EcoStruxure Panel Server (PAS400 / PAS600 / PAS800) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
255
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
1116
Product range
Ascii-1R
2716
Product family
Ascii-1R
4317
Vendor URL
Ascii-1R
6116
Commercial Reference - Example "PAS600L"
Ascii-1R
816
EcoStruxure Panel Server hardware version on 11 ASCII characters, valid for firmware version 001.008.007 and later. Example: 000.000.001
Ascii-1R
1016
Serial number on 12 ASCII characters; 12 alphanumeric digits maximum [SN] or [S/N]: PP YY WW [D L[nnnn]]
Ascii-1R
1216
EcoStruxure Panel Server firmware version on 11 ASCII characters, valid for firmware version 001.008.007 and later. Example: 001.008.007
Ascii-1R
12716
Product capability
Ascii-1R
14316
Additionnal product capability
Ascii-1R
1591
Health state of EcoStruxure Panel Server
UInt16-1R
16016
Manufacturer Name - "Schneider Electric"
Ascii-1R
2511
Synthesis Table server address (Default @247)
UInt16-1R
5051
Virtual address of wireless device 1
UInt16-1R
5101
Virtual address of wireless device 2
UInt16-1R
5151
Virtual address of wireless device 3
UInt16-1R
5201
Virtual address of wireless device 4
UInt16-1R
5251
Virtual address of wireless device 5
UInt16-1R
5301
Virtual address of wireless device 6
UInt16-1R
5351
Virtual address of wireless device 7
UInt16-1R
5401
Virtual address of wireless device 8
UInt16-1R
5451
Virtual address of wireless device 9
UInt16-1R
5501
Virtual address of wireless device 10
UInt16-1R
5551
Virtual address of wireless device 11
UInt16-1R
5601
Virtual address of wireless device 12
UInt16-1R
5651
Virtual address of wireless device 13
UInt16-1R
5701
Virtual address of wireless device 14
UInt16-1R
5751
Virtual address of wireless device 15
UInt16-1R
5801
Virtual address of wireless device 16
UInt16-1R
5851
Virtual address of wireless device 17
UInt16-1R
5901
Virtual address of wireless device 18
UInt16-1R
5951
Virtual address of wireless device 19
UInt16-1R
6001
Virtual address of wireless device 20
UInt16-1R
6051
Virtual address of wireless device 21
UInt16-1R
6101
Virtual address of wireless device 22
UInt16-1R
6151
Virtual address of wireless device 23
UInt16-1R
6201
Virtual address of wireless device 24
UInt16-1R
6251
Virtual address of wireless device 25
UInt16-1R
6301
Virtual address of wireless device 26
UInt16-1R
6351
Virtual address of wireless device 27
UInt16-1R
6401
Virtual address of wireless device 28
UInt16-1R
6451
Virtual address of wireless device 29
UInt16-1R
6501
Virtual address of wireless device 30
UInt16-1R
6551
Virtual address of wireless device 31
UInt16-1R
6601
Virtual address of wireless device 32
UInt16-1R
6651
Virtual address of wireless device 33
UInt16-1R
6701
Virtual address of wireless device 34
UInt16-1R
6751
Virtual address of wireless device 35
UInt16-1R
6801
Virtual address of wireless device 36
UInt16-1R
6851
Virtual address of wireless device 37
UInt16-1R
6901
Virtual address of wireless device 38
UInt16-1R
6951
Virtual address of wireless device 39
UInt16-1R
7001
Virtual address of wireless device 40
UInt16-1R
7051
Virtual address of wireless device 41
UInt16-1R
7101
Virtual address of wireless device 42
UInt16-1R
7151
Virtual address of wireless device 43
UInt16-1R
7201
