Acuvim II (Acuvim-II V3, AXM-WEB2 option) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
163842
Frequency
Float32Hz1R
163862
Phase A line-to-neutral voltage (Ua)
Float32V1R
163882
Phase B line-to-neutral voltage (Ub)
Float32V1R
163902
Phase C line-to-neutral voltage (Uc)
Float32V1R
163922
Average line-to-neutral voltage (Uavg)
Float32V1R
163942
Line voltage AB (Uab)
Float32V1R
163962
Line voltage BC (Ubc)
Float32V1R
163982
Line voltage CA (Uca)
Float32V1R
164002
Average line voltage (Ulavg)
Float32V1R
164022
Phase A current (Ia)
Float32A1R
164042
Phase B current (Ib)
Float32A1R
164062
Phase C current (Ic)
Float32A1R
164082
Average phase current (Iavg)
Float32A1R
164102
Neutral current (In)
Float32A1R
164122
Phase A active power (Pa)
Float register holds W, value shown in kW (P = Rx / 1000 in the vendor map).
Float32kW0.001R
164142
Phase B active power (Pb)
Float register holds W, value shown in kW (P = Rx / 1000 in the vendor map).
Float32kW0.001R
164162
Phase C active power (Pc)
Float register holds W, value shown in kW (P = Rx / 1000 in the vendor map).
Float32kW0.001R
164182
Total system active power (Psum)
Float register holds W, value shown in kW (P = Rx / 1000 in the vendor map).
Float32kW0.001R
164202
Phase A reactive power (Qa)
Float register holds var, value shown in kvar (Q = Rx / 1000 in the vendor map).
Float32kvar0.001R
164222
Phase B reactive power (Qb)
Float register holds var, value shown in kvar (Q = Rx / 1000 in the vendor map).
Float32kvar0.001R
164242
Phase C reactive power (Qc)
Float register holds var, value shown in kvar (Q = Rx / 1000 in the vendor map).
Float32kvar0.001R
164262
Total reactive power (Qsum)
Float register holds var, value shown in kvar (Q = Rx / 1000 in the vendor map).
Float32kvar0.001R
164282
Phase A apparent power (Sa)
Float register holds VA, value shown in kVA (S = Rx / 1000 in the vendor map).
Float32kVA0.001R
164302
Phase B apparent power (Sb)
Float register holds VA, value shown in kVA (S = Rx / 1000 in the vendor map).
Float32kVA0.001R
164322
Phase C apparent power (Sc)
Float register holds VA, value shown in kVA (S = Rx / 1000 in the vendor map).
Float32kVA0.001R
164342
Total apparent power (Ssum)
Float register holds VA, value shown in kVA (S = Rx / 1000 in the vendor map).
Float32kVA0.001R
164362
Phase A power factor (PFa)
Float32-1R
164382
Phase B power factor (PFb)
Float32-1R
164402
Phase C power factor (PFc)
Float32-1R
164422
Total power factor (PFsum)
Float32-1R
164442
Voltage unbalance (U_unbl)
Float32%1R
164462
Current unbalance (I_unbl)
Float32%1R
164482
Load characteristic (L/C/R)
Vendor values: 76.0 = inductive (L), 67.0 = capacitive (C), 82.0 = resistive (R).
Float32-1R
123562
Phase A displacement power factor (DPFa)
Float32-1R
123582
Phase B displacement power factor (DPFb)
Float32-1R
123602
Phase C displacement power factor (DPFc)
Float32-1R
125062
System displacement power factor (DPF)
Float32-1R
164502
Active power demand (P_Dmd)
Float32kW0.001R
164522
Reactive power demand (Q_Dmd)
Float32kvar0.001R
164542
Apparent power demand (S_Dmd)
Float32kVA0.001R
179202
Phase A current demand (Ia_Dmd)
Float32A1R
179222
Phase B current demand (Ib_Dmd)
Float32A1R
179242
Phase C current demand (Ic_Dmd)
Float32A1R
123622
Predictive active power demand (P_Dmd_Pred)
Float32kW0.001R
123642
Predictive reactive power demand (Q_Dmd_Pred)
Float32kvar0.001R
123662
Predictive apparent power demand (S_Dmd_Pred)
Float32kVA0.001R
187832
Residual current (I_res)
Float32A1R
164562
Import active energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kWh0.1RW
164582
Export active energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kWh0.1RW
164602
Import reactive energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kvarh0.1RW
164622
Export reactive energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kvarh0.1RW
164642
Total active energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kWh0.1RW
164662
Net active energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
Int32kWh0.1RW
164682
Total reactive energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kvarh0.1RW
164702
Net reactive energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000. The vendor map types this row UInt32 although its range is marked +/-.
UInt32kvarh0.1RW
164722
Apparent energy
Primary-display mode scaling (Ep = Rx / 10); the map also documents a secondary-display mode with / 1000.
UInt32kVAh0.1RW
179522
Phase A import active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179542
Phase A export active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179562
Phase B import active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179582
Phase B export active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179602
Phase C import active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179622
Phase C export active energy
Primary-display mode scaling (E = Rx / 10).
UInt32kWh0.1RW
179642
Phase A import reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179662
Phase A export reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179682
Phase B import reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179702
Phase B export reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179722
Phase C import reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179742
Phase C export reactive energy
Primary-display mode scaling (E = Rx / 10).
UInt32kvarh0.1RW
179762
Phase A apparent energy
Primary-display mode scaling (E = Rx / 10).
UInt32kVAh0.1RW
179782
Phase B apparent energy
Primary-display mode scaling (E = Rx / 10).
UInt32kVAh0.1RW
179802
Phase C apparent energy
Primary-display mode scaling (E = Rx / 10).
UInt32kVAh0.1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Accuenergy 'Acuvim II V3 Modbus Map' v1.10 (2026-09-25), the vendor's own spreadsheet at https://www.accuenergy.com/wp-content/uploads/Acuvim-II-V3-Modbus-map-v1.10.xlsx , read sheet by sheet ('Basic Real-time (FLOAT)', 'Energy'). The same document's 'Parameter & Status Settings' sheet gives the factory communication defaults used here: communication address 1, baud rate 19200, parity 'Non1' (no parity, 1 stop bit), 8 data bits. Every row below is marked '03H Read' in the map, i.e. a holding register read with function code 03. Addresses are the map's decimal column, which equals its hex column (4000H = 16384), so they are wire addresses (zero-based). The Acuvim II Power Meter User Manual 1040E1303 states the 32-bit format is stored 'with the high word at the front and the low word at the end', which is why word order is HighFirst. Energy rows use the map's primary-display relationship (Rx / 10); the same map documents an alternative secondary-display relationship (Rx / 1000) selected by register 1019H. Deliberate omissions: the 49xx energy block (the vendor's relationship column there repeats the 'Esc=Rx/10' formula for every row and contradicts its own parameter names), the TOU/max-min/harmonic/alarm/IO/data-log sheets, and the 16-bit integer copy of the same measurements in 'Basic Real-time (INT)' (its formulas depend on the programmed PT/CT ratios).