Schneider Electric · Battery monitor

Conext Battery Monitor (CM/RCM battery monitor for Conext XW and SW systems) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
08
Device Name
Ascii-1RW
1010
FGA Number
Ascii-1R
2010
Unique ID Number
Ascii-1R
3010
Firmware Version
Ascii-1R
401
Modbus Address
UInt16-1RW
411
Device Number
UInt16-1RW
421
System Instance
UInt16-1RW
4310
Hardware Serial Number
Ascii-1R
641
Device State
See section 2
UInt16-1R
651
Device Present
0=Inactive (all data invalid) 1=Active (data valid)
UInt16-1R
662
Configuration Errors
UInt32-1R
682
DC Source ID
See section 8
UInt32-1R
702
Battery Voltage
UInt32V0.001R
722
Battery Current
Int32A0.001R
742
Battery Temperature
UInt32°C0.01 (offset -273)R
762
Battery State of Charge
UInt32%1R
782
Battery State of Health
UInt32%1R
802
Battery Percent Over Charge
UInt32%1R
822
Battery Midpoint 1 Voltage
UInt32V0.001R
842
Battery Midpoint 2 Voltage
UInt32V0.001R
862
Battery Midpoint 3 Voltage
UInt32V0.001R
882
Battery Capacity Remaining
UInt32Ah1R
902
Battery Capacity Removed
UInt32Ah1R
922
Battery BTS Present
See section 4
UInt32-1R
942
Battery Time To Full
UInt32Min1R
962
Battery Time To Discharge
UInt32Min1R
982
Battery Hours In Float
UInt32Hr0.1R
1002
Battery Last Equalize
UInt32Days1R
1021
Battery Average Discharge
Int16Ah1R
1031
Battery Average Discharge Percent
Int16%0.01R
1041
Battery Deepest Discharge
Int16Ah1R
1051
Battery Deepest Discharge Percent
Int16%0.01R
1062
Battery Capacity Removed
UInt32Ah1R
1082
Battery Capacity Returned
UInt32Ah1R
1101
Battery Number of Charge Cycles
UInt16-1R
1111
Battery Number of Synchronizations
UInt16-1R
1121
Battery Number of Discharges
UInt16-1R
1181
Nominal Temperature
UInt16°C0.01 (offset -273)RW
1191
Temperature unit
0=Imperial 1=Metric
UInt16-1RW
1201
Temperature Coefficient
UInt16Ah/°C0.01RW
1211
Nominal Discharge Rate
UInt16Hr1RW
1221
Self Discharge Rate
UInt16%0.1RW
1231
Shunt Amp Rating
See section 5
UInt16A1RW
1241
Shunt Voltage Rating
0=50 1=60
UInt16mV1RW
1251
Charge Efficiency Factor Mode
0=Manual 1=Automatic
UInt16-1RW
1261
Backlight mode
The map prints this row's unit as s. See section 6 for the backlight modes.
UInt16s1RW
1271
Nominal Voltage
0=12 1=24 2=48
UInt16V1RW
1281
Setup lock
0=Disable 1=Enable
UInt16-1RW
1291
Time Remaining Averaging Filter
0=Fastest 1=Faster 2=Fast
UInt16-1RW
1301
Default Temperature
UInt16°C0.01 (offset -273)RW
1381
Charger Float Voltage
UInt16V0.001RW
1391
Charger Float Current
UInt16%0.1RW
1401
Discharge Floor
UInt16%1RW
1411
Auto Sync Time
See section 7
UInt16s1RW
1421
Auto Sync Sensitivity
UInt16%1RW
1442
Nominal Voltage Deprecated
UInt32V0.001RW
1461
Battery Capacity
UInt16Ah1RW
1471
Peukert Exponent
UInt16-0.002 (offset 1)RW
1481
Charge Efficiency Factor
UInt16%1RW
1601
RS485 Address
UInt16-1R
1611
RS485 Baud Rate
0=9600 1=19200 2=38400 3=57600 4=115200
UInt16-1R
1621
RS485 Parity
0=None 1=Odd 2=Even
UInt16-1R
1631
RS485 Stop Bits
1=1 2=2
UInt16-1R
1641
Modbus Byte Order
0=LSB 1=MSB
UInt16-1R
1721
Refresh Configuration Data
1=Refresh
UInt16-1RW
1731
Synchronize Enable/Disable
0=Disable 1=Enable
UInt16-1RW
1741
DC Association (Battery)
See section 8
UInt16-1RW
1751
Identify Enable
0=Disable 1=Enable
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

The unit ID is a declared placeholder: the map prints the device's own 'Modbus Address' register but no factory value, and the Conext ComBox / Conext Gateway assigns the Modbus addresses itself (the ComBox Owner's Guide says it assigns them per device type at installation, valid 1-247, and lets you change or reset them), so read the address from the ComBox's Settings > Modbus Address List and use that. Port 502 is the ComBox's default Modbus TCP port as printed in its Owner's Guide. The map prints no function code; the ComBox writes its string registers with function code 0x10 (write multiple registers), so these rows are holding registers. Addresses are the map's own hexadecimal 'Modbus Address' column, stored as zero-based wire addresses. Rows whose type the map gives as str<nn> are seeded as Ascii rows of nn/2 registers. The Conext Battery Monitor speaks Xanbus; these registers are the device map that the Conext ComBox or Conext Gateway presents over Modbus, and every register the map prints is in this file. The map's own RS-485 rows (0x00A0-0x00A4: address, baud rate, parity, stop bits, byte order) are read-only status rows that report the monitor's serial settings; the device is reached here through the ComBox or Gateway, which is why the seed is a TCP device. The printed hexadecimal numbers are the wire addresses (zero_based): in each of these maps the identity block is Device Name (str16) at 0x0000, FGA Number (str20) at 0x000A and Unique ID Number (str20) at 0x0014, so the ten registers of FGA Number run 0x000A-0x0013 into Unique ID Number at 0x0014, which only works if 0x0000 is register 0. The maps print no byte or word order for their uint32/sint32 rows, so HighFirst is the Modbus convention; if a two-register reading looks word-swapped, switch the device to LowFirst. Map: 'Modbus Map: Conext Battery Monitor Device', 503-0261-01-01 Revision A.4, in Schneider's 'Conext Modbus Maps V4' pack.