Accuenergy · Energy meter

AcuRev 4100 multi-channel branch-circuit submeter (24 input channels) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
81922
System frequency
Float32Hz1R
81942
Phase A line-to-neutral voltage
Float32V1R
81962
Phase B line-to-neutral voltage
Float32V1R
81982
Phase C line-to-neutral voltage
Float32V1R
82002
Average line-to-neutral voltage
Float32V1R
82022
Phase A-B line-to-line voltage
Float32V1R
82042
Phase B-C line-to-line voltage
Float32V1R
82062
Phase C-A line-to-line voltage
Float32V1R
82082
Average line-to-line voltage
Float32V1R
82102
Phase A voltage phase angle
Float32°1R
82122
Phase B voltage phase angle
Float32°1R
82142
Phase C voltage phase angle
Float32°1R
82162
Phase A current
Float32A1R
82182
Phase A active power
Float32kW1R
82202
Phase A reactive power
Float32kvar1R
82222
Phase A apparent power
Float32kVA1R
82262
Phase A power factor
Float32-1R
82282
Phase B current
Float32A1R
82302
Phase B active power
Float32kW1R
82322
Phase B reactive power
Float32kvar1R
82342
Phase B apparent power
Float32kVA1R
82382
Phase B power factor
Float32-1R
82402
Phase C current
Float32A1R
82422
Phase C active power
Float32kW1R
82442
Phase C reactive power
Float32kvar1R
82462
Phase C apparent power
Float32kVA1R
82502
Phase C power factor
Float32-1R
82522
System average current
Float32A1R
82542
System active power
Float32kW1R
82562
System reactive power
Float32kvar1R
82582
System apparent power
Float32kVA1R
82622
System power factor
Float32-1R
89602
Phase A current demand
Float32A1R
89622
Phase A import active power demand
Float32kW1R
89642
Phase A export active power demand
Float32kW1R
89662
Phase A import reactive power demand
Float32kvar1R
89682
Phase A export reactive power demand
Float32kvar1R
89702
Phase A apparent power demand
Float32kVA1R
89722
Phase B current demand
Float32A1R
89742
Phase B import active power demand
Float32kW1R
89762
Phase B export active power demand
Float32kW1R
89782
Phase B import reactive power demand
Float32kvar1R
89802
Phase B export reactive power demand
Float32kvar1R
89822
Phase B apparent power demand
Float32kVA1R
89842
Phase C current demand
Float32A1R
89862
Phase C import active power demand
Float32kW1R
89882
Phase C export active power demand
Float32kW1R
89902
Phase C import reactive power demand
Float32kvar1R
89922
Phase C export reactive power demand
Float32kvar1R
89942
Phase C apparent power demand
Float32kVA1R
89962
System average current demand
Float32A1R
89982
System import active power demand
Float32kW1R
90002
System export active power demand
Float32kW1R
90022
System import reactive power demand
Float32kvar1R
90042
System export reactive power demand
Float32kvar1R
90062
System apparent power demand
Float32kVA1R
122884
Phase A active energy import
Float64kWh1R
122924
Phase A active energy export
Float64kWh1R
122964
Phase A active energy net
Float64kWh1R
123004
Phase A active energy total
Float64kWh1R
123044
Phase A reactive energy import
Float64kvarh1R
123084
Phase A reactive energy export
Float64kvarh1R
123124
Phase A reactive energy net
Float64kvarh1R
123164
Phase A reactive energy total
Float64kvarh1R
123204
Phase A apparent energy
Float64kVAh1R
123244
Phase B active energy import
Float64kWh1R
123284
Phase B active energy export
Float64kWh1R
123324
Phase B active energy net
Float64kWh1R
123364
Phase B active energy total
Float64kWh1R
123404
Phase B reactive energy import
Float64kvarh1R
123444
Phase B reactive energy export
Float64kvarh1R
123484
Phase B reactive energy net
Float64kvarh1R
123524
Phase B reactive energy total
Float64kvarh1R
123564
Phase B apparent energy
Float64kVAh1R
123604
Phase C active energy import
Float64kWh1R
123644
Phase C active energy export
Float64kWh1R
123684
Phase C active energy net
Float64kWh1R
123724
Phase C active energy total
Float64kWh1R
123764
Phase C reactive energy import
Float64kvarh1R
123804
Phase C reactive energy export
Float64kvarh1R
123844
Phase C reactive energy net
Float64kvarh1R
123884
Phase C reactive energy total
Float64kvarh1R
123924
Phase C apparent energy
Float64kVAh1R
123964
System active energy import
Float64kWh1R
124004
System active energy export
Float64kWh1R
124044
System active energy net
Float64kWh1R
124084
System active energy total
Float64kWh1R
124124
System reactive energy import
Float64kvarh1R
124164
System reactive energy export
Float64kvarh1R
124204
System reactive energy net
Float64kvarh1R
124244
System reactive energy total
Float64kvarh1R
124284
System apparent energy
Float64kVAh1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

TCP device: the AcuRev 4100 has two Ethernet ports and a Modbus TCP server. Sources: Accuenergy "AcuRev 4100 Modbus Map v1.02" (vendor XLSX, sheet "Real time": system and per-phase basic parameters at 0x2000+, demand at 0x2300+; sheet "Energy": the energy counters at 0x3000+) and the "AcuRev 4100 Series Multi-Channel Branch Circuit Submeter User Manual" V1.0.1 (October 2026): Table 4-2 (Modbus TCP defaults: slave address 1, port 502), Table 4-1 (RS-485 defaults: address 1, 19200, None 1) and 5.3.1 (Word 16 bit, Dword 32 bit with the high word first, Float single precision in two registers). All blocks are function code 03, so every row is a holding register, and every row is read-only in the map. Power, demand and RMS values are IEEE-754 single precision in two registers; the energy counters are the map's "double" in four registers, stored here as Float64. The manual defines no double type, so the width comes from the map's four-register rows, the high-word-first order is the Dword convention applied to them, and no scaling relationship is printed for them, so they keep scale 1 - all three are declared conventions, not cited facts. The seed carries the system, phase A/B/C and demand blocks only: the map repeats the same 6-value block for each of the 24 input channels and 12 user channels and those per-branch rows are left out, as are the "Load nature" enum rows (the map prints no values for them) and the input-channel and user-channel demand blocks. This is not a duplicate of accuenergy-acurev-2100: the 4100 is the 24-channel branch-circuit submeter with a different register map (0x2000/0x2300/0x3000 blocks, 64-bit energies) and two Ethernet ports. The map prints no unit column either, so the V/A/kW/kvar/kVA/Hz/degree labels are the manual's engineering units for those parameters.