Accuenergy · Energy meter
AcuRev 2100 series multi-circuit power and energy meter (18 circuits) Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 8192 | 2 | Frequency | Float32 | Hz | 1 | R |
| 8194 | 2 | Voltage L1-N (U1) | Float32 | V | 1 | R |
| 8196 | 2 | Voltage L2-N (U2) | Float32 | V | 1 | R |
| 8198 | 2 | Voltage L3-N (U3) | Float32 | V | 1 | R |
| 8200 | 2 | Average line-to-neutral voltage (Uavg) | Float32 | V | 1 | R |
| 8202 | 2 | Line-to-line voltage L1-L2 (U12) | Float32 | V | 1 | R |
| 8204 | 2 | Line-to-line voltage L2-L3 (U23) | Float32 | V | 1 | R |
| 8206 | 2 | Line-to-line voltage L3-L1 (U31) | Float32 | V | 1 | R |
| 8208 | 2 | Average line-to-line voltage (Ulavg) | Float32 | V | 1 | R |
| 8210 | 2 | Current L1 | Float32 | A | 1 | R |
| 8212 | 2 | Current L2 | Float32 | A | 1 | R |
| 8214 | 2 | Current L3 | Float32 | A | 1 | R |
| 8216 | 2 | Average current | Float32 | A | 1 | R |
| 8218 | 2 | Total inline system active power | Float32 | kW | 1 | R |
| 8220 | 2 | Total inline system reactive power | Float32 | kvar | 1 | R |
| 8222 | 2 | Total inline system apparent power | Float32 | kVA | 1 | R |
| 8224 | 2 | Total inline system power factor | Float32 | - | 1 | R |
| 8226 | 2 | Total inline system load nature Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C). | Float32 | - | 1 | R |
| 8228 | 2 | Active power L1 | Float32 | kW | 1 | R |
| 8230 | 2 | Active power L2 | Float32 | kW | 1 | R |
| 8232 | 2 | Active power L3 | Float32 | kW | 1 | R |
| 8234 | 2 | Reactive power L1 | Float32 | kvar | 1 | R |
| 8236 | 2 | Reactive power L2 | Float32 | kvar | 1 | R |
| 8238 | 2 | Reactive power L3 | Float32 | kvar | 1 | R |
| 8240 | 2 | Apparent power L1 | Float32 | kVA | 1 | R |
| 8242 | 2 | Apparent power L2 | Float32 | kVA | 1 | R |
| 8244 | 2 | Apparent power L3 | Float32 | kVA | 1 | R |
| 8246 | 2 | Power factor L1 | Float32 | - | 1 | R |
| 8248 | 2 | Power factor L2 | Float32 | - | 1 | R |
| 8250 | 2 | Power factor L3 | Float32 | - | 1 | R |
| 8252 | 2 | Load nature A Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C). | Float32 | - | 1 | R |
| 8254 | 2 | Load nature B Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C). | Float32 | - | 1 | R |
| 8256 | 2 | Load nature C Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C). | Float32 | - | 1 | R |
| 9472 | 2 | Imported active energy L1 | UInt32 | kWh | 0.1 | RW |
| 9474 | 2 | Imported active energy L2 | UInt32 | kWh | 0.1 | RW |
| 9476 | 2 | Imported active energy L3 | UInt32 | kWh | 0.1 | RW |
| 9478 | 2 | Imported active energy, total (Sum) | UInt32 | kWh | 0.1 | RW |
| 11008 | 2 | Imported reactive energy L1 | UInt32 | kvarh | 0.1 | RW |
| 11010 | 2 | Imported reactive energy L2 | UInt32 | kvarh | 0.1 | RW |
| 11012 | 2 | Imported reactive energy L3 | UInt32 | kvarh | 0.1 | RW |
| 11014 | 2 | Imported reactive energy, total (Sum) | UInt32 | kvarh | 0.1 | RW |
| 11064 | 2 | Imported apparent energy L1 | UInt32 | kVAh | 0.1 | RW |
| 11066 | 2 | Imported apparent energy L2 | UInt32 | kVAh | 0.1 | RW |
| 11068 | 2 | Imported apparent energy L3 | UInt32 | kVAh | 0.1 | RW |
| 11070 | 2 | Imported apparent energy, total (Sum) | UInt32 | kVAh | 0.1 | RW |
| 11520 | 2 | Total inline system active power demand | Float32 | kW | 1 | R |
| 11522 | 2 | Total inline system active power demand prediction Predicted demand for the running demand window. | Float32 | kW | 1 | R |
| 11524 | 2 | Maximum total inline system active power demand Peak demand since the last demand-max reset. | Float32 | kW | 1 | R |
| 11529 | 2 | Total inline system reactive power demand | Float32 | kvar | 1 | R |
| 11531 | 2 | Total inline system reactive power demand prediction Predicted demand for the running demand window. | Float32 | kvar | 1 | R |
| 11533 | 2 | Maximum total inline system reactive power demand Peak demand since the last demand-max reset. | Float32 | kvar | 1 | R |
| 11538 | 2 | Total inline system apparent power demand | Float32 | kVA | 1 | R |
| 11540 | 2 | Total inline system apparent power demand prediction Predicted demand for the running demand window. | Float32 | kVA | 1 | R |
| 11542 | 2 | Maximum total inline system apparent power demand Peak demand since the last demand-max reset. | Float32 | kVA | 1 | R |
| 11547 | 2 | Total inline system current demand (average) | Float32 | A | 1 | R |
| 11549 | 2 | Total inline system current demand prediction Predicted demand for the running demand window. | Float32 | A | 1 | R |
| 11551 | 2 | Maximum total inline system current demand Peak demand since the last demand-max reset. | Float32 | A | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
TCP device: the AcuRev 2100 has its own Ethernet port and Modbus TCP server. Sources: Accuenergy "AcuRev 2100 Modbus Map v1.00" (vendor XLSX: hex and decimal address, type, size and read/write right per register) and the "AcuRev 2100 Multi-Circuit Power Energy Meter User Manual" V1.1.10 (July 2026): ch. 4 (Modbus TCP address default 1; RS-485 default address 1, 19200 bps, parity None 1), 5.1.1 (RTU frame: 8 data bits, no/odd/even parity, 1 stop bit) and 5.3 (a Dword is 32 bit, high word first). Energy counters are 32-bit unsigned, scaled 0.1 kWh: the map's range column prints "Max 999999999 (99999999.9)", the manual's address table prints "IMP=Rx/10" on every energy register, and the worked example in 5.2.5 reads 123456 as 12345.6 kWh. Table 5-14 instead prints "Energy E=Rx/100"; that one line contradicts the other three and is not followed. Every block is read with function code 03, so all rows are holding registers. The energy blocks are RW because both documents print them writable (they can be preset), as accuenergy-acurev-1310 does. Real-time and demand values are floats. No Modbus TCP port is printed, so the seed keeps 502. Seeded: the inline (three-phase) block, the four inline import energies and the inline demand block. Left out: the repeats of the 12-value block for every individual and user channel, the demand-max timestamps, meter run time and clock, demand-max reset and wire check, TOU, DI/RO state, datalog and daily energy history. The power-quality sheet is a scope decision: its THD, crest-factor and THF rows are bare Words whose scale and unit no document prints, the harmonics are grouped 29-register ranges, and the manual's own power-quality table prints address, parameter and description on drifting baselines. Not a duplicate of the other Accuenergy seeds: the AcuRev 2100 is a multi-circuit tenant submeter with its own map and Ethernet interface. The map prints no unit column; the V/A/kW/kvar/kVA/Hz labels are the manual's units.