All devices

SUTO iTEC · Flow meter

S461 clamp-on ultrasonic flow meter / thermal energy meter Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
20001
Group ID
Group ID of the device type; the document's Group IDs table gives 2 for the S461 water flow sensor (15 is the 'Others' group, not this device).
UInt16-1R
20011
Device ID
System information block.
UInt16-1R
20022
Serial number
System information block, 4-byte unsigned integer.
UInt32-1R
20041
Firmware / hardware version
High byte = firmware version, low byte = hardware version.
UInt16-1R
20091
Valid days from calibration date
Days remaining in the calibration validity. The calibration date itself is an 8-byte DOUBLE at 2005-2008; it is not seeded because the table defines no value encoding for it (its Contents/Example cell is blank), not because the schema lacks a 64-bit type.
UInt16days1R
20101
Number of measuring channels
Number of channels the device serves; the document supports up to 50.
UInt16-1R
20118
Device name
16-byte ASCII device name (8 registers).
Ascii-1R
23001
Status
Bit 15 = 1 means the sensor settings were changed by the user since the last read; bits 0-14 report one measuring channel each, 0 = channel OK and 1 = channel NG.
UInt16-1R
23012
Flow
Floating-point channel value; the unit is defined by the channel's unit+resolution register at 2200 and defaults to m3/h.
Float32m3/h1R
23032
Velocity
Floating-point channel value; default unit m/s.
Float32m/s1R
23052
Consumption (forward)
Forward totalizer; default unit m3.
Float32m31R
23072
Consumption (reverse)
Reverse totalizer; default unit m3.
Float32m31R
23112
Energy flow (instantaneous energy)
Thermal energy flow; default unit GJ/h. Energy meter variants only.
Float32GJ/h1R
23132
Heat accumulated
Heat totalizer; default unit GJ. Energy meter variants only.
Float32GJ1R
23152
Cold accumulated
Cooling-energy totalizer; default unit GJ. Energy meter variants only.
Float32GJ1R
23172
Delta T
Temperature difference between the two sensors; default unit degC.
Float32°C1R
23192
Temperature inlet
Inlet temperature; default unit degC. Energy meter variants only.
Float32°C1R
23212
Temperature outlet
Outlet temperature; default unit degC.
Float32°C1R
23232
Signal strength upstream
Signal quality of the upstream path; the document's resolution table gives 0.1 steps over 0.1-99.9 and prints no unit for this row.
Float32-1R
23252
Signal strength downstream
Signal quality of the downstream path; same 0.1 steps over 0.1-99.9 and no printed unit.
Float32-1R
23272
Signal quality
Signal quality as a 4-byte signed integer (the resolution table gives 1-99).
Int32-1R
23291
Measurement status
One of E, G or N (ASCII). E = error, G = gain adjustment, N = normal.
Ascii-1R
23311
Status
Status register, see the status bit explanation for register 2300.
UInt16-1R
23322
Sound velocity ratio
Measured sound velocity divided by the reference value; the resolution table gives 0.1 steps over 0.1-99.
Float32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: SUTO iTEC 'S461 Modbus Register Table (User Version)', EN 2023-1, sections 1 'Modbus Interface' and 2 'Modbus Register Table' - vendor-hosted at suto-itec.com (SHA-256 8453ed2f034d496e33d763c3be062af1bbb6e7e3172e021bfe0213e9ee94bd56), cross-checked against the S461 installation manual 2023-2 section 10.3. Factory frame: Modbus RTU, device address 1, 19200 baud, 8 data bits, no parity, 1 stop bit; 8N1 framing is printed in section 1. Byte order: the document's own table gives 1-0-3-2 for FLOAT, UINT32 and INT32, i.e. the low word sits at the lower address and the high byte comes first inside each word, which the seed stores as BigEndian + LowFirst. Addressing: the document prints an 'Addr.' column with no statement of its base; the seed declares zero_based because the printed numbers behave as wire addresses - the 4-byte values step by 2 (2002 -> 2004), the 8-byte calibration date steps by 4 (2005 -> 2009) and the 16-byte device name occupies 2011-2018 before the next block starts at 2200. Units: the resolution table prints '_' (none) for signal strength (2323/2325), signal quality and sound velocity ratio, so those rows carry no unit; flow, velocity, consumption, energy and temperature use the documented default units m3/h, m/s, m3, GJ/h, GJ and degC. The unit+resolution block at 2200-2215 is NOT seeded: each of those registers packs a unit code in the first byte and a data-type/resolution code in the second, so they are configuration rather than fixed measurements - the float channel values at 2301+ are the same values in their default units. The 8-byte DOUBLE calibration date at 2005 is omitted because the table defines no value encoding for it (its Contents/Example cell is blank).