All devices

Accuenergy · Energy meter

AcuRev 1310 / 1312 / 1313 / 1314 (DIN-rail three-phase meter) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
46162
System active power demand
Float32kW1R
46182
System reactive power demand
Float32kvar1R
46202
System apparent power demand
Float32kVA1R
46222
Phase A current demand
Float32A1R
46242
Phase B current demand
Float32A1R
46262
Phase C current demand
Float32A1R
81922
Total current
Float32A1R
81942
Phase A current
Float32A1R
81962
Phase B current
Float32A1R
81982
Phase C current
Float32A1R
82002
Phase voltage average
Float32V1R
82022
Phase A voltage
Float32V1R
82042
Phase B voltage
Float32V1R
82062
Phase C voltage
Float32V1R
82082
Line voltage average
The vendor table prints the hex span as '2001H-2011H' (a typo); the decimal span it prints in the same row, 8208-8209, is what this seed uses.
Float32V1R
82102
Line voltage AB
Float32V1R
82122
Line voltage BC
Float32V1R
82142
Line voltage CA
Float32V1R
82162
Frequency
Float32Hz1R
82182
Total active power
Float32kW1R
82202
Phase A active power
Float32kW1R
82222
Phase B active power
Float32kW1R
82242
Phase C active power
Float32kW1R
82262
Total apparent power
Float32kVA1R
82282
Phase A apparent power
Float32kVA1R
82302
Phase B apparent power
Float32kVA1R
82322
Phase C apparent power
Float32kVA1R
82342
Total reactive power
Float32kvar1R
82362
Phase A reactive power
Float32kvar1R
82382
Phase B reactive power
Float32kvar1R
82402
Phase C reactive power
Float32kvar1R
82422
Power factor
Float32-1R
82442
Phase A power factor
Float32-1R
82462
Phase B power factor
Float32-1R
82482
Phase C power factor
Float32-1R
82502
Phase angle V1/V1
Float32deg1R
82522
Phase angle of V2 to V1 (V23 to V12 in three-phase three-wire wiring)
Float32deg1R
82542
Phase angle of V3 to V1 (V31 to V12 in three-phase three-wire wiring)
Float32deg1R
82562
Phase angle of I1 to V1 (I1 to V12 in three-phase three-wire wiring)
Float32deg1R
82582
Phase angle of I2 to V1 (I2 to V12 in three-phase three-wire wiring)
Float32deg1R
82602
Phase angle of I3 to V1
Float32deg1R
82622
Total exported active energy
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82642
Exported active energy, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82662
Exported active energy, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82682
Exported active energy, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82702
Total imported active energy
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82722
Imported active energy, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82742
Imported active energy, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82762
Imported active energy, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kWh0.01RW
82782
Total exported apparent energy
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82802
Exported apparent energy, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82822
Exported apparent energy, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82842
Exported apparent energy, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82862
Total imported apparent energy
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82882
Imported apparent energy, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82902
Imported apparent energy, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82922
Imported apparent energy, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kVAh0.01RW
82942
Total imported reactive energy, quad 1
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
82962
Imported reactive energy, quad 1, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
82982
Imported reactive energy, quad 1, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83002
Imported reactive energy, quad 1, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83022
Total imported reactive energy, quad 2
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83042
Imported reactive energy, quad 2, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83062
Imported reactive energy, quad 2, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83082
Imported reactive energy, quad 2, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83102
Total imported reactive energy, quad 3
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83122
Imported reactive energy, quad 3, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83142
Imported reactive energy, quad 3, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83162
Imported reactive energy, quad 3, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83182
Total imported reactive energy, quad 4
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83202
Imported reactive energy, quad 4, phase A
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83222
Imported reactive energy, quad 4, phase B
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW
83242
Imported reactive energy, quad 4, phase C
Scaled 0.01: section 5.2 ‘Communication Format’ works the total active energy through ‘Real value = Communication value/100’ (response 00H 00H 00H 7FH = 1.27 kWh), and register 21AH/538 ‘Energy Display Decimal’ has a factory value of 1 decimal place. The vendor table types the counter 'Dword' (32-bit, high word first); its range column prints '0-9999999999kWh' even on the apparent and reactive counters, so the unit in this row is taken from the parameter name.
UInt32kvarh0.01RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Accuenergy 'AcuRev 1310 DIN-Rail Power Meter - User Manual' v1.2.11 (October 2026), chapter 5 'Communication', section 5.3.3 'Parameter Address Table' - the read-only real-time block (Table 5-9 onwards, addresses 2000H-2045H), the demand block (1208H-1213H) and the energy blocks (2046H-2085H) - https://www.accuenergy.com/wp-content/uploads/AcuRev-1310-User-Manual.pdf . The same table gives the factory communication defaults used here: meter address 1 (200H), baud rate 19200 (201H) and parity setting 3, which the manual defines as 'No parity, Stop Bit 1' (202H) - i.e. 19200 8N1, unit 1. Both the hex and the decimal column of the address table are printed and agree, so the addresses are wire addresses. Function code 03 is used throughout ('float' and 'Dword' rows). The energy counters are scaled 0.01 per section 5.2 ('Real value = Communication value/100', worked example 127 = 1.27 kWh) and register 21AH/538 'Energy Display Decimal' (factory value 1); the real-time and demand values are floats and carry scale 1. The address table itself has no unit column; the units recorded here are the ones the meter's own display menu prints for the same parameters ('System Active Power(kW)' etc.). Deliberate omissions: the seal/status/settings registers (100H-2xx), the meter and load running-time counters, the MAX/MIN record blocks, the TOU and tariff blocks, the event-log and alarm blocks, the harmonics/THD blocks and the 2200H+ multi-channel inline blocks (separate AcuRev 2100 family).