  "spec_version": 1,
  "slug": "suto-s461-ultrasonic-flow-meter",
  "manufacturer": "SUTO iTEC",
  "model": "S461 clamp-on ultrasonic flow meter / thermal energy meter",
  "category": "Flow meter",
  "supplier_url": "https://www.suto-itec.com/en/products/s461-ultrasonic-flow-meter-for-water-and-other-liquids-clamp-on/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "LowFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 2000,
      "count": 1,
      "name": "Group ID",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Group ID of the device type; the document's Group IDs table gives 2 for the S461 water flow sensor (15 is the 'Others' group, not this device)."
    },
    {
      "address": 2001,
      "count": 1,
      "name": "Device ID",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "System information block."
    },
    {
      "address": 2002,
      "count": 2,
      "name": "Serial number",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "System information block, 4-byte unsigned integer."
    },
    {
      "address": 2004,
      "count": 1,
      "name": "Firmware / hardware version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "High byte = firmware version, low byte = hardware version."
    },
    {
      "address": 2009,
      "count": 1,
      "name": "Valid days from calibration date",
      "data_type": "UInt16",
      "units": "days",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Days remaining in the calibration validity. The calibration date itself is an 8-byte DOUBLE at 2005-2008; it is not seeded because the table defines no value encoding for it (its Contents/Example cell is blank), not because the schema lacks a 64-bit type."
    },
    {
      "address": 2010,
      "count": 1,
      "name": "Number of measuring channels",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Number of channels the device serves; the document supports up to 50."
    },
    {
      "address": 2011,
      "count": 8,
      "name": "Device name",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "16-byte ASCII device name (8 registers)."
    },
    {
      "address": 2300,
      "count": 1,
      "name": "Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit 15 = 1 means the sensor settings were changed by the user since the last read; bits 0-14 report one measuring channel each, 0 = channel OK and 1 = channel NG."
    },
    {
      "address": 2301,
      "count": 2,
      "name": "Flow",
      "data_type": "Float32",
      "units": "m3/h",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Floating-point channel value; the unit is defined by the channel's unit+resolution register at 2200 and defaults to m3/h."
    },
    {
      "address": 2303,
      "count": 2,
      "name": "Velocity",
      "data_type": "Float32",
      "units": "m/s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Floating-point channel value; default unit m/s."
    },
    {
      "address": 2305,
      "count": 2,
      "name": "Consumption (forward)",
      "data_type": "Float32",
      "units": "m3",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Forward totalizer; default unit m3."
    },
    {
      "address": 2307,
      "count": 2,
      "name": "Consumption (reverse)",
      "data_type": "Float32",
      "units": "m3",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Reverse totalizer; default unit m3."
    },
    {
      "address": 2311,
      "count": 2,
      "name": "Energy flow (instantaneous energy)",
      "data_type": "Float32",
      "units": "GJ/h",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Thermal energy flow; default unit GJ/h. Energy meter variants only."
    },
    {
      "address": 2313,
      "count": 2,
      "name": "Heat accumulated",
      "data_type": "Float32",
      "units": "GJ",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Heat totalizer; default unit GJ. Energy meter variants only."
    },
    {
      "address": 2315,
      "count": 2,
      "name": "Cold accumulated",
      "data_type": "Float32",
      "units": "GJ",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Cooling-energy totalizer; default unit GJ. Energy meter variants only."
    },
    {
      "address": 2317,
      "count": 2,
      "name": "Delta T",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Temperature difference between the two sensors; default unit degC."
    },
    {
      "address": 2319,
      "count": 2,
      "name": "Temperature inlet",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Inlet temperature; default unit degC. Energy meter variants only."
    },
    {
      "address": 2321,
      "count": 2,
      "name": "Temperature outlet",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Outlet temperature; default unit degC."
    },
    {
      "address": 2323,
      "count": 2,
      "name": "Signal strength upstream",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signal quality of the upstream path; the document's resolution table gives 0.1 steps over 0.1-99.9 and prints no unit for this row."
    },
    {
      "address": 2325,
      "count": 2,
      "name": "Signal strength downstream",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signal quality of the downstream path; same 0.1 steps over 0.1-99.9 and no printed unit."
    },
    {
      "address": 2327,
      "count": 2,
      "name": "Signal quality",
      "data_type": "Int32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signal quality as a 4-byte signed integer (the resolution table gives 1-99)."
    },
    {
      "address": 2329,
      "count": 1,
      "name": "Measurement status",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "One of E, G or N (ASCII). E = error, G = gain adjustment, N = normal."
    },
    {
      "address": 2331,
      "count": 1,
      "name": "Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Status register, see the status bit explanation for register 2300."
    },
    {
      "address": 2332,
      "count": 2,
      "name": "Sound velocity ratio",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Measured sound velocity divided by the reference value; the resolution table gives 0.1 steps over 0.1-99."
    }
  ],
  "combined_registers": [],
  "notes": "Source: SUTO iTEC 'S461 Modbus Register Table (User Version)', EN 2023-1, sections 1 'Modbus Interface' and 2 'Modbus Register Table' - vendor-hosted at suto-itec.com (SHA-256 8453ed2f034d496e33d763c3be062af1bbb6e7e3172e021bfe0213e9ee94bd56), cross-checked against the S461 installation manual 2023-2 section 10.3. Factory frame: Modbus RTU, device address 1, 19200 baud, 8 data bits, no parity, 1 stop bit; 8N1 framing is printed in section 1. Byte order: the document's own table gives 1-0-3-2 for FLOAT, UINT32 and INT32, i.e. the low word sits at the lower address and the high byte comes first inside each word, which the seed stores as BigEndian + LowFirst. Addressing: the document prints an 'Addr.' column with no statement of its base; the seed declares zero_based because the printed numbers behave as wire addresses - the 4-byte values step by 2 (2002 -> 2004), the 8-byte calibration date steps by 4 (2005 -> 2009) and the 16-byte device name occupies 2011-2018 before the next block starts at 2200. Units: the resolution table prints '_' (none) for signal strength (2323/2325), signal quality and sound velocity ratio, so those rows carry no unit; flow, velocity, consumption, energy and temperature use the documented default units m3/h, m/s, m3, GJ/h, GJ and degC. The unit+resolution block at 2200-2215 is NOT seeded: each of those registers packs a unit code in the first byte and a data-type/resolution code in the second, so they are configuration rather than fixed measurements - the float channel values at 2301+ are the same values in their default units. The 8-byte DOUBLE calibration date at 2005 is omitted because the table defines no value encoding for it (its Contents/Example cell is blank)."
}