Finder · Energy meter

7M.24 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
33
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
24982
Frequency
Float32Hz1R
25002
Voltage L1
Float32V1R
25162
Current L1
Float32A1R
25302
Active power L1
Float32W1R
25362
Active power, total
Float32W1R
25382
Reactive power L1
Float32var1R
25442
Reactive power, total
Float32var1R
25462
Apparent power L1
Float32VA1R
25522
Apparent power, total
Float32VA1R
25542
Power factor L1
Float32-1R
25602
Power factor, total
Float32-1R
25622
Power factor L1 (capacitive/inductive)
Float32-1R
25682
Power factor, total (capacitive/inductive)
Float32-1R
25702
Phase angle between U1 and I1
Float32°1R
25762
Power angle, total
Float32°1R
25882
Current THD L1
Float32%1R
25942
Voltage THD L1
Float32%1R
26382
Energy counter n1 (second copy)
Protocol document: energy counter n1 in Wh.
Float32kWh0.001R
26402
Energy counter n2 (second copy)
Protocol document: energy counter n2 in varh.
Float32kvarh0.001R
26582
Internal temperature
Float32°C1R
27502
Active tariff
Float32-1R
27522
Energy counter n1
Protocol document: energy counter n1 in Wh. Counters n1/n3 are active energy and n2/n4 reactive energy; conventionally n1/n2 import and n3/n4 export.
Float32kWh0.001R
27542
Energy counter n2
Protocol document: energy counter n2 in varh.
Float32kvarh0.001R
27562
Energy counter n3
Protocol document: energy counter n3 in Wh.
Float32kWh0.001R
27582
Energy counter n4
Protocol document: energy counter n4 in varh.
Float32kvarh0.001R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (address 33, 19200 bps, 8N2). Sources: Finder 'Modbus communication protocol 7M24 - 7M38' v2 (30.06.2021) for the register table and Finder 'Benutzerhandbuch 7M' for the factory defaults. The 'IEEE 754' measurement bank is used, so all values are 32-bit floats read with function code 04; the protocol document's 3xxxxx register numbers map to wire address = number - 30000 and the 4xxxxx settings to number - 40000. Energy counters are transmitted in Wh/varh and scaled to kWh/kvarh here. This is the single-phase 7M.24; the three-phase 7M.38 has its own seed.