profile: STOPMODE_RAMP. Coil reference 000008, which is the address on the wire."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Control word coil JOGGING_1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = run at jogging 1 speed. DCU profile: STOPMODE_EMERGENCY_RAMP. Coil reference 000009, which is the address on the wire."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Control word coil JOGGING_2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = run at jogging 2 speed. DCU profile: STOPMODE_COAST. Coil reference 000010, which is the address on the wire."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Control word coil REMOTE_CMD",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = continue normal operation, 1 = fieldbus control enabled. DCU profile: Reserved. Coil reference 000011, which is the address on the wire."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Control word coil EXT_CTRL_LOC",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Selects external control location EXT2 (1) or EXT1 (0). DCU profile: RAMP_OUT_ZERO. Coil reference 000012, which is the address on the wire."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Control word coil USER_0",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Writable control bit for application logic. DCU profile: RAMP_HOLD. Coil reference 000013, which is the address on the wire."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Control word coil USER_1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Writable control bit for application logic. DCU profile: RAMP_IN_ZERO. Coil reference 000014, which is the address on the wire."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Control word coil USER_2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Writable control bit for application logic. DCU profile: Reserved. Coil reference 000015, which is the address on the wire."
    },
    {
      "address": 16,
      "count": 1,
      "name": "Control word coil USER_3",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Writable control bit for application logic. DCU profile: Reserved. Coil reference 000016, which is the address on the wire."
    },
    {
      "address": 33,
      "count": 1,
      "name": "Control for RO1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = energise relay output RO1 (10.99 bit 0). Coil reference 000033, which is the address on the wire."
    },
    {
      "address": 34,
      "count": 1,
      "name": "Control for RO2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = energise relay output RO2 (10.99 bit 1). Coil reference 000034, which is the address on the wire."
    },
    {
      "address": 35,
      "count": 1,
      "name": "Control for RO3",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = energise relay output RO3 (10.99 bit 2). Coil reference 000035, which is the address on the wire."
    },
    {
      "address": 36,
      "count": 1,
      "name": "Control for RO4",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = energise relay output RO4 (10.99 bit 3). Coil reference 000036, which is the address on the wire."
    },
    {
      "address": 37,
      "count": 1,
      "name": "Control for RO5",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "1 = energise relay output RO5 (10.99 bit 4). Coil reference 000037, which is the address on the wire."
    }
  ],
  "discrete_inputs": [
    {
      "address": 0,
      "count": 1,
      "name": "Status word bit RDY_ON",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "READY TO SWITCH ON. DCU profile: READY. Discrete input reference 0 in the manual's 1xxxx table."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Status word bit RDY_RUN",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "READY TO OPERATE. DCU profile: ENABLED. Discrete input reference 1 in the manual's 1xxxx table."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Status word bit RDY_REF",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "OPERATION ENABLED. DCU profile: Reserved. Discrete input reference 2 in the manual's 1xxxx table."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Status word bit TRIPPED",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "FAULT. DCU profile: RUNNING. Discrete input reference 3 in the manual's 1xxxx table."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Status word bit OFF_2_STATUS",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "OFF2 inactive. DCU profile: ZERO_SPEED. Discrete input reference 4 in the manual's 1xxxx table."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Status word bit OFF_3_STATUS",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "OFF3 inactive. DCU profile: Reserved. Discrete input reference 5 in the manual's 1xxxx table."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Status word bit SWC_ON_INHIB",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "SWITCH-ON INHIBITED. DCU profile: Reserved. Discrete input reference 6 in the manual's 1xxxx table."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Status word bit ALARM",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Warning or alarm active. DCU profile: AT_SETPOINT. Discrete input reference 7 in the manual's 1xxxx table."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Status word bit AT_SETPOINT",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "OPERATING: actual value equals the reference. DCU profile: LIMIT. Discrete input reference 8 in the manual's 1xxxx table."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Status word bit REMOTE",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Drive control location REMOTE (EXT1/EXT2). DCU profile: SUPERVISION. Discrete input reference 9 in the manual's 1xxxx table."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Status word bit ABOVE_LIMIT",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Actual frequency/speed at or above the supervision limit. DCU profile: Reserved. Discrete input reference 10 in the manual's 1xxxx table."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Status word bit USER_0",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status bit for application logic. DCU profile: Reserved. Discrete input reference 11 in the manual's 1xxxx table."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Status word bit USER_1",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status bit for application logic. DCU profile: PANEL_LOCAL. Discrete input reference 12 in the manual's 1xxxx table."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Status word bit USER_2",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status bit for application logic. DCU profile: FIELDBUS_LOCAL. Discrete input reference 13 in the manual's 1xxxx table."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Status word bit USER_3",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status bit for application logic. DCU profile: EXT2_ACT. Discrete input reference 14 in the manual's 1xxxx table."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Status word bit RESERVED",
      "data_type": "Binary",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Reserved. DCU profile: FAULT. Discrete input reference 15 in the manual's 1xxxx table."
