  "spec_version": 1,
  "slug": "yaskawa-a1000",
  "manufacturer": "Yaskawa",
  "model": "A1000 (CIMR-A) high performance vector control drive",
  "category": "VFD",
  "supplier_url": "https://www.yaskawa.com/downloads/search-index/details?showType=details&docnum=SIEPC71061627",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 31,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 1,
      "count": 1,
      "name": "Operation commands and multi-function inputs",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0001H. bit 0 forward run (H5-12 = 0) or run (H5-12 = 1), bit 1 reverse run (H5-12 = 0) or forward/reverse (H5-12 = 1), bit 2 external fault EF0, bit 3 fault reset, bits 4-11 multi-function inputs 1-8, bits 12-15 reserved. Set unused bits to 0."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Frequency reference",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "0002H. Units are determined by o1-03: 0.01 Hz at o1-03 = 0 (the factory default in V/f, V/f w/PG, OLV, CLV and OLV/PM), 0.01 % of the maximum output frequency at o1-03 = 1, min-1 at o1-03 = 2 and user-set units at o1-03 = 3 (o1-10/o1-11). The factor shown assumes o1-03 = 0."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Output voltage gain",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "0003H. 20 to 2000 (2.0 % to 200.0 %), default when powered on 1000 (100.0 %)."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Torque reference / torque limit",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "0004H. 0.1 % units, signed; usable only if torque control is enabled."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Torque compensation",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "0005H. 0.1 % units, signed; usable only if torque control is enabled."
    },
    {
      "address": 6,
      "count": 1,
      "name": "PID target",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "0006H. 0.01 % units, signed."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Analog output terminal FM setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0007H. 10 V / 4000H, i.e. the value 4000 corresponds to 10 V at terminal FM."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Analog output terminal AM setting",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0008H. 10 V / 4000H, i.e. the value 4000 corresponds to 10 V at terminal AM."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Settings for multi-function digital outputs",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0009H. bit 0 M1-M2, bit 1 M3-M4, bit 2 M5-M6, bits 3-5 reserved, bit 6 enables the function in bit 7, bit 7 fault contact output MA/MB-MC, bits 8-15 reserved."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Pulse output terminal MP setting",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "000AH. 1 Hz units, setting range 0 to 32000."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Control selection setting",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "000FH. bit 1 PID setpoint input, bit 2 torque reference/torque limit input, bit 3 torque compensation input, bits 12-15 enable terminal S5-S8 input for broadcast data; other bits reserved."
    },
    {
      "address": 27,
      "count": 1,
      "name": "Analog monitor option AO-A3 output 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "001BH. 10 V / 4000H."
    },
    {
      "address": 28,
      "count": 1,
      "name": "Analog monitor option AO-A3 output 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "001CH. 10 V / 4000H."
    },
    {
      "address": 29,
      "count": 1,
      "name": "Digital output option DO-A3 output",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "001DH. Binary output pattern of the DO-A3 option card."
    },
    {
      "address": 32,
      "count": 1,
      "name": "Drive status 1",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0020H. bit 0 during run, bit 1 during reverse, bit 2 drive ready, bit 3 fault, bit 4 data setting error, bit 5 M1-M2, bit 6 M3-M4, bit 7 M5-M6, bit E ComRef enabled, bit F ComCtrl enabled."
    },
    {
      "address": 33,
      "count": 1,
      "name": "Fault contents 1",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0021H. Grouped active faults: bit 0 overcurrent/ground fault, bit 1 drive overheat warning, bit 2 drive overload, bit 3 overheat 1/2, bit 4 braking fault, bit 6 PID feedback loss, bit 7 external fault, bit 8 CPF hardware fault, bit 9 motor overload/overtorque/undertorque, bit A PG/overspeed/deviation, bit B main circuit undervoltage, bit C DC bus undervoltage, bit D phase loss, bit E communication error, bit F operator connection fault."
    },
    {
      "address": 34,
      "count": 1,
      "name": "Data link status",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0022H. bit 0 writing data or switching motors, bit 3 upper or lower limit error, bit 4 data conformity error, bit 5 writing to EEPROM, bit 6 0 = write into EEPROM / 1 = write in RAM only (only when H5-17 = 1)."
    },
    {
      "address": 35,
      "count": 1,
      "name": "Frequency reference (monitor)",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "0023H. Units are determined by o1-03 (0.01 Hz at o1-03 = 0, which is the factory default in the usual control modes)."
    },
    {
      "address": 36,
      "count": 1,
      "name": "Output frequency (monitor)",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "0024H. Units are determined by o1-03 (0.01 Hz at o1-03 = 0)."
    },
    {
      "address": 37,
      "count": 1,
      "name": "Output voltage reference",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "0025H. 0.1 V units; the displayed units are determined by H5-10."
