All devices

Continental Control Systems · Energy meter

WattNode Modbus WNC-3Y-208-MB / -3Y-400-MB / -3Y-480-MB / -3Y-600-MB / -3D-240-MB / -3D-400-MB / -3D-480-MB Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
0
Addressing
1-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
10012
EnergySum (total net energy)
Net real energy of all active phases; negative energy is subtracted. Preserved across power failures.
Float32kWh1R
10032
EnergyPosSum (total positive energy)
Float32kWh1R
10052
EnergySumNR (total net energy, non-resettable)
Float32kWh1R
10072
EnergyPosSumNR (total positive energy, non-resettable)
Float32kWh1R
10092
PowerSum (real power, sum of active phases)
Float32W1R
10112
PowerA (real power, phase A)
Float32W1R
10132
PowerB (real power, phase B)
Float32W1R
10152
PowerC (real power, phase C)
Float32W1R
10172
VoltAvgLN (average line-to-neutral voltage)
Float32V1R
10192
VoltA (phase A to neutral voltage)
Float32V1R
10212
VoltB (phase B to neutral voltage)
Float32V1R
10232
VoltC (phase C to neutral voltage)
Float32V1R
10252
VoltAvgLL (average line-to-line voltage)
Float32V1R
10272
VoltAB (line-to-line voltage A-B)
Float32V1R
10292
VoltBC (line-to-line voltage B-C)
Float32V1R
10312
VoltAC (line-to-line voltage A-C)
Float32V1R
10332
Freq (power line frequency)
Float32Hz1R
11012
EnergyA (net energy, phase A)
Float32kWh1R
11032
EnergyB (net energy, phase B)
Float32kWh1R
11052
EnergyC (net energy, phase C)
Float32kWh1R
11072
EnergyPosA (positive energy, phase A)
Float32kWh1R
11092
EnergyPosB (positive energy, phase B)
Float32kWh1R
11112
EnergyPosC (positive energy, phase C)
Float32kWh1R
11132
EnergyNegSum (negative energy, sum of active phases)
Float32kWh1R
11152
EnergyNegSumNR (negative energy, sum of active phases, non-resettable)
Float32kWh1R
11172
EnergyNegA (negative energy, phase A)
Float32kWh1R
11192
EnergyNegB (negative energy, phase B)
Float32kWh1R
11212
EnergyNegC (negative energy, phase C)
Float32kWh1R
11232
EnergyReacSum (reactive energy, sum of active phases)
Float32kVARh1R
11252
EnergyReacA (net reactive energy, phase A)
Float32kVARh1R
11272
EnergyReacB (net reactive energy, phase B)
Float32kVARh1R
11292
EnergyReacC (net reactive energy, phase C)
Float32kVARh1R
11312
EnergyAppSum (apparent energy, sum of active phases)
Float32kVAh1R
11332
EnergyAppA (apparent energy, phase A)
Float32kVAh1R
11352
EnergyAppB (apparent energy, phase B)
Float32kVAh1R
11372
EnergyAppC (apparent energy, phase C)
Float32kVAh1R
11392
PowerFactorAvg (power factor, average)
Float32-1R
11412
PowerFactorA (power factor, phase A)
Float32-1R
11432
PowerFactorB (power factor, phase B)
Float32-1R
11452
PowerFactorC (power factor, phase C)
Float32-1R
11472
PowerReacSum (reactive power, sum of active phases)
Float32VAR1R
11492
PowerReacA (reactive power, phase A)
Float32VAR1R
11512
PowerReacB (reactive power, phase B)
Float32VAR1R
11532
PowerReacC (reactive power, phase C)
Float32VAR1R
11552
PowerAppSum (apparent power, sum of active phases)
Float32VA1R
11572
PowerAppA (apparent power, phase A)
Float32VA1R
11592
PowerAppB (apparent power, phase B)
Float32VA1R
11612
PowerAppC (apparent power, phase C)
Float32VA1R
11632
CurrentA (phase A current)
Float32A1R
11652
CurrentB (phase B current)
Float32A1R
11672
CurrentC (phase C current)
Float32A1R
11692
Demand (real power demand)
Real power averaged over the demand period (DemPerMins, default 15 minutes).
Float32W1R
11712
DemandMin (minimum power demand)
Float32W1R
11732
DemandMax (maximum power demand)
Float32W1R
11772
DemandA (real power demand, phase A)
Float32W1R
11792
DemandB (real power demand, phase B)
Float32W1R
11812
DemandC (real power demand, phase C)
Float32W1R
17012
SerialNumber (meter serial number)
UInt32-1R
17032
UptimeSecs (time since last power on)
UInt32s1R
17052
TotalSecs (total seconds of operation)
UInt32s1R
17071
Model (encoded WattNode model)
UInt16-1R
17081
Version (firmware version)
UInt16-1R
17091
Options (WattNode meter options)
UInt16-1R
17101
ErrorStatus (list of recent errors and events)
UInt16-1R
17111
PowerFailCount (power failure count)
UInt16-1R
17121
CrcErrorCount (Modbus CRC communication errors)
UInt16-1R
17131
FrameErrorCount (Modbus framing errors)
UInt16-1R
17141
PacketErrorCount (bad Modbus packets)
UInt16-1R
17151
OverrunCount (Modbus buffer overruns)
UInt16-1R
17161
ErrorStatus1 (newest error or event, 0 = no errors)
UInt16-1R
17171
ErrorStatus2 (next oldest error or event)
UInt16-1R
17181
ErrorStatus3 (next oldest error or event)
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Continental Control Systems 'WattNode Modbus Installation and Operation Manual', WNC-MB-1.16d, Rev 1.16d, firmware version 16, revision date 28 January 2011, https://ctlsys.com/wp-content/uploads/2016/10/WNC-MODBUS-Manual-V16.pdf. Serial defaults from Table 4 and the Modbus Communication chapter: 9,600 baud (DIP switch 8 down), 8 data bits, no parity and one stop bit; the manual states the meter does not follow the Modbus RTU even-parity default and that even parity is available as factory Option EP or through ParityMode 1654. Unit ID: as shipped the DIP-switch address is 0, which the manual describes as an invalid broadcast address that prevents communication, so 0 is stored here as the documented factory state - set DIP switches 1-7 (addresses 1-127) or register 1652 before polling; Option AD orders a pre-programmed address. Addressing: the manual documents one-based register numbers (EnergySum at 1001 = wire address 0x03E8) so the printed numbers are stored with addressing 'one_based'. Word order: for 32-bit float and long-integer registers the lower address holds the least significant 16 bits, so word_order is 'LowFirst'. The meter treats holding and input registers interchangeably; measurements are seeded as input registers and configuration registers as holding registers. Deliberate omissions: the parallel integer register lists (1201-1221, 1301-1362) duplicate the floating-point values in scaled integer form; the apparent-power demand register (1175) is left out because the register list prints 'W' next to a value named DemandApp (apparent demand, documented in VA elsewhere); the Averaging (1608), PowerIntScale (1609), DemPerMins (1610), DemSubints (1611), GainAdjust (1612-1614) and PhaseAdjust (1615-1617) default values are printed in a configuration table whose default column does not align with the register rows, so they are omitted rather than guessed; the custom register map block (2000+) is installation-specific.