Virtual address of wireless device 44
UInt16-1R
7251
Virtual address of wireless device 45
UInt16-1R
7301
Virtual address of wireless device 46
UInt16-1R
7351
Virtual address of wireless device 47
UInt16-1R
7401
Virtual address of wireless device 48
UInt16-1R
7451
Virtual address of wireless device 49
UInt16-1R
7501
Virtual address of wireless device 50
UInt16-1R
7551
Virtual address of wireless device 51
UInt16-1R
7601
Virtual address of wireless device 52
UInt16-1R
7651
Virtual address of wireless device 53
UInt16-1R
7701
Virtual address of wireless device 54
UInt16-1R
7751
Virtual address of wireless device 55
UInt16-1R
7801
Virtual address of wireless device 56
UInt16-1R
7851
Virtual address of wireless device 57
UInt16-1R
7901
Virtual address of wireless device 58
UInt16-1R
7951
Virtual address of wireless device 59
UInt16-1R
8001
Virtual address of wireless device 60
UInt16-1R
8051
Virtual address of wireless device 61
UInt16-1R
8101
Virtual address of wireless device 62
UInt16-1R
8151
Virtual address of wireless device 63
UInt16-1R
8201
Virtual address of wireless device 64
UInt16-1R
8251
Virtual address of wireless device 65
UInt16-1R
8301
Virtual address of wireless device 66
UInt16-1R
8351
Virtual address of wireless device 67
UInt16-1R
8401
Virtual address of wireless device 68
UInt16-1R
8451
Virtual address of wireless device 69
UInt16-1R
8501
Virtual address of wireless device 70
UInt16-1R
8551
Virtual address of wireless device 71
UInt16-1R
8601
Virtual address of wireless device 72
UInt16-1R
8651
Virtual address of wireless device 73
UInt16-1R
8701
Virtual address of wireless device 74
UInt16-1R
8751
Virtual address of wireless device 75
UInt16-1R
8801
Virtual address of wireless device 76
UInt16-1R
8851
Virtual address of wireless device 77
UInt16-1R
8901
Virtual address of wireless device 78
UInt16-1R
8951
Virtual address of wireless device 79
UInt16-1R
9001
Virtual address of wireless device 80
UInt16-1R
9051
Virtual address of wireless device 81
UInt16-1R
9101
Virtual address of wireless device 82
UInt16-1R
9151
Virtual address of wireless device 83
UInt16-1R
9201
Virtual address of wireless device 84
UInt16-1R
9251
Virtual address of wireless device 85
UInt16-1R
9301
Virtual address of wireless device 86
UInt16-1R
9351
Virtual address of wireless device 87
UInt16-1R
9401
Virtual address of wireless device 88
UInt16-1R
9451
Virtual address of wireless device 89
UInt16-1R
9501
Virtual address of wireless device 90
UInt16-1R
9551
Virtual address of wireless device 91
UInt16-1R
9601
Virtual address of wireless device 92
UInt16-1R
9651
Virtual address of wireless device 93
UInt16-1R
9701
Virtual address of wireless device 94
UInt16-1R
9751
Virtual address of wireless device 95
UInt16-1R
9801
Virtual address of wireless device 96
UInt16-1R
9851
Virtual address of wireless device 97
UInt16-1R
9901
Virtual address of wireless device 98
UInt16-1R
9951
Virtual address of wireless device 99
UInt16-1R
10001
Virtual address of wireless device 100
UInt16-1R
10011
DI1 validity. If a device is connected on DI1, a valid value is returned (= 1). Otherwise an invalid value is returned.
UInt16-1R
10021
DI2 validity. If a device is connected on DI2, a valid value is returned (= 1). Otherwise an invalid value is returned.