    },
    {
      "address": 38,
      "count": 1,
      "name": "Output current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "0026H. 0.1 A units."
    },
    {
      "address": 41,
      "count": 1,
      "name": "Fault contents 2",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0029H. bit 0 output short circuit or IGBT fault, bit 1 ground fault, bit 2 input phase loss, bit 3 output phase loss, bit 4 braking resistor overheat, bit 6 motor overheat (PTC input)."
    },
    {
      "address": 42,
      "count": 1,
      "name": "Alarm contents 1",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "002AH. bit 2 forward/reverse run command input error, bit 3 baseblock, bit 4 overtorque detection 1, bit 5 heatsink overheat, bit 6 drive overheat warning, bit 7 undervoltage, bit 8 internal fan fault, bit 9 communication error, bit A option communication error, bit B undertorque detection, bit C motor overheat, bit D PID feedback loss, bit F serial communication transmission error."
    },
    {
      "address": 43,
      "count": 1,
      "name": "Input terminal status",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "002BH. bit 0 terminal S1 closed through bit 7 terminal S8 closed."
    },
    {
      "address": 44,
      "count": 1,
      "name": "Drive status 2",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "002CH. bit 0 during run, bit 1 zero speed, bit 2 speed agree, bit 3 user speed agree, bit 4 frequency detection 1, bit 5 frequency detection 2, bit 6 drive ready, bit 7 during undervoltage, bit 8 during baseblock, bit 9 frequency reference from operator, bit A run command from operator, bit B over/undertorque detection, bit C frequency reference loss, bit D during fault restart, bit E fault, bit F communication timeout."
    },
    {
      "address": 45,
      "count": 1,
      "name": "Output terminal status",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "002DH. bit 0 M1-M2, bit 1 M3-M4, bit 2 M5-M6, bit 7 fault contact output MA/MB-MC."
    },
    {
      "address": 47,
      "count": 1,
      "name": "Frequency reference bias (Up/Down 2)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "002FH. 0.1 % units."
    },
    {
      "address": 49,
      "count": 1,
      "name": "DC bus voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0031H. 1 Vdc units."
    },
    {
      "address": 50,
      "count": 1,
      "name": "Torque reference (U1-09)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0032H. 1 % units."
    },
    {
      "address": 52,
      "count": 1,
      "name": "Product code 1",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0034H. ASCII product type, A0 for A1000."
    },
    {
      "address": 53,
      "count": 1,
      "name": "Product code 2",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0035H. ASCII region code."
    },
    {
      "address": 56,
      "count": 1,
      "name": "PID feedback",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "0038H. 0.1 % units, unsigned; 100 % corresponds to the maximum output frequency."
    },
    {
      "address": 57,
      "count": 1,
      "name": "PID input",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "0039H. 0.1 % units, signed; 100 % corresponds to the maximum output frequency."
    },
    {
      "address": 61,
      "count": 1,
      "name": "Communications error contents",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "003DH. bit 0 CRC error, bit 1 data length error, bit 3 parity error, bit 4 overrun error, bit 5 framing error, bit 6 timeout. The contents are saved until the fault is reset."
    },
    {
      "address": 62,
      "count": 1,
      "name": "Output frequency in min-1",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "003EH. Output frequency in min-1; the correct motor pole count must be set in E2-04, E4-04 or E5-04 for the value to be correct."
    },
    {
      "address": 63,
      "count": 1,
      "name": "Output frequency in percent",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "003FH. 0.01 % units, 100 % = maximum output frequency."
    },
    {
      "address": 75,
      "count": 1,
      "name": "Drive status (U1-12)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "004BH. bit 0 during run, bit 1 during zero speed, bit 2 during reverse run, bit 3 during fault reset signal input, bit 4 during speed agree, bit 5 drive ready, bit 6 minor fault, bit 7 fault, bit 8 during operation error, bit 9 during momentary power loss, bit A motor 2 selected, bit E ComRef/NetRef status, bit F ComCtrl/NetCtrl status."
    },
    {
      "address": 127,
      "count": 1,
      "name": "Minor fault code",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "007FH. Code of the active minor fault, see the alarm register contents in the manual."
    },
    {
      "address": 152,
      "count": 1,
      "name": "Cumulative operation time, high part (U4-01)",
      "data_type": "UInt16",
      "units": "h",
      "scale_factor": 10,
      "offset": 0,
      "access": "R",
      "description": "0098H. High part of U4-01: the example in the manual shows 12345 h stored as 0098H = 1234 and 0099H = 5, so hours = 0098H * 10 + 0099H."
    },
    {
      "address": 153,
      "count": 1,
      "name": "Cumulative operation time, low digit (U4-01)",
      "data_type": "UInt16",
      "units": "h",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0099H. Last digit of U4-01; hours = 0098H * 10 + 0099H."
