AcuRev 2100 series multi-circuit power and energy meter (18 circuits) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
81922
Frequency
Float32Hz1R
81942
Voltage L1-N (U1)
Float32V1R
81962
Voltage L2-N (U2)
Float32V1R
81982
Voltage L3-N (U3)
Float32V1R
82002
Average line-to-neutral voltage (Uavg)
Float32V1R
82022
Line-to-line voltage L1-L2 (U12)
Float32V1R
82042
Line-to-line voltage L2-L3 (U23)
Float32V1R
82062
Line-to-line voltage L3-L1 (U31)
Float32V1R
82082
Average line-to-line voltage (Ulavg)
Float32V1R
82102
Current L1
Float32A1R
82122
Current L2
Float32A1R
82142
Current L3
Float32A1R
82162
Average current
Float32A1R
82182
Total inline system active power
Float32kW1R
82202
Total inline system reactive power
Float32kvar1R
82222
Total inline system apparent power
Float32kVA1R
82242
Total inline system power factor
Float32-1R
82262
Total inline system load nature
Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C).
Float32-1R
82282
Active power L1
Float32kW1R
82302
Active power L2
Float32kW1R
82322
Active power L3
Float32kW1R
82342
Reactive power L1
Float32kvar1R
82362
Reactive power L2
Float32kvar1R
82382
Reactive power L3
Float32kvar1R
82402
Apparent power L1
Float32kVA1R
82422
Apparent power L2
Float32kVA1R
82442
Apparent power L3
Float32kVA1R
82462
Power factor L1
Float32-1R
82482
Power factor L2
Float32-1R
82502
Power factor L3
Float32-1R
82522
Load nature A
Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C).
Float32-1R
82542
Load nature B
Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C).
Float32-1R
82562
Load nature C
Values: 1 = resistive (R), 2 = inductive (L), 3 = capacitive (C).
Float32-1R
94722
Imported active energy L1
UInt32kWh0.1RW
94742
Imported active energy L2
UInt32kWh0.1RW
94762
Imported active energy L3
UInt32kWh0.1RW
94782
Imported active energy, total (Sum)
UInt32kWh0.1RW
110082
Imported reactive energy L1
UInt32kvarh0.1RW
110102
Imported reactive energy L2
UInt32kvarh0.1RW
110122
Imported reactive energy L3
UInt32kvarh0.1RW
110142
Imported reactive energy, total (Sum)
UInt32kvarh0.1RW
110642
Imported apparent energy L1
UInt32kVAh0.1RW
110662
Imported apparent energy L2
UInt32kVAh0.1RW
110682
Imported apparent energy L3
UInt32kVAh0.1RW
110702
Imported apparent energy, total (Sum)
UInt32kVAh0.1RW
115202
Total inline system active power demand
Float32kW1R
115222
Total inline system active power demand prediction
Predicted demand for the running demand window.
Float32kW1R
115242
Maximum total inline system active power demand
Peak demand since the last demand-max reset.
Float32kW1R
115292
Total inline system reactive power demand
Float32kvar1R
115312
Total inline system reactive power demand prediction
Predicted demand for the running demand window.
Float32kvar1R
115332
Maximum total inline system reactive power demand
Peak demand since the last demand-max reset.
Float32kvar1R
115382
Total inline system apparent power demand
Float32kVA1R
115402
Total inline system apparent power demand prediction
Predicted demand for the running demand window.
Float32kVA1R
115422
Maximum total inline system apparent power demand
Peak demand since the last demand-max reset.
Float32kVA1R
115472
Total inline system current demand (average)
Float32A1R
115492
Total inline system current demand prediction
Predicted demand for the running demand window.
Float32A1R
115512
Maximum total inline system current demand
Peak demand since the last demand-max reset.
Float32A1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

TCP device: the AcuRev 2100 has its own Ethernet port and Modbus TCP server. Sources: Accuenergy "AcuRev 2100 Modbus Map v1.00" (vendor XLSX: hex and decimal address, type, size and read/write right per register) and the "AcuRev 2100 Multi-Circuit Power Energy Meter User Manual" V1.1.10 (July 2026): ch. 4 (Modbus TCP address default 1; RS-485 default address 1, 19200 bps, parity None 1), 5.1.1 (RTU frame: 8 data bits, no/odd/even parity, 1 stop bit) and 5.3 (a Dword is 32 bit, high word first). Energy counters are 32-bit unsigned, scaled 0.1 kWh: the map's range column prints "Max 999999999 (99999999.9)", the manual's address table prints "IMP=Rx/10" on every energy register, and the worked example in 5.2.5 reads 123456 as 12345.6 kWh. Table 5-14 instead prints "Energy E=Rx/100"; that one line contradicts the other three and is not followed. Every block is read with function code 03, so all rows are holding registers. The energy blocks are RW because both documents print them writable (they can be preset), as accuenergy-acurev-1310 does. Real-time and demand values are floats. No Modbus TCP port is printed, so the seed keeps 502. Seeded: the inline (three-phase) block, the four inline import energies and the inline demand block. Left out: the repeats of the 12-value block for every individual and user channel, the demand-max timestamps, meter run time and clock, demand-max reset and wire check, TOU, DI/RO state, datalog and daily energy history. The power-quality sheet is a scope decision: its THD, crest-factor and THF rows are bare Words whose scale and unit no document prints, the harmonics are grouped 29-register ranges, and the manual's own power-quality table prints address, parameter and description on drifting baselines. Not a duplicate of the other Accuenergy seeds: the AcuRev 2100 is a multi-circuit tenant submeter with its own map and Ethernet interface. The map prints no unit column; the V/A/kW/kvar/kVA/Hz labels are the manual's units.