All devices

Schneider Electric · Energy meter

Acti9 PowerTag Energy (PTE / PTEnergy, via Panel Server, Smartlink or PowerTag Link) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
30002
RMS current on phase A
Float32A1R
30022
RMS current on phase B
Float32A1R
30042
RMS current on phase C
Float32A1R
30062
RMS current on Neutral
Float32A1R
30202
RMS phase-to-phase voltage A-B
Float32V1R
30222
RMS phase-to-phase voltage B-C
Float32V1R
30242
RMS phase-to-phase voltage C-A
Float32V1R
30282
RMS phase-to-neutral voltage A-N
Float32V1R
30302
RMS phase-to-neutral voltage B-N
Float32V1R
30322
RMS phase-to-neutral voltage C-N
Float32V1R
30542
Active power on phase A
Float32W1R
30562
Active power on phase B
Float32W1R
30582
Active power on phase C
Float32W1R
30602
Total active power
Float32W1R
30622
Reactive power on phase A
Float32VAR1R
30642
Reactive power on phase B
Float32VAR1R
30662
Reactive power on phase C
Float32VAR1R
30682
Total reactive power
Float32VAR1R
30702
Apparent power on phase A
Float32VA1R
30722
Apparent power on phase B
Float32VA1R
30742
Apparent power on phase C
Float32VA1R
30762
Total apparent power (arithmetic)
Float32VA1R
30782
Power factor on phase A
Float32-1R
30802
Power factor on phase B
Float32-1R
30822
Power factor on phase C
Float32-1R
30842
Total power factor
Float32-1R
30861
Power factor sign convention
UInt16-1R
31102
AC frequency
Float32Hz1R
31322
Device internal temperature
Float32°C1R
33022
Last RMS current measured on phase B when voltage loss occurred
Float32A1R
33042
Last RMS current measured on phase A when voltage loss occurred
Float32A1R
33062
Last RMS current measured on phase C when voltage loss occurred
Float32A1R
33102
Active power threshold for load operating time counter. Counter starts above the threshold value.
Float32W1R
37662
Demand total active power
Float32W1R
37702
Peak demand total active power
Float32W1R
305011
Product ID of the Panel Server
UInt16-1R
3050216
Commercial reference of the Panel Server
Ascii-1R
305186
Firmware version of the Panel Server Example - xxx.yyy.zzz
Ascii-1R
3052410
Serial number of the Panel Server
Ascii-1R
305348
Product model of the Panel Server
Ascii-1R
3100110
Device name of the wireless device. The user can enter maximum 20 characters.
Ascii-1R
310113
Label of the wireless device. The user can enter maximum five characters.
Ascii-1R
310141
Indicates the usage of the wireless device with:
UInt16-1R
310151
Phase sequence with:
UInt16-1R
310161
Mounting position
UInt16-1R
310181
Rated current of the protective device to the wireless device
UInt16A1R
310191
Electrical network system type
UInt16-1R
310202
Rated voltage:
Float32V1R
310221
Indicates the commodity of the wireless device 1. Electricity 2. Gas 3. Fuel oil 4. Air 5. Steam 6. Water 7. Environment 8. Other 9. Custom (Free text to enter): User can enter 10
UInt16-1R
310231
Reset the Peak Active Power Demand for this wireless device, Any value writen will reset Peak Active Power Demand to 0
UInt16-1RW
310241
Power supply type
UInt16-1R
310261
Virtual Modbus server address
UInt16-1R
310321
Wireless product identifier : 16131 - LV933071W, LV933072W, LV933073W 16132 - LV947600W, LV947602W, LV947603W 17200 - A9MEM1520 17201 - A9MEM1521 17202 - A9MEM1522 17203 - A9MEM1540
UInt16-1R
3104516
Vendor name
Ascii-1R
3106116
Commercial reference
Ascii-1R
310776
Firmware revision
Ascii-1R
310836
Hardware revision
Ascii-1R
3108910
Serial number
Ascii-1R
310998
Product range
Ascii-1R
311078
Product model
Ascii-1R
311158
Product family
Ascii-1R
311451
Validity of the RF communication between the device and Panel Server status.
Hex-1R
311461
Communication status between Panel Server and wireless devices.
Hex-1R
311472
Packet Error Rate (PER) of the device, received by Panel Server
Float32-1R
311492
RSSI of the device, received by Panel Server
Float32dBm1R
311511
Link Quality Indicator (LQI) of the device, received by Panel Server
UInt16-1R
311522
PER of gateway, calculated inside the Panel Server
Float32-1R
311542
Radio Signal Strength Indicator (RSSI) calculated inside the Panel Server
Float32dBm1R
311561
LQI, calculated inside the Panel Server
UInt16-1R
311572
PER – Maximum value between device and Panel Server
Float32-1R
311592
RSSI – Minimal value between device and Panel Server
Float32dBm1R
311611
LQI – Minimal value between device and Panel Server
UInt16-1R

Notes

Addresses are the decimal 'Register (dec)' column of Schneider's EcoStruxure Panel Server Modbus file DOCA0241EN (tabs PTE63-PoTag QO, PTEnergy250_630-PoTag Efram and PTE Rope-PoTag Rope). A PowerTag is a wireless sensor: it is not reachable directly, but the EcoStruxure Panel Server (PAS400/PAS600/PAS800) publishes each paired PowerTag on its Modbus TCP server (port 502) at the unit ID that matches the device's virtual Modbus address - the Panel Server lists that address and the sensor's RFID in its 'List of wireless devices' block (registers 501-700, see the Panel Server map). The same map is served by Acti9 Smartlink and PowerTag Link gateways on their RS-485 bus. Values are read-only, IEEE 754 single precision from register 3000. Every energy counter of a PowerTag is a 64-bit integer in Wh, which this format cannot express, so only the load-side measurements, demand and alarm values are listed. Not every reference provides every register: reactive power and frequency exist on the PTEnergy250/630 and Rope sensors, the single-phase references omit the B and C phases.