Goodrive350-UL series high-performance VFD Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
81921
Communication-based control command
2000H. 0001H forward run, 0002H reverse run, 0003H forward jogging, 0004H reverse jogging, 0005H stop, 0006H coast to stop, 0007H fault reset, 0008H jogging to stop. Requires P00.01 = 2 (communication) and P00.02 = 0 (Modbus).
UInt16-1RW
81931
Communication-based frequency setting
2001H. 0 to Fmax, unit 0.01 Hz (fieldbus scale 100).
UInt16Hz0.01RW
81941
PID setting
2002H. 0-1000, 1000 corresponds to 100.0 %. Requires the PID reference source P09.00 to select Modbus communication.
UInt16%0.1RW
81951
PID feedback
2003H. 0-1000, 1000 corresponds to 100.0 %.
UInt16%0.1RW
81961
Torque setting
2004H. -3000 to +3000, 1000 corresponds to 100.0 % of the rated motor current.
Int16%0.1RW
81971
Upper limit of forward running frequency
2005H. 0 to Fmax, unit 0.01 Hz.
UInt16Hz0.01RW
81981
Upper limit of reverse running frequency
2006H. 0 to Fmax, unit 0.01 Hz.
UInt16Hz0.01RW
81991
Upper limit of electromotion torque
2007H. 0-3000, 1000 corresponds to 100.0 % of the rated VFD current.
UInt16%0.1RW
82001
Upper limit of brake torque
2008H. 0-3000, 1000 corresponds to 100.0 % of the rated motor current.
UInt16%0.1RW
82011
Special control command word
2009H. Bits 1-0 motor selection (00 motor 1 ... 11 motor 4), bit 2 torque control disabled, bit 3 power consumption reset, bit 4 pre-excitation, bit 5 DC brake.
UInt16-1RW
82021
Virtual input terminal command
200AH. 0x000-0x1FF. Virtual input terminal command bits; each bit acts as a digital input, for example a virtual forward-run or fault-reset terminal.
Hex-1RW
82031
Virtual output terminal command
200BH. 0x00-0x0F. Virtual output terminal command bits (VDO1-VDO4), used when an output function is set to Modbus.
Hex-1RW
82041
Voltage setting
200CH. 0-1000, 1000 corresponds to 100.0 % of the rated motor voltage; used with V/F separation.
UInt16%0.1RW
82051
AO output setting 1
200DH. -1000 to +1000, 1000 corresponds to 100.0 %.
Int16%0.1RW
82061
AO output setting 2
200EH. -1000 to +1000, 1000 corresponds to 100.0 %.
Int16%0.1RW
84481
VFD state word 1
2100H. 0001H forward running, 0002H reverse running, 0003H stopped, 0004H faulty, 0005H POFF, 0006H pre-excited.
UInt16-1R
84491
VFD state word 2
2101H. Bit 0 ready to run, bits 2-1 motor selection, bit 3 asynchronous/synchronous machine, bit 4 overload alarm, bits 6-5 control source (00 keypad, 01 terminal, 10 communication), bit 8 speed/torque control, bit 9 position control, bits 11-10 control mode.
UInt16-1R
84501
VFD fault code
2102H. Fault code of the active fault, see the fault-type description in the manual.
UInt16-1R
84511
VFD identification code
2103H. Device identification code. The device-code table gives 01H for the GD series in the 8 most significant bits and a0H for the GD350-UL vector VFD in the 8 least significant bits (01A0H), while the state-word table itself prints GD350-UL as 0109H; the two statements conflict in the manual and 01A0H is the one the encoding table defines.
Hex-1R
122881
Running frequency
3000H. 0 to Fmax, unit 0.01 Hz.
UInt16Hz0.01R
122891
Set frequency
3001H. 0 to Fmax, unit 0.01 Hz.
UInt16Hz0.01R
122901
Bus voltage
3002H. 0.0-2000.0 V, unit 0.1 V.
UInt16V0.1R
122911
Output voltage
3003H. 0-1200 V, unit 1 V.
UInt16V1R
122921
Output current
3004H. 0.0-3000.0 A, unit 0.1 A.
UInt16A0.1R
122931
Rotating speed
3005H. 0-65535, unit 1 RPM.
UInt16rpm1R
122941
Output power
3006H. -300.0 to +300.0 %, unit 0.1 %.
Int16%0.1R
122951
Output torque
3007H. -250.0 to +250.0 %, unit 0.1 %.
Int16%0.1R
122961
Closed-loop setting
3008H. -100.0 to +100.0 %, unit 0.1 %.
Int16%0.1R
122971
Closed-loop feedback
3009H. -100.0 to +100.0 %, unit 0.1 %.
Int16%0.1R
122981
Input state
300AH. 000-1FF, the state of the digital inputs.
Hex-1R
122991
Output state
300BH. 000-1FF, the state of the digital and relay outputs.
Hex-1R
123001
Analog input 1
300CH. 0.00-10.00 V, unit 0.01 V.
UInt16V0.01R
123011
Analog input 2
300DH. 0.00-10.00 V, unit 0.01 V.
UInt16V0.01R
123021
Analog input 3
300EH. -10.00 to +10.00 V, unit 0.01 V.
Int16V0.01R
123031
Analog input 4
300FH. -10.00 to +10.00 V, unit 0.01 V.
Int16V0.01R
123041
High-speed pulse input 1
3010H. 0.00-50.00 kHz range, resolution 0.01 kHz; the manual prints the resolution suffix as 'unit: 0.01Hz' against this kHz range, which contradicts the range and is read as kHz.
UInt16kHz0.01R
123051
High-speed pulse input 2
3011H. 0.00-50.00 kHz range, resolution 0.01 kHz; the manual prints the resolution suffix as 'unit: 0.01Hz' against this kHz range, which contradicts the range and is read as kHz.
UInt16kHz0.01R
123061
Current step of multi-step speed
3012H. 0-15.
UInt16-1R
123071
External length
3013H. 0-65535.
UInt16-1R
123081
External count value
3014H. 0-65535.
UInt16-1R
123091
Torque setting (monitor)
3015H. -300.0 to +300.0 %, unit 0.1 %.
Int16%0.1R
123101
Identification code (monitor)
3016H. Device identification code.
Hex-1R
204801
Fault code (monitor area)
5000H. Fault code as exposed in the monitor area.
UInt16-1R
11
P00.01 Running command channel
Parameter P00.01 at 0001H: 0 keypad, 1 terminal, 2 communication. Set to 2 to let the drive accept run commands from Modbus.
UInt16-1RW
21
P00.02 Communication running command channel
Parameter P00.02 at 0002H: 0 Modbus, 1 PROFIBUS/CANopen/DeviceNet, 2 Ethernet, 3 EtherCAT/PROFINET, 4 PLC card, 5 Bluetooth card. Set to 0 for Modbus control.
UInt16-1RW
31
P00.03 Maximum output frequency
Parameter P00.03 at 0003H: unit 0.01 Hz, factory 60.00 Hz. The parameter list gives the range as P00.04-400.00 Hz and the detailed description as Max. (P00.04, 10.00)-630.00 Hz; the keypad figure prints a minimum and default of 50.00 Hz instead, which the parameter list contradicts.
UInt16Hz0.01RW
41
P00.04 Upper limit of running frequency
Parameter P00.04 at 0004H: range P00.05-P00.03, unit 0.01 Hz, factory 60.00 Hz.
UInt16Hz0.01RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Addresses are the manual's hexadecimal function-code addresses used unchanged on the wire: control and setting words 2000H-200EH, state words 2100H-2103H, monitors 3000H-3016H, fault code 5000H, and parameters addressed as 