All devices

ORNO · Energy meter

OR-WE-517 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
21
Meter ID
1 to 247.
UInt16-1RW
31
Baud rate
1200, 2400, 4800 or 9600.
UInt16bps1RW
41
Software version
UInt16-1R
61
Hardware version
UInt16-1R
81
CT ratio
UInt16-1RW
92
S0 output rate
Float32imp/kWh1RW
111
Combined code
UInt16-1RW
121
Holiday/weekend tariff
UInt16-1RW
131
Display cycle time
UInt16s1RW
142
Voltage L1
Float32V1R
162
Voltage L2
Float32V1R
182
Voltage L3
Float32V1R
202
Grid frequency
Float32Hz1R
222
Current L1
Float32A1R
242
Current L2
Float32A1R
262
Current L3
Float32A1R
282
Total active power
Float32W1000R
302
Active power L1
Float32W1000R
322
Active power L2
Float32W1000R
342
Active power L3
Float32W1000R
362
Total reactive power
Float32var1000R
382
Reactive power L1
Float32var1000R
402
Reactive power L2
Float32var1000R
422
Reactive power L3
Float32var1000R
442
Total apparent power
Float32VA1000R
462
Apparent power L1
Float32VA1000R
482
Apparent power L2
Float32VA1000R
502
Apparent power L3
Float32VA1000R
522
Total power factor
Float32-1R
542
Power factor L1
Float32-1R
562
Power factor L2
Float32-1R
582
Power factor L3
Float32-1R
2562
Total active energy
Float32kWh1R
2582
L1 total active energy
Float32kWh1R
2602
L2 total active energy
Float32kWh1R
2622
L3 total active energy
Float32kWh1R
2642
Forward active energy
Float32kWh1R
2662
L1 forward active energy
Float32kWh1R
2682
L2 forward active energy
Float32kWh1R
2702
L3 forward active energy
Float32kWh1R
2722
Reverse active energy
Float32kWh1R
2742
L1 reverse active energy
Float32kWh1R
2762
L2 reverse active energy
Float32kWh1R
2782
L3 reverse active energy
Float32kWh1R
2802
Total reactive energy
Float32kVArh1R
2822
L1 reactive energy
Float32kVArh1R
2842
L2 reactive energy
Float32kVArh1R
2862
L3 reactive energy
Float32kVArh1R
2882
Forward reactive energy
Float32kVArh1R
2902
L1 forward reactive energy
Float32kVArh1R
2922
L2 forward reactive energy
Float32kVArh1R
2942
L3 forward reactive energy
Float32kVArh1R
2962
Reverse reactive energy
Float32kVArh1R
2982
L1 reverse reactive energy
Float32kVArh1R
3002
L2 reverse reactive energy
Float32kVArh1R
3022
L3 reverse reactive energy
Float32kVArh1R
3042
Tariff 1 total active energy
Float32kWh1R
3062
Tariff 1 forward active energy
Float32kWh1R
3082
Tariff 1 reverse active energy
Float32kWh1R
3102
Tariff 1 total reactive energy
Float32kVArh1R
3122
Tariff 1 forward reactive energy
Float32kVArh1R
3142
Tariff 1 reverse reactive energy
Float32kVArh1R
3162
Tariff 2 total active energy
Float32kWh1R
3182
Tariff 2 forward active energy
Float32kWh1R
3202
Tariff 2 reverse active energy
Float32kWh1R
3222
Tariff 2 total reactive energy
Float32kVArh1R
3242
Tariff 2 forward reactive energy
Float32kVArh1R
3262
Tariff 2 reverse reactive energy
Float32kVArh1R
3282
Tariff 3 total active energy
Float32kWh1R
3302
Tariff 3 forward active energy
Float32kWh1R
3322
Tariff 3 reverse active energy
Float32kWh1R
3342
Tariff 3 total reactive energy
Float32kVArh1R
3362
Tariff 3 forward reactive energy
Float32kVArh1R
3382
Tariff 3 reverse reactive energy
Float32kVArh1R
3402
Tariff 4 total active energy
Float32kWh1R
3422
Tariff 4 forward active energy
Float32kWh1R
3442
Tariff 4 reverse active energy
Float32kWh1R
3462
Tariff 4 total reactive energy
Float32kVArh1R
3482
Tariff 4 forward reactive energy
Float32kVArh1R
3502
Tariff 4 reverse reactive energy
Float32kVArh1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. All values are IEEE-754 Float32 with the high word first and are read/written with function code 03. Power values are reported by the meter in kW/kvar/kVA and converted to W/var/VA here (scale 1000). The tariff time-interval blocks at 0x0300-0x036F are not mapped because their packed date/time layout is model-specific.