All devices

Schneider Electric · Energy gateway

Acti 9 Smartlink Modbus (A9XMSB11) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
1006
Serial number (ASCII, 12 characters)
Product serial number; the NULL character ends the string.
Ascii-1R
1093
Software version (ASCII, 6 characters)
For example "V0.0.1".
Ascii-1R
1121
Device status and diagnostic register
Bit 0 = 1 start-up phase, bit 1 = 1 operating phase, bit 2 = 1 downgraded mode (24 V supply too low or Ti24 overload), bit 3 = 1 failure mode, bit 6 = 1 invalid data, bit 7 = 1 invalid 24 V I/O, bit 13 = E2PROM error, bit 14 = RAM error, bit 15 = FLASH error. Bits 0 to 3 are exclusive.
Hex-1R
1201
Summary of channels 1 to 11, status word 1 (channels 1-8)
One bit per channel: bit N set means the channel data are valid. Word 1 covers channels 1 to 8.
Hex-1R
1211
Summary of channels 1 to 11, status word 2 (channels 9-11)
Bits 0 to 2 cover channels 9 to 11.
Hex-1R
1301
Summary of channels 1 to 11, orders word 1 (channels 1-8)
One bit per channel for the summary command word.
Hex-1RW
1311
Summary of channels 1 to 11, orders word 2 (channels 9-11)
Hex-1RW
1321
Summary of channels 1 to 11, orders word 3 (reserved)
Hex-1RW
1331
Summary of channels 1 to 11, orders word 4 (reserved)
Hex-1RW
140002
Power or flow indicator, channel 1 input I1
Power or flow of the impulse counter on channel 1 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140022
Power or flow indicator, channel 2 input I1
Power or flow of the impulse counter on channel 2 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140042
Power or flow indicator, channel 3 input I1
Power or flow of the impulse counter on channel 3 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140062
Power or flow indicator, channel 4 input I1
Power or flow of the impulse counter on channel 4 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140082
Power or flow indicator, channel 5 input I1
Power or flow of the impulse counter on channel 5 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140102
Power or flow indicator, channel 6 input I1
Power or flow of the impulse counter on channel 6 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140122
Power or flow indicator, channel 7 input I1
Power or flow of the impulse counter on channel 7 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140142
Power or flow indicator, channel 8 input I1
Power or flow of the impulse counter on channel 8 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140162
Power or flow indicator, channel 9 input I1
Power or flow of the impulse counter on channel 9 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140182
Power or flow indicator, channel 10 input I1
Power or flow of the impulse counter on channel 10 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140202
Power or flow indicator, channel 11 input I1
Power or flow of the impulse counter on channel 11 input 1 (3600 x pulse weight / time between two pulses).
Float32-1R
140222
Power or flow indicator, channel 1 input I2
Float32-1R
140242
Power or flow indicator, channel 2 input I2
Float32-1R
140262
Power or flow indicator, channel 3 input I2
Float32-1R
140282
Power or flow indicator, channel 4 input I2
Float32-1R
140302
Power or flow indicator, channel 5 input I2
Float32-1R
140322
Power or flow indicator, channel 6 input I2
Float32-1R
140342
Power or flow indicator, channel 7 input I2
Float32-1R
140362
Power or flow indicator, channel 8 input I2
Float32-1R
140382
Power or flow indicator, channel 9 input I2
Float32-1R
140402
Power or flow indicator, channel 10 input I2
Float32-1R
140422
Power or flow indicator, channel 11 input I2
Float32-1R
140502
Consumption meter, channel 1 input I1
Number of pulses of the meter on channel 1 input 1 multiplied by the pulse weight.
UInt32-1R
140522
Consumption meter, channel 2 input I1
Number of pulses of the meter on channel 2 input 1 multiplied by the pulse weight.
UInt32-1R
140542
Consumption meter, channel 3 input I1
Number of pulses of the meter on channel 3 input 1 multiplied by the pulse weight.
UInt32-1R
140562
Consumption meter, channel 4 input I1
Number of pulses of the meter on channel 4 input 1 multiplied by the pulse weight.
UInt32-1R
140582
Consumption meter, channel 5 input I1
Number of pulses of the meter on channel 5 input 1 multiplied by the pulse weight.
UInt32-1R
140602
Consumption meter, channel 6 input I1
Number of pulses of the meter on channel 6 input 1 multiplied by the pulse weight.
UInt32-1R
140622
Consumption meter, channel 7 input I1
Number of pulses of the meter on channel 7 input 1 multiplied by the pulse weight.
UInt32-1R
140642
Consumption meter, channel 8 input I1
Number of pulses of the meter on channel 8 input 1 multiplied by the pulse weight.
UInt32-1R
140662
Consumption meter, channel 9 input I1
Number of pulses of the meter on channel 9 input 1 multiplied by the pulse weight.
UInt32-1R
140682
Consumption meter, channel 10 input I1
Number of pulses of the meter on channel 10 input 1 multiplied by the pulse weight.
UInt32-1R
140702
Consumption meter, channel 11 input I1
Number of pulses of the meter on channel 11 input 1 multiplied by the pulse weight.
UInt32-1R
140722
Consumption meter, channel 1 input I2
UInt32-1R
140742
Consumption meter, channel 2 input I2
UInt32-1R
140762
Consumption meter, channel 3 input I2
UInt32-1R
140782
Consumption meter, channel 4 input I2
UInt32-1R
140802
Consumption meter, channel 5 input I2
UInt32-1R
140822
Consumption meter, channel 6 input I2
UInt32-1R
140842
Consumption meter, channel 7 input I2
UInt32-1R
140862
Consumption meter, channel 8 input I2
UInt32-1R
140882
Consumption meter, channel 9 input I2