    }
  ],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 0,
      "count": 1,
      "name": "Control word (16 bit)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400001: control word (CW). ABB Drives profile bits: 0 OFF1, 1 OFF2, 2 OFF3, 3 inhibit operation, 4 ramp out zero, 5 ramp hold, 6 ramp in zero, 7 reset, 8-9 jogging, 10 remote command, 11 ext ctrl loc, 12-15 user. DCU profile: 0 stop, 1 start, 2 reverse, 4 reset, 5 EXT2, 6 run disable, 7-9 stop mode, 11-13 ramp control. Selection changeable with 58.101."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Reference 1 (REF1)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400002: reference 1. Type and scaling from 58.26 EFB ref1 type and 46.01-46.04; with the speed or frequency type, 20000 equals the scaling limit and -20000 the negative limit."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Reference 2 (REF2)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400003: reference 2. Type and scaling from 58.27 EFB ref2 type and 46.01-46.04."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Status word (16 bit)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400004: status word (SW). ABB Drives profile bits: 0 ready to switch on, 1 ready to operate, 2 operation enabled, 3 fault, 4 OFF2 inactive, 5 OFF3 inactive, 6 switch-on inhibited, 7 warning/alarm, 8 at setpoint, 9 remote, 10 above limit, 11-14 user. DCU profile: 0 ready, 1 enabled, 3 running, 4 zero speed, 7 at setpoint, 8 limit, 9 supervision, 12 panel local, 13 fieldbus local, 14 EXT2 act, 15 fault."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Actual value 1 (Act1)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400005: actual value 1, selected by 58.28 EFB act1 type and scaled by 46.01-46.04. A 16-bit word with a sign bit and a 15-bit integer."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Actual value 2 (Act2)",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400006: actual value 2, selected by 58.29 EFB act2 type and scaled by 46.01-46.04."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Data in/out 7",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400007: data word 7, selected and routed by parameter 58.107 Data I/O 7."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Data in/out 8",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400008: data word 8, selected and routed by parameter 58.108 Data I/O 8."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Data in/out 9",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400009: data word 9, selected and routed by parameter 58.109 Data I/O 9."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Data in/out 10",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400010: data word 10, selected and routed by parameter 58.110 Data I/O 10."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Data in/out 11",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400011: data word 11, selected and routed by parameter 58.111 Data I/O 11."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Data in/out 12",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400012: data word 12, selected and routed by parameter 58.112 Data I/O 12."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Data in/out 13",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400013: data word 13, selected and routed by parameter 58.113 Data I/O 13."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Data in/out 14",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400014: data word 14, selected and routed by parameter 58.114 Data I/O 14."
    },
    {
      "address": 89,
      "count": 1,
      "name": "Reset error registers",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Holding register 400090: write 1 to reset the internal error registers 91...95, write 0 to do nothing."
    },
    {
      "address": 90,
      "count": 1,
      "name": "Error function code",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400091: function code of the last failed Modbus query."
    },
    {
      "address": 91,
      "count": 1,
      "name": "Error code",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400092: set when exception code 04h is generated (01h illegal function, 02h illegal address, 03h illegal value, 04h device failure)."
    },
    {
      "address": 92,
      "count": 1,
      "name": "Failed register",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400093: the last register that failed to be read or written."
    },
    {
      "address": 93,
      "count": 1,
      "name": "Last register written",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400094: the last register written successfully."
    },
    {
      "address": 94,
      "count": 1,
      "name": "Last register read",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Holding register 400095: the last register read successfully."
    }
  ],
  "combined_registers": [],
  "notes": "The ACS380 has an embedded EIA-485 Modbus RTU interface on the BMIO-01 module of the standard variant ACS380-04xS and on the I/O and Modbus extension module (option +L538) of the configured variant ACS380-04xC; enable it with 58.01 Protocol enable = Modbus RTU. Factory settings of the embedded interface are node address 58.03 = 1, baud rate 58.04 = 19.2 kbps, parity/stop bits 58.05 = 8 EVEN 1, control profile 58.25 = ABB Drives, word order 58.34 = LO-HI (58.33 Addressing mode = Mode 0). The manual prints the holding registers as 4xxxx references, so 400001 (control word) is wire address 0; coils are printed as 1-based 0xxxx references that, as the manual states, match the address on the wire, so coil 000001 is wire address 1 and is stored as 1; discrete inputs are printed as 0-based 1xxxx references and are stored unchanged. Coils 17-31 are reserved in the ABB Drives profile (FB_LOCAL_CTL/REF and user bits in the DCU profile) and are left out. Holding registers 400007...400014 are Data in/out 7...14, routed to drive parameters with 58.107...58.114; drive parameters themselves are reached at 400101...465536 through 58.33 Addressing mode and are not listed because their addresses depend on that setting. Source: ABB 'ACS380 machinery control program firmware manual', code 3AXD50000029275 Rev E (EN), 2018-05-05, chapter 9 'Fieldbus control through the embedded fieldbus interface (EFB)' - parameter table pages 419-421, control/status words pages 426-431, Modbus holding register addresses page 435, function codes page 436, coils and discrete inputs pages 438-440, error code registers pages 440-441; PDF (mirror of the ABB-hosted file) at https://cdn.logic-control.com/docs/abb-drives/acs380/ACS380%20Firmware%20Manual.pdf, SHA-256 997707c980f0b515e59fd287143a8b17149778c66f87308b89a31b6e7edf92ce."
}