All devices

Endress+Hauser · Flow meter

Proline Promag W 400 (Modbus RS485) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
247
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
38742
Volume flow
Signed floating-point volume flow measured value. The unit is whatever is selected in the volume-flow unit register (2103).
Float32-1R
38762
Mass flow
Signed floating-point mass flow measured value (requires the density input used by the device). Unit from the mass-flow unit register (2101).
Float32-1R
20132
Conductivity
Signed floating-point conductivity measured value. Unit from the conductivity unit register (2121).
Float32-1R
26102
Totalizer 1 value
Signed floating-point totalizer 1 value. Unit from the volume unit register (2104).
Float32-1R
26122
Totalizer 1 overflow
Signed integer totalizer 1 overflow counter: the current totalizer 1 reading is the totalizer 1 value plus 10 000 000 x this overflow. Type caveat: the parameter's own description types it 'Integer with sign', while the register table's data type column says Float (4 bytes) - it is read here as a signed 32-bit integer, as the parameter description states; check it against the local display on an installation that has passed 7 digits before relying on it.
Int32-1R
28102
Totalizer 2 value
Signed floating-point totalizer 2 value.
Float32-1R
28122
Totalizer 2 overflow
Signed integer totalizer 2 overflow counter: the current totalizer 2 reading is the totalizer 2 value plus 10 000 000 x this overflow. Same type caveat as totalizer 1 overflow: parameter description 'Integer with sign' against the register table's Float (4 bytes).
Int32-1R
30102
Totalizer 3 value
Signed floating-point totalizer 3 value.
Float32-1R
30122
Totalizer 3 overflow
Signed integer totalizer 3 overflow counter: the current totalizer 3 reading is the totalizer 3 value plus 10 000 000 x this overflow. Same type caveat as totalizer 1 overflow: parameter description 'Integer with sign' against the register table's Float (4 bytes).
Int32-1R
21011
Mass flow unit
Unit code for the mass flow. The vendor register table lists the complete selection list; the factory setting is country-dependent.
UInt16-1RW
21021
Mass unit
Unit code for the mass. Factory setting is country-dependent.
UInt16-1RW
21031
Volume flow unit
Unit code for the volume flow, e.g. 18 = l/h, 45 = gal/min (US). The vendor table lists the complete selection list; the factory setting is country-dependent.
UInt16-1RW
21041
Volume unit
Unit code for the volume/totalizer, e.g. 2 = m3, 4 = l. The register table lists the complete selection list.
UInt16-1RW
21071
Density unit
Unit code for the density, e.g. kg/l or lb/ft3. Factory setting is country-dependent.
UInt16-1RW
21091
Temperature unit
Unit code for temperature: 0 = degC, 1 = K, 2 = degF, 3 = degR. Factory setting is country-dependent (degC or degF).
UInt16-1RW
21211
Conductivity unit
Unit code for conductivity (1 = MS/m, 2 = kS/m, 3 = S/m, 4 = S/cm, ... 10 = nS/cm).
UInt16-1RW
21501
Date/time format
Date/time display format.
UInt16-1RW
49101
Bus address
Modbus RS485 bus address of the device (1-247). Factory setting 247.
UInt16-1RW
49121
Baudrate
Modbus RS485 baud-rate code (1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200). Factory setting 19200.
UInt16-1RW
49131
Data transfer mode
Data transfer mode: ASCII or RTU. Factory setting RTU.
UInt16-1RW
49141
Parity
Parity bits: 0 = even, 1 = odd, 2 = none/1 stop bit, 3 = none/2 stop bits. Factory setting 0 (even, 1 stop bit).
UInt16-1RW
49151
Byte order
Byte transmission sequence: 0-1-2-3, 3-2-1-0, 1-0-3-2 or 2-3-0-1. Factory setting 1-0-3-2.
UInt16-1RW
49201
Failure mode
Measured-value output on a diagnostic message: NaN value or last valid value. Factory setting NaN value.
UInt16-1RW
25471
Device ID
Modbus device ID of the measuring device.
UInt16-1R
44811
Device revision
Modbus device revision.
UInt16-1R
27321
Actual diagnostics
Diagnostic event code of the currently pending diagnostic message.
UInt16-1R
27341
Previous diagnostics
Diagnostic event code of the last diagnostic message that was pending.
UInt16-1R
27361
Diagnostics 1
Diagnostic list entry 1 (current diagnostic event code).
UInt16-1R
27381
Diagnostics 2
Diagnostic list entry 2.
UInt16-1R
27401
Diagnostics 3
Diagnostic list entry 3.
UInt16-1R
27421
Diagnostics 4
Diagnostic list entry 4.
UInt16-1R
27441
Diagnostics 5
Diagnostic list entry 5.
UInt16-1R
202616
Device tag
Device tag, max. 32 characters, packed into 16 registers.