UInt32-1R
140902
Consumption meter, channel 10 input I2
UInt32-1R
140922
Consumption meter, channel 11 input I2
UInt32-1R
141002
Operation counter, channel 1 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141022
Operation counter, channel 2 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141042
Operation counter, channel 3 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141062
Operation counter, channel 4 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141082
Operation counter, channel 5 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141102
Operation counter, channel 6 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141122
Operation counter, channel 7 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141142
Operation counter, channel 8 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141162
Operation counter, channel 9 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141182
Operation counter, channel 10 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141202
Operation counter, channel 11 input I1
Number of changes of state of input 1 from 1 to 0.
UInt32-1RW
141222
Operation counter, channel 1 input I2
UInt32-1RW
141242
Operation counter, channel 2 input I2
UInt32-1RW
141262
Operation counter, channel 3 input I2
UInt32-1RW
141282
Operation counter, channel 4 input I2
UInt32-1RW
141302
Operation counter, channel 5 input I2
UInt32-1RW
141322
Operation counter, channel 6 input I2
UInt32-1RW
141342
Operation counter, channel 7 input I2
UInt32-1RW
141362
Operation counter, channel 8 input I2
UInt32-1RW
141382
Operation counter, channel 9 input I2
UInt32-1RW
141402
Operation counter, channel 10 input I2
UInt32-1RW
141422
Operation counter, channel 11 input I2
UInt32-1RW
141442
Running hours counter, channel 1 input I1
Counting starts when the input is activated.
UInt32h1RW
141462
Running hours counter, channel 2 input I1
Counting starts when the input is activated.
UInt32h1RW
141482
Running hours counter, channel 3 input I1
Counting starts when the input is activated.
UInt32h1RW
141502
Running hours counter, channel 4 input I1
Counting starts when the input is activated.
UInt32h1RW
141522
Running hours counter, channel 5 input I1
Counting starts when the input is activated.
UInt32h1RW
141542
Running hours counter, channel 6 input I1
Counting starts when the input is activated.
UInt32h1RW
141562
Running hours counter, channel 7 input I1
Counting starts when the input is activated.
UInt32h1RW
141582
Running hours counter, channel 8 input I1
Counting starts when the input is activated.
UInt32h1RW
141602
Running hours counter, channel 9 input I1
Counting starts when the input is activated.
UInt32h1RW
141622
Running hours counter, channel 10 input I1
Counting starts when the input is activated.
UInt32h1RW
141642
Running hours counter, channel 11 input I1
Counting starts when the input is activated.
UInt32h1RW
142001
Channel 1 status
Electrical status of inputs 1 and 2 of the device on channel 1: bit 0 = electrical level of input 1, bit 1 = electrical level of input 2 (0 = no current, 1 = input current); bits 2 to 15 are reserved. With an iOF+SD24 auxiliary, bit 0 = 1 means the circuit breaker is closed and bit 1 = 1 that the device is not tripped.
Hex-1R
142011
Channel 1 command word, Acti 9 product (outputs Q)
Close and open order for a product in the Acti 9 range: bit 0 = close order, bit 1 = open order. The Smartlink clears the bit once the order is executed; if both bits are 1 the order has no effect.
Hex-1RW
142021
Channel 1 command word, non-Acti 9 product (outputs Q)
Deactivation and activation order for a product outside the Acti 9 range: bit 0 = deactivation, bit 1 = activation. The Smartlink clears the bit once the order is executed.
Hex-1RW
142031
Channel 1 output Q state
State of output Q of the device on channel 1: bit 0 = 0 output inactive, bit 1 output active.
Hex-1R
142042
Channel 1 power or flow indicator, input I1
Float32-1R
142062
Channel 1 power or flow indicator, input I2
Float32-1R
142082
Channel 1 consumption meter, input I1
UInt32-1R
142102
Channel 1 consumption meter, input I2
UInt32-1R
142122
Channel 1 operation counter, input I1
UInt32-1RW
142142
Channel 1 operation counter, input I2
UInt32-1RW
142162
Channel 1 running hours counter, input I1
UInt32h1RW
142301
Channel 1 pulse weight, input I1
Pulse weight of the meter on input 1; factory setting 10.
UInt16-1RW
142311
Channel 1 pulse weight, input I2
Factory setting 10. The pulse weight for the other channels is at 14230 + 40 x (N - 1) and 14231 + 40 x (N - 1).
UInt16-1RW

Notes

Addresses are the decimal Modbus addresses of Schneider's Acti 9 Smartlink Modbus communication system user manual DOCA0004EN; the manual notes that the protocol addresses start at 0 and that the data-model address is the address + 1. The Smartlink collects up to 11 channels of Acti 9 devices (iOF/SD24, iACT24, iATL24, RCA iC60, Reflex iC60, iEM2000T or iEM3000 meters, contactors, impulse relays) and publishes their status, commands, power or flow indicators, consumption meters and counters in one compact map: the summary block from 14000 gives one value per channel, and each channel also has a 40-register detail block starting at 14200 + 40 x (channel - 1). The detail registers of channel 1 are listed here; channels 2 to 11 use the same layout with a +40 offset per channel. DATE registers (date and time of the operation counters, 14218-14229) are 4-register TI081 date-time values, which this format cannot express, so they are not listed. The Acti 9 Smartlink is an RS-485 device; the factory serial settings are 19200 bps, 8E1 and slave address 1 (set by the two rotary switches).