Accuenergy · Energy meter
AcuRev 4100 multi-channel branch-circuit submeter (24 input channels) Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 8192 | 2 | System frequency | Float32 | Hz | 1 | R |
| 8194 | 2 | Phase A line-to-neutral voltage | Float32 | V | 1 | R |
| 8196 | 2 | Phase B line-to-neutral voltage | Float32 | V | 1 | R |
| 8198 | 2 | Phase C line-to-neutral voltage | Float32 | V | 1 | R |
| 8200 | 2 | Average line-to-neutral voltage | Float32 | V | 1 | R |
| 8202 | 2 | Phase A-B line-to-line voltage | Float32 | V | 1 | R |
| 8204 | 2 | Phase B-C line-to-line voltage | Float32 | V | 1 | R |
| 8206 | 2 | Phase C-A line-to-line voltage | Float32 | V | 1 | R |
| 8208 | 2 | Average line-to-line voltage | Float32 | V | 1 | R |
| 8210 | 2 | Phase A voltage phase angle | Float32 | ° | 1 | R |
| 8212 | 2 | Phase B voltage phase angle | Float32 | ° | 1 | R |
| 8214 | 2 | Phase C voltage phase angle | Float32 | ° | 1 | R |
| 8216 | 2 | Phase A current | Float32 | A | 1 | R |
| 8218 | 2 | Phase A active power | Float32 | kW | 1 | R |
| 8220 | 2 | Phase A reactive power | Float32 | kvar | 1 | R |
| 8222 | 2 | Phase A apparent power | Float32 | kVA | 1 | R |
| 8226 | 2 | Phase A power factor | Float32 | - | 1 | R |
| 8228 | 2 | Phase B current | Float32 | A | 1 | R |
| 8230 | 2 | Phase B active power | Float32 | kW | 1 | R |
| 8232 | 2 | Phase B reactive power | Float32 | kvar | 1 | R |
| 8234 | 2 | Phase B apparent power | Float32 | kVA | 1 | R |
| 8238 | 2 | Phase B power factor | Float32 | - | 1 | R |
| 8240 | 2 | Phase C current | Float32 | A | 1 | R |
| 8242 | 2 | Phase C active power | Float32 | kW | 1 | R |
| 8244 | 2 | Phase C reactive power | Float32 | kvar | 1 | R |
| 8246 | 2 | Phase C apparent power | Float32 | kVA | 1 | R |
| 8250 | 2 | Phase C power factor | Float32 | - | 1 | R |
| 8252 | 2 | System average current | Float32 | A | 1 | R |
| 8254 | 2 | System active power | Float32 | kW | 1 | R |
| 8256 | 2 | System reactive power | Float32 | kvar | 1 | R |
| 8258 | 2 | System apparent power | Float32 | kVA | 1 | R |
| 8262 | 2 | System power factor | Float32 | - | 1 | R |
| 8960 | 2 | Phase A current demand | Float32 | A | 1 | R |
| 8962 | 2 | Phase A import active power demand | Float32 | kW | 1 | R |
| 8964 | 2 | Phase A export active power demand | Float32 | kW | 1 | R |
| 8966 | 2 | Phase A import reactive power demand | Float32 | kvar | 1 | R |
| 8968 | 2 | Phase A export reactive power demand | Float32 | kvar | 1 | R |
| 8970 | 2 | Phase A apparent power demand | Float32 | kVA | 1 | R |
| 8972 | 2 | Phase B current demand | Float32 | A | 1 | R |
| 8974 | 2 | Phase B import active power demand | Float32 | kW | 1 | R |
| 8976 | 2 | Phase B export active power demand | Float32 | kW | 1 | R |
| 8978 | 2 | Phase B import reactive power demand | Float32 | kvar | 1 | R |
| 8980 | 2 | Phase B export reactive power demand | Float32 | kvar | 1 | R |
| 8982 | 2 | Phase B apparent power demand | Float32 | kVA | 1 | R |
| 8984 | 2 | Phase C current demand | Float32 | A | 1 | R |
| 8986 | 2 | Phase C import active power demand | Float32 | kW | 1 | R |
| 8988 | 2 | Phase C export active power demand | Float32 | kW | 1 | R |
| 8990 | 2 | Phase C import reactive power demand | Float32 | kvar | 1 | R |
| 8992 | 2 | Phase C export reactive power demand | Float32 | kvar | 1 | R |
| 8994 | 2 | Phase C apparent power demand | Float32 | kVA | 1 | R |
| 8996 | 2 | System average current demand | Float32 | A | 1 | R |
| 8998 | 2 | System import active power demand | Float32 | kW | 1 | R |
| 9000 | 2 | System export active power demand | Float32 | kW | 1 | R |
| 9002 | 2 | System import reactive power demand | Float32 | kvar | 1 | R |
| 9004 | 2 | System export reactive power demand | Float32 | kvar | 1 | R |
| 9006 | 2 | System apparent power demand | Float32 | kVA | 1 | R |
| 12288 | 4 | Phase A active energy import | Float64 | kWh | 1 | R |
| 12292 | 4 | Phase A active energy export | Float64 | kWh | 1 | R |
| 12296 | 4 | Phase A active energy net | Float64 | kWh | 1 | R |
| 12300 | 4 | Phase A active energy total | Float64 | kWh | 1 | R |
