All devices

Finder · Energy meter

7M.38 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
33
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
25002
Voltage L1
Float32V1R
25022
Voltage L2
Float32V1R
25042
Voltage L3
Float32V1R
25062
Average voltage L-N
Float32V1R
25082
Voltage L1-L2
Float32V1R
25102
Voltage L2-L3
Float32V1R
25122
Voltage L3-L1
Float32V1R
25142
Average voltage L-L
Float32V1R
25162
Current L1
Float32A1R
25182
Current L2
Float32A1R
25202
Current L3
Float32A1R
25222
Sum of currents
Float32A1R
25282
Average current
Float32A1R
25302
Active power L1
Float32W1R
25322
Active power L2
Float32W1R
25342
Active power L3
Float32W1R
25362
Active power, total
Float32W1R
25382
Reactive power L1
Float32var1R
25402
Reactive power L2
Float32var1R
25422
Reactive power L3
Float32var1R
25442
Reactive power, total
Float32var1R
25462
Apparent power L1
Float32VA1R
25482
Apparent power L2
Float32VA1R
25502
Apparent power L3
Float32VA1R
25522
Apparent power, total
Float32VA1R
25542
Power factor L1
Float32-1R
25562
Power factor L2
Float32-1R
25582
Power factor L3
Float32-1R
25602
Power factor, total
Float32-1R
25762
Power angle, total
Float32°1R
25842
Frequency
Float32Hz1R
25882
Current THD L1
Float32%1R
25902
Current THD L2
Float32%1R
25922
Current THD L3
Float32%1R
25942
Voltage THD L1
Float32%1R
25962
Voltage THD L2
Float32%1R
25982
Voltage THD L3
Float32%1R
27522
Active energy imported
Float32kWh0.001R
27542
Reactive energy imported
Float32kVArh0.001R
27562
Active energy exported
Float32kWh0.001R
27582
Reactive energy exported
Float32kVArh0.001R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (address 33, 19200 bps, 8N2). Measurements and energy counters are IEEE-754 Float32 values read with function code 04, high word first. Energy is transmitted in Wh and scaled to kWh here. Configuration registers are holding registers; their addresses are the Modicom 4xxxx numbers minus 40000.