SUTO iTEC · Flow meter
S461 clamp-on ultrasonic flow meter / thermal energy meter Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- Low word first
- Baud rate
- 19200
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 2000 | 1 | Group ID Group ID of the device type; the document's Group IDs table gives 2 for the S461 water flow sensor (15 is the 'Others' group, not this device). | UInt16 | - | 1 | R |
| 2001 | 1 | Device ID System information block. | UInt16 | - | 1 | R |
| 2002 | 2 | Serial number System information block, 4-byte unsigned integer. | UInt32 | - | 1 | R |
| 2004 | 1 | Firmware / hardware version High byte = firmware version, low byte = hardware version. | UInt16 | - | 1 | R |
| 2009 | 1 | Valid days from calibration date Days remaining in the calibration validity. The calibration date itself is an 8-byte DOUBLE at 2005-2008; it is not seeded because the table defines no value encoding for it (its Contents/Example cell is blank), not because the schema lacks a 64-bit type. | UInt16 | days | 1 | R |
| 2010 | 1 | Number of measuring channels Number of channels the device serves; the document supports up to 50. | UInt16 | - | 1 | R |
| 2011 | 8 | Device name 16-byte ASCII device name (8 registers). | Ascii | - | 1 | R |
| 2300 | 1 | Status Bit 15 = 1 means the sensor settings were changed by the user since the last read; bits 0-14 report one measuring channel each, 0 = channel OK and 1 = channel NG. | UInt16 | - | 1 | R |
| 2301 | 2 | Flow Floating-point channel value; the unit is defined by the channel's unit+resolution register at 2200 and defaults to m3/h. | Float32 | m3/h | 1 | R |
| 2303 | 2 | Velocity Floating-point channel value; default unit m/s. | Float32 | m/s | 1 | R |
| 2305 | 2 | Consumption (forward) Forward totalizer; default unit m3. | Float32 | m3 | 1 | R |
| 2307 | 2 | Consumption (reverse) Reverse totalizer; default unit m3. | Float32 | m3 | 1 | R |
| 2311 | 2 | Energy flow (instantaneous energy) Thermal energy flow; default unit GJ/h. Energy meter variants only. | Float32 | GJ/h | 1 | R |
| 2313 | 2 | Heat accumulated Heat totalizer; default unit GJ. Energy meter variants only. | Float32 | GJ | 1 | R |
| 2315 | 2 | Cold accumulated Cooling-energy totalizer; default unit GJ. Energy meter variants only. | Float32 | GJ | 1 | R |
| 2317 | 2 | Delta T Temperature difference between the two sensors; default unit degC. | Float32 | °C | 1 | R |
| 2319 | 2 | Temperature inlet Inlet temperature; default unit degC. Energy meter variants only. | Float32 | °C | 1 | R |
| 2321 | 2 | Temperature outlet Outlet temperature; default unit degC. | Float32 | °C | 1 | R |
| 2323 | 2 | Signal strength upstream Signal quality of the upstream path; the document's resolution table gives 0.1 steps over 0.1-99.9 and prints no unit for this row. | Float32 | - | 1 | R |
| 2325 | 2 | Signal strength downstream Signal quality of the downstream path; same 0.1 steps over 0.1-99.9 and no printed unit. | Float32 | - | 1 | R |
| 2327 | 2 | Signal quality Signal quality as a 4-byte signed integer (the resolution table gives 1-99). | Int32 | - | 1 | R |
| 2329 | 1 | Measurement status One of E, G or N (ASCII). E = error, G = gain adjustment, N = normal. | Ascii | - | 1 | R |
| 2331 | 1 | Status Status register, see the status bit explanation for register 2300. | UInt16 | - | 1 | R |
| 2332 | 2 | Sound velocity ratio Measured sound velocity divided by the reference value; the resolution table gives 0.1 steps over 0.1-99. | Float32 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: SUTO iTEC 'S461 Modbus Register Table (User Version)', EN 2023-1, sections 1 'Modbus Interface' and 2 'Modbus Register Table' - vendor-hosted at suto-itec.com (SHA-256 8453ed2f034d496e33d763c3be062af1bbb6e7e3172e021bfe0213e9ee94bd56), cross-checked against the S461 installation manual 2023-2 section 10.3. Factory frame: Modbus RTU, device address 1, 19200 baud, 8 data bits, no parity, 1 stop bit; 8N1 framing is printed in section 1. Byte order: the document's own table gives 1-0-3-2 for FLOAT, UINT32 and INT32, i.e. the low word sits at the lower address and the high byte comes first inside each word, which the seed stores as BigEndian + LowFirst. Addressing: the document prints an 'Addr.' column with no statement of its base; the seed declares zero_based because the printed numbers behave as wire addresses - the 4-byte values step by 2 (2002 -> 2004), the 8-byte calibration date steps by 4 (2005 -> 2009) and the 16-byte device name occupies 2011-2018 before the next block starts at 2200. Units: the resolution table prints '_' (none) for signal strength (2323/2325), signal quality and sound velocity ratio, so those rows carry no unit; flow, velocity, consumption, energy and temperature use the documented default units m3/h, m/s, m3, GJ/h, GJ and degC. The unit+resolution block at 2200-2215 is NOT seeded: each of those registers packs a unit code in the first byte and a data-type/resolution code in the second, so they are configuration rather than fixed measurements - the float channel values at 2301+ are the same values in their default units. The 8-byte DOUBLE calibration date at 2005 is omitted because the table defines no value encoding for it (its Contents/Example cell is blank).