UInt16-1R
10031
DI1 input mode
UInt16-1R
10041
DI2 input mode
UInt16-1R
100520
User application name of the device connected on DI1
Ascii-1R
102520
User application name of the device connected on DI2
Ascii-1R
10453
Electrical label of the device connected on DI1
Ascii-1R
10483
Electrical label of the device connected on DI2
Ascii-1R
10511
Indicates the usage of the device connected on DI1
UInt16-1R
10521
Indicates the usage of the device connected on DI2
UInt16-1R
10531
Logical status of the Digital Input DI1 (takes into account the configured polarity) ON // Active OFF // Inactive Undetermined // Invalid value
UInt16-1R
10541
Logical status of the Digital Input DI2 (takes into account the configured polarity) ON // Active OFF // Inactive Undetermined // Invalid value
UInt16-1R
10552
Non resettable DI1 operating time
UInt32-1R
10572
Non resettable DI2 operating time
UInt32-1R
10592
Resettable DI1 operating time
UInt32-1RW
10612
Resettable DI2 operating time
UInt32-1RW
10712
Non resettable DI1 operation counter
UInt32-1R
10732
Non resettable DI2 operation counter
UInt32-1R
10752
Resettable DI1 operation counter
UInt32-1RW
10772
Resettable DI2 operation counter
UInt32-1RW
10872
Pulse weight of device connected on DI1 if DI1 mode is set to Pulse
Float32-1R
10892
Pulse weight of device connected on DI2 if DI2 mode is set to Pulse
Float32-1R
11732
Measured flow value on DI1 if DI1 mode is set to Pulse. The unit of the measured flow value depends on the DI1 configuration 0 None (None/empty) None/empty (None/empty) 1
Float32-1R
11752
Measured flow value on DI2 if DI2 mode is set to Pulse. The unit of the measured flow value depends on the DI2 configuration 0 None (None/empty) None/empty (None/empty) 1
Float32-1R
12191
Commodity of device connected to DI1 1. Electricity 2. Gas 3. Fuel oil 4. Air 5. Steam 6. Water 7. Environment 8. Other 9. Custom (Free text to enter): User can enter 10 custom values
UInt16-1R
12201
Commodity of device connected to DI2 1. Electricity 2. Gas 3. Fuel oil 4. Air 5. Steam 6. Water 7. Environment 8. Other 9. Custom (Free text to enter): User can enter 10 custom values
UInt16-1R
12211
Features assigned to digital input: 0 None 1 Custom 2 Circuit breaker status 3 Trip fault (SD) 4 Trip indicator synthesis 5 Trip elec fault (SDE) 6 Trip thermal fault (SDT) 7 Earth
UInt16-1R
12221
Features assigned to digital input: 0 None 1 Custom 2 Circuit breaker status 3 Trip fault (SD) 4 Trip indicator synthesis 5 Trip elec fault (SDE) 6 Trip thermal fault (SDT) 7 Earth
UInt16-1R
12231
Digital input DI1 electrical status. Indicates the electrical status of the input, regardless of the assignment reference & polarity
UInt16-1R
12241
Digital input DI2 electrical status. Indicates the electrical status of the input, regardless of the assignment reference & polarity
UInt16-1R
12251
Polarity of the Digital Input DI1 Meaning of input: /0 for inactive/1 for active/: // Input Electrical status = 0V --> input is inactive (eg: Trip fault (SD) = ‘No Fault’ / Motor run =
UInt16-1R
12261
Polarity of the Digital Input DI2 Meaning of input: /0 for inactive/1 for active/: // Input Electrical status = 0V --> input is inactive (eg: Trip fault (SD) = ‘No Fault’ / Motor run =
UInt16-1R
122710
Text giving the context of use of the Digital Input DI1 when DI1 is defined as 'Custom'
Ascii-1R
123710
Text giving the context of use of the Digital Input DI2 when DI2 is defined as 'Custom'
Ascii-1R
124710
Text defining the inactive value of the Digital Input DI1 when DI1 is defined as 'Custom'
Ascii-1R
125710
Text defining the inactive value of the Digital Input DI2 when DI2 is defined as 'Custom'
Ascii-1R
126710
Text defining the active value of the Digital Input DI1 when DI1 is defined as 'Custom'
Ascii-1R
127710
Text defining the active value of the Digital Input DI2 when DI2 is defined as 'Custom'
Ascii-1R
12871
Feature assigned to digital input (Accumulated value + unit, and associated flow value + flow unit) 0 None (None/empty) None/empty (None/empty) 1
UInt16-1R
12881
Feature assigned to digital input (Accumulated value + unit, and associated flow value + flow unit) 0 None (None/empty) None/empty (None/empty) 1
UInt16-1R
128920
Custom Metering accumulated name for DI1. Only applicable if DI mode is "Pulse"
Ascii-1R
130920
Custom Metering accumulated name for DI2 Only applicable if DI mode is "Pulse"
