Signet 9900 SmartPro transmitter with 3-9900.270 Modbus module (M2 / M3 / M4) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
34
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
12
Status
Registers 40001-40002. All bits clear = sensor reading is good, no errors. Bits: 0 wrong sensor connected, 1 check sensor, 2 missing sensor, 3 sensor error, 4 secondary reading is totalizer, 5 secondary reading not available, 6 reset-to-default jumper active, 7 9900 communication active, 8 manufacturing area protected, 9 device using default communication parameters, 10 not used, 11-31 not used.
UInt32-1R
32
Primary reading
IEEE-754 float at 40003-40004; the unit is given by the primary unit code at 40008. Not updated in Factory or Batch instrument types.
Float32-1R
52
Secondary reading
IEEE-754 float at 40005-40006, unit given by the secondary unit code at 40009. For flow instruments the secondary reading is the totalizer and exists only on Generation 4 or greater transmitters; pH, conductivity, salinity and dissolved-oxygen instruments return temperature here.
Float32-1R
71
Measurement type
Instrument type code: 0x0000 factory, 0x4201 flow, 0x5102 pH, 0x5103 ORP, 0x5704 conductivity/resistivity, 0x4105 pressure, 0x5C06 level/volume, 0x4007 temperature, 0x0008 4-20 mA input, 0x5A09 salinity, 0x510B dissolved oxygen. Batch instruments do not answer over Modbus.
UInt16-1R
81
Primary units of measure code
Unit code of the primary reading: flow 22 GPS, 16 GPM, 136 GPH, 235 GPD, 24 L/s, 17 L/min, 138 L/h, 131 m3/min, 19 m3/h, 29 m3/d, 15 ft3/min, 130 ft3/h, 27 ft3/d, 23 MGD, 25 MLD, 133 bpm, 134 bph, 135 bpd, 20 ft/s, 21 m/s, 252 all other flow units, 240 flow totalization; pH 59; temperature 32 degC, 33 degF; ORP 36 mV; conductivity 67 uS, 66 mS, 139 ppm, 169 ppb, 163 kOhm, 170 MOhm; pressure 6 psi, 7 bar, 12 kPa.
UInt16-1R
91
Secondary units of measure code
Unit code of the secondary reading, from the same code table as the primary unit code register.
UInt16-1R
90011
Modbus address
Register 49001, range 1-247, factory default 34. The register map's address base is 40001/49001, so the stored address is the printed reference minus 40000 (declared one_based).
UInt16-1RW
90021
Network termination
Register 49002, 1 = termination on, 0 = off, factory default 0.
UInt16-1RW
90031
Modbus mode
Register 49003, 0 = Modbus RTU, 1 = Modbus ASCII, factory default 0.
UInt16-1RW
90041
Baud rate
Register 49004, 0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200, 5 = 38400, 6 = 57600, 7 = 115200, factory default 4 (19200).
UInt16-1RW
90051
Parity
Register 49005, 0 = no parity, 1 = odd, 2 = even, factory default 2 (even).
UInt16-1RW
90061
Floating point endianness
Register 49006, factory default 1. The register table prints 'Little Endian = 0, Big Endian = 1 (default 1)' while the programming flow chart below it prints 'Set Endian: 0 = Big Endian, 1 = Little Endian' and the start-up table prints 'Endian: Big'. The seed follows the register table plus the start-up table (Big Endian, i.e. HighFirst); a site that reads nonsense floats should flip this register or the seed's word order.
UInt16-1RW
90071
Save communication settings
Register 49007. Write 0 to save the registers, or write the Modbus address to save and reboot the module. The new communication settings take effect after a power cycle.
UInt16-1RW
91041
9900 HSB transactions
Register 49104, communication diagnostic counter.
UInt16-1R
91051
Second counter
Register 49105, communication diagnostic counter.
UInt16s1R
91061
Bus message counter
Register 49106, communication diagnostic counter.
UInt16-1R
91071
Bus message error counter
Register 49107, communication diagnostic counter.
UInt16-1R
91081
Slave exception counter
Register 49108, communication diagnostic counter.
UInt16-1R
91091
Slave message counter
Register 49109, communication diagnostic counter.
UInt16-1R
91101
Slave no response counter
Register 49110, communication diagnostic counter.
UInt16-1R
91111
Slave NAK counter
Register 49111, communication diagnostic counter.
UInt16-1R
91121
Slave busy counter
Register 49112, communication diagnostic counter.
UInt16-1R
91131
Bus character overrun counter
Register 49113, communication diagnostic counter.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: GF Signet 'Signet 9900 Modbus Module - Installation and Programming', 3-9900.270.090 Rev 3 02/19, chapter 'Modbus Register Map' plus the programming map and unit-code table (the copy read is an Instrumart distributor copy, SHA-256 0fe728881998dc58ebb1b3a44ea97dc05063f4ea904623b625b60b013168d3de), corroborated by the vendor-hosted instruction sheet 3-9900.270.091 Rev 4 07/20 (SHA-256 1f6d098c8482929625f263e255cc47d66ed53866a1590fc9b284c7cbea5d199c). Factory frame: Modbus RTU, address 34, 19200 baud, even parity, 8 data bits, 1 stop bit, Big Endian; the RTU data/stop bits are stated in the specification list ('RTU Mode 8 Data bits', 'RTU Mode 1 Stop bit', ASCII mode uses 7 bits and 2 stop bits). The seed declares one_based because the table prints Modicon references (40001, 49001, 49104) and stores them as reference minus 40000, which is how the document's own byte-order example is read (float 0x570A4318 at 40003/40004 = wire 2/3). The device-identification block from register 49501 is NOT seeded: in that table only some rows print a register number while the four strings of each group sit on column-offset baselines, so the addresses cannot be paired row by row without guessing. Per the guide's footnotes, Factory and Batch instrument types do not update the primary or secondary readings, Batch instruments have no Modbus operation at all, and secondary flow readings exist only on Generation 4 or greater transmitters.