Ascii-1R
70036
Serial number
Serial number, max. 11 characters, packed into 6 registers.
Ascii-1R
72774
Firmware version
Firmware version as a character string xx.yy.zz, in 4 registers.
Ascii-1R
72638
Device name
Device name, max. 32 characters, in 8 registers.
Ascii-1R
205810
Order code
Order code string, in 10 registers.
Ascii-1R
48181
Configuration counter
Increments on every change of a device parameter; useful to detect configuration changes.
UInt16-1R
22731
Filter options
Filter option selection for the flow measurement.
UInt16-1RW
22741
Flow damping
Flow damping (response time) of the flow measurement.
UInt16-1RW
55031
Flow override
Flow override mode: forces the flow output to a configured value for a defined time.
UInt16-1RW
51061
Empty pipe detection
Empty pipe detection on/off.
UInt16-1RW
22801
Electrode cleaning circuit
Electrode cleaning circuit (ECC) on/off.
UInt16-1RW
23282
ECC cleaning cycle
Electrode cleaning cycle duration in hours; the register table gives the entry range as 0.5 to 168 h.
Float32h1RW
23302
ECC duration
Duration of the electrode cleaning pulse in seconds.
Float32s1RW
23322
ECC recovery time
Recovery time after electrode cleaning in seconds.
Float32s1RW
23341
ECC polarity
Polarity of the electrode cleaning circuit.
UInt16-1R
24971
Density source
Source of the density used for mass flow: fixed value or external density input.
UInt16-1RW
21172
External density
External density value supplied to the device.
Float32-1R
28302
Fixed density
Fixed density value used when the density source is the fixed value.
Float32-1RW
55011
Installation direction
Installation direction of the sensor: flow direction or reverse flow direction.
UInt16-1RW
22602
Integration time
Integration time of the measuring signal in milliseconds; the register table gives the range as 1 to 65 ms.
Float32ms1R
28522
Measuring period
Measuring period of the device in milliseconds; the register table gives the range as 2 to 1000 ms.
Float32ms1R
55192
Volume flow factor
Factor for the volume-flow process-variable adjustment.
Float32-1RW
55212
Volume flow offset
Offset for the volume-flow process-variable adjustment.
Float32-1RW
55232
Mass flow factor
Factor for the mass-flow process-variable adjustment.
Float32-1RW
55252
Mass flow offset
Offset for the mass-flow process-variable adjustment.
Float32-1RW
55272
Conductivity factor
Factor for the conductivity process-variable adjustment.
Float32-1RW
55292
Conductivity offset
Offset for the conductivity process-variable adjustment.
Float32-1RW
68171
Device reset
Device reset command (restart the device or restore settings, depending on the written value).
UInt16-1RW
68142
Simulation process variable value
Value used for the process variable when simulation is active.
Float32-1RW
68121
Device alarm simulation
Switches the device alarm on/off for simulation.
UInt16-1RW
42591
Diagnostic event simulation
Diagnostic event selected for simulation.
UInt16-1RW
42611
Diagnostic event category
Category used for the diagnostic event simulation.
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Endress+Hauser 'Proline Promag W 400 — Modbus RS485 — Operating Instructions' BA01231D/06/EN/04.19 (2019), section 9.3 'Modbus RS485 information' and section 10.4.3 'Configuring the communication interface', plus the matching 'Description of Device Parameters — Proline Promag 400 Modbus RS485' GP01045D/06/EN/02.21 (2022-02-01), chapter 6.3 'Register information' — every row above is a row of that table (parameter name and register number). The pair covers the Modbus RS485 variant of the Promag W 400, the water/wastewater version of the Promag 400 family. Factory frame from the OI parameter overview: bus address 247, baud rate 19200, RTU, parity even with 1 stop bit, byte order 1-0-3-2. Addressing: section 6.1.2 'Address model' puts the register numbers on the Modbus Application Protocol scale and adds a '3'/'4' prefix only for Modicon notation, so the printed numbers are stored unchanged with addressing = zero_based; its illustrative example still calls mass flow 2007/32007 (a leftover from an earlier revision) while the register table gives mass flow as 3876 to 3877, and the table is followed. Byte order 1-0-3-2 for FLOAT is CDAB (Byte 1, Byte 0, Byte 3, Byte 2): the low word sits at the lower address, the bytes inside each 16-bit word staying big-endian (the same option's INTEGER table sends Byte 1/Byte 0, MSB first) → byte_order BigEndian, word_order LowFirst. The OI says the device does not distinguish function codes 03 and 04, so the whole map is carried in the holding-register area. Deliberately omitted: the diagnostic-list timestamp strings (no register count printed), the web-server IP strings and the display-only rows. Conductivity and mass flow need the matching software option/hardware. The totalizer overflow rows are typed 'Integer with sign' by the parameter description but 'Float (4 byte)' by the register table; they are read as Int32 and the conflict is stated in each row.