| 12304 | 4 | Phase A reactive energy import | Float64 | kvarh | 1 | R |
| 12308 | 4 | Phase A reactive energy export | Float64 | kvarh | 1 | R |
| 12312 | 4 | Phase A reactive energy net | Float64 | kvarh | 1 | R |
| 12316 | 4 | Phase A reactive energy total | Float64 | kvarh | 1 | R |
| 12320 | 4 | Phase A apparent energy | Float64 | kVAh | 1 | R |
| 12324 | 4 | Phase B active energy import | Float64 | kWh | 1 | R |
| 12328 | 4 | Phase B active energy export | Float64 | kWh | 1 | R |
| 12332 | 4 | Phase B active energy net | Float64 | kWh | 1 | R |
| 12336 | 4 | Phase B active energy total | Float64 | kWh | 1 | R |
| 12340 | 4 | Phase B reactive energy import | Float64 | kvarh | 1 | R |
| 12344 | 4 | Phase B reactive energy export | Float64 | kvarh | 1 | R |
| 12348 | 4 | Phase B reactive energy net | Float64 | kvarh | 1 | R |
| 12352 | 4 | Phase B reactive energy total | Float64 | kvarh | 1 | R |
| 12356 | 4 | Phase B apparent energy | Float64 | kVAh | 1 | R |
| 12360 | 4 | Phase C active energy import | Float64 | kWh | 1 | R |
| 12364 | 4 | Phase C active energy export | Float64 | kWh | 1 | R |
| 12368 | 4 | Phase C active energy net | Float64 | kWh | 1 | R |
| 12372 | 4 | Phase C active energy total | Float64 | kWh | 1 | R |
| 12376 | 4 | Phase C reactive energy import | Float64 | kvarh | 1 | R |
| 12380 | 4 | Phase C reactive energy export | Float64 | kvarh | 1 | R |
| 12384 | 4 | Phase C reactive energy net | Float64 | kvarh | 1 | R |
| 12388 | 4 | Phase C reactive energy total | Float64 | kvarh | 1 | R |
| 12392 | 4 | Phase C apparent energy | Float64 | kVAh | 1 | R |
| 12396 | 4 | System active energy import | Float64 | kWh | 1 | R |
| 12400 | 4 | System active energy export | Float64 | kWh | 1 | R |
| 12404 | 4 | System active energy net | Float64 | kWh | 1 | R |
| 12408 | 4 | System active energy total | Float64 | kWh | 1 | R |
| 12412 | 4 | System reactive energy import | Float64 | kvarh | 1 | R |
| 12416 | 4 | System reactive energy export | Float64 | kvarh | 1 | R |
| 12420 | 4 | System reactive energy net | Float64 | kvarh | 1 | R |
| 12424 | 4 | System reactive energy total | Float64 | kvarh | 1 | R |
| 12428 | 4 | System apparent energy | Float64 | kVAh | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
TCP device: the AcuRev 4100 has two Ethernet ports and a Modbus TCP server. Sources: Accuenergy "AcuRev 4100 Modbus Map v1.02" (vendor XLSX, sheet "Real time": system and per-phase basic parameters at 0x2000+, demand at 0x2300+; sheet "Energy": the energy counters at 0x3000+) and the "AcuRev 4100 Series Multi-Channel Branch Circuit Submeter User Manual" V1.0.1 (October 2026): Table 4-2 (Modbus TCP defaults: slave address 1, port 502), Table 4-1 (RS-485 defaults: address 1, 19200, None 1) and 5.3.1 (Word 16 bit, Dword 32 bit with the high word first, Float single precision in two registers). All blocks are function code 03, so every row is a holding register, and every row is read-only in the map. Power, demand and RMS values are IEEE-754 single precision in two registers; the energy counters are the map's "double" in four registers, stored here as Float64. The manual defines no double type, so the width comes from the map's four-register rows, the high-word-first order is the Dword convention applied to them, and no scaling relationship is printed for them, so they keep scale 1 - all three are declared conventions, not cited facts. The seed carries the system, phase A/B/C and demand blocks only: the map repeats the same 6-value block for each of the 24 input channels and 12 user channels and those per-branch rows are left out, as are the "Load nature" enum rows (the map prints no values for them) and the input-channel and user-channel demand blocks. This is not a duplicate of accuenergy-acurev-2100: the 4100 is the 24-channel branch-circuit submeter with a different register map (0x2000/0x2300/0x3000 blocks, 64-bit energies) and two Ethernet ports. The map prints no unit column either, so the V/A/kW/kvar/kVA/Hz/degree labels are the manual's engineering units for those parameters.