    },
    {
      "address": 154,
      "count": 1,
      "name": "Cooling fan operation time, high part (U4-03)",
      "data_type": "UInt16",
      "units": "h",
      "scale_factor": 10,
      "offset": 0,
      "access": "R",
      "description": "009AH. High part of U4-03; hours = 009AH * 10 + 009BH (same split as U4-01)."
    },
    {
      "address": 155,
      "count": 1,
      "name": "Cooling fan operation time, low digit (U4-03)",
      "data_type": "UInt16",
      "units": "h",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "009BH. Last digit of U4-03; hours = 009AH * 10 + 009BH."
    },
    {
      "address": 171,
      "count": 1,
      "name": "Drive rated current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00ABH. The unit depends on the model: 0.01 A for CIMR-A2A0004 to 2A0040 and A4A0002 to 4A0023, 0.1 A for A2A0056 to 2A0312 and A4A0031 to 4A0675, 1 A for A4A0930 to 4A1200. No single factor is applied."
    },
    {
      "address": 172,
      "count": 1,
      "name": "Motor speed in min-1 (U1-05)",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00ACH. Motor speed in min-1; the correct motor pole count must be set in E2-04, E4-04 or E5-04."
    },
    {
      "address": 173,
      "count": 1,
      "name": "Motor speed in percent (U1-05)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "00ADH. 0.01 % units, 100 % = maximum output frequency."
    },
    {
      "address": 176,
      "count": 1,
      "name": "Option code connected to CN5-A",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00B0H. ASCII option code, for example AI-A3 = 0003H, AO-A3 = 0004H, DI-A3 = 0001H, DO-A3 = 0002H, PG-B3 = 0011H, PG-X3 = 0012H, SI-N3 = 534EH, SI-P3 = 5350H, SI-ET3 = 1004H."
    },
    {
      "address": 178,
      "count": 1,
      "name": "Option code connected to CN5-B",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00B2H. ASCII option code, same encoding as CN5-A."
    },
    {
      "address": 179,
      "count": 1,
      "name": "Option code connected to CN5-C",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00B3H. ASCII option code, same encoding as CN5-A."
    },
    {
      "address": 181,
      "count": 1,
      "name": "Frequency reference after soft-starter in min-1 (U1-16)",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00B5H. Output of the accel/decel ramp generator in min-1."
    },
    {
      "address": 182,
      "count": 1,
      "name": "Frequency reference after soft-starter in percent (U1-16)",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "00B6H. 0.01 % units, 100 % = maximum output frequency."
    },
    {
      "address": 183,
      "count": 1,
      "name": "Frequency reference in min-1",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "00B7H. Frequency reference in min-1."
    },
    {
      "address": 184,
      "count": 1,
      "name": "Frequency reference in percent",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "00B8H. 0.01 % units, 100 % = maximum output frequency."
    }
  ],
  "combined_registers": [],
  "notes": "MEMOBUS/Modbus RTU on the RS-422/RS-485 port; the protocol is RTU only, the data length is fixed at 8 bits and the stop bit at 1 bit, and parity is selectable. Factory settings are H5-01 Drive Slave Address = 1F (31), H5-02 Communication Speed = 3 (9600 bps), H5-03 parity = 0 (none) and H5-06 Drive Transmit Wait Time = 5 ms; a changed baud rate, parity or slave address takes effect after a power cycle. H5-04 stopping method after a communication error defaults to 3 (alarm only). Command data 0001H-001FH is read/write, monitor data 0020H-00C3H is read-only; unused command bits must be set to 0 and reserved registers must not be written. Frequency values (0023H, 0024H, 002FH and the command frequency reference 0002H) follow o1-03: 0.01 Hz at o1-03 = 0, which is the factory default in V/f, V/f w/PG, OLV, CLV and OLV/PM control modes, 0.01 % of the maximum output frequency at o1-03 = 1, min-1 at o1-03 = 2 and user-set units at o1-03 = 3. The 0.01 Hz factors stored here assume o1-03 = 0. Register 0027H output power is left out because the manual lists no unit for it, as is 0028H torque reference (no unit given); 0032H torque reference in 1 % units is included instead. Source: Yaskawa 'AC Drive A1000 Technical Manual', manual no. SIEP C710616 27J, chapter C.1 MEMOBUS/Modbus Communication Specifications (page 553), C.4 MEMOBUS/Modbus Setup Parameters H5-01 to H5-06 (pages 555-556), C.9 MEMOBUS/Modbus Data Table - command data (page 565) and monitor data (pages 566-569), and o1-03 (page 314); PDF at https://www.yaskawa.eu.com/_downloads/download_d5120."
}