Ascii-1R
132920
Metering accumulated custom unit for DI1. Unit defined at Commissioning time. Used only if unit is custom. Only applicable if DI mode is "Pulse"
Ascii-1R
134920
Metering accumulated custom unit for DI2. Unit defined at Commissioning time. Used only if unit is custom. Only applicable if DI mode is "Pulse"
Ascii-1R
136920
Custom Flow name for DI1. Only applicable if DI mode is "Pulse"
Ascii-1R
138920
Custom Flow name for DI2. Only applicable if DI mode is "Pulse"
Ascii-1R
140920
Measured Flow custom unit for DI1. Unit defined at Commissioning time. Used only if unit is custom. Only applicable if DI mode is "Pulse"
Ascii-1R
142920
Measured Flow custom unit for DI2. Unit defined at Commissioning time. Used only if unit is custom. Only applicable if DI mode is "Pulse"
Ascii-1R
14492
Measured volume value on DI1 if DI1 mode is set to Pulse and DI1 configuration equals V_gaz or V_water. The unit of the measured volume value is in (m³) for: WaterVolume(m³) and
Float32-1R
14512
Measured volume value on DI2 if DI2 mode is set to Pulse and DI2 configuration equals V_gaz or V_water. The unit of the measured volume value is in (m³) for: WaterVolume(m³) and
Float32-1R
563832
EcoStruxure Panel Server user application name
Ascii-1R
100011
Synchronize (reset) all the timers of the Exiway Devices connected to the PaS: ENUM { Sync = 1, }
UInt16-1RW
124001
Modbus ID of PaS
UInt16-1R
124011
Modbus Parity
UInt16-1R
124021
Modbus Baud Rate
UInt16-1R
124031
Number of stop bits
UInt16-1R
124041
Silent Time after Modbus SL packet end in millisecond:
UInt16-1R
124051
Delay Between Modbus SL Packets in millisecond:
UInt16-1R
124061
Connect/Disconnect the RS485 termination resistor:
UInt16-1R
124071
Transmission Line State
UInt16-1R
124081
Message timeout of modbus SL request
UInt16-1R
124091
Timeout of Modbus TCP/IP Client in milliseconds:
UInt16-1R
124102
Message timeout of modbus TCP/IP request in milliseconds:
UInt32-1R
124121
Message timeout of modbus TCP/IP client request in milliseconds:
UInt16-1R
124211
Modbus Serial Client Configuration of serial line 1 range. The minimum address value of supported addresses (Starting address):
UInt16-1R
124221
Modbus Serial Client Configuration of serial line 1 range. The maximum address value of supported addresses (Ending address):
UInt16-1R
124231
Modbus Parity (Serial Line 2)
UInt16-1R
124241
Modbus Baud Rate (Serial Line 2)
UInt16-1R
124251
Number of stop bits (Serial Line 2)
UInt16-1R
124261
Silent Time after Modbus SL packet end in millisecond (Serial Line 2):
UInt16-1R
124271
Delay Between Modbus SL Packets in millisecond (Serial Line 2):
UInt16-1R
124281
Connect/Disconnect the RS485 termination resistor (Serial Line 2):
UInt16-1R
124291
Transmission Line 2 State
UInt16-1R
124301
Modbus Serial Client Configuration of serial line 2 range. The minimum address value of supported addresses (Starting address):
UInt16-1R
124311
Modbus Serial Client Configuration of serial line 2 range. The maximum address value of supported addresses (Ending address):
UInt16-1R
124321
Message timeout of modbus SL Line 2 request
UInt16-1R
300312
Power demand sliding window in seconds for all applicable wireless devices
Float32SEC1R
300331
Reset all Peak Active Power Demand of all applicable wireless devices; any value writen in the register will reset Peak Active Power Demand to 0
UInt16-1RW
614431
EcoStruxure Panel Server product identifier
UInt16-1R
6144416
EcoStruxure Panel Server product model
Ascii-1R

Notes

Addresses are the decimal 'Register (dec)' column of Schneider's EcoStruxure Panel Server Modbus file DOCA0241EN, tab 'Panel Server', and apply to the Panel Server's own Modbus TCP server (port 502, unit ID 255) for PAS400 / PAS600 / PAS600L / PAS800 references. The device block from 501 lists the paired wireless PowerTag, TH110/TH150 and CL110 sensors: each device has a virtual Modbus address (UINT16) and a 64-bit RFID, which is not listed here because this format has no 64-bit integer type. To read a sensor, poll its virtual address as the unit ID with the PowerTag register map. The local digital inputs, the read-back of the Modbus serial and TCP configuration and the health state are listed; configuration is written with function code 16 to the same registers, as noted in the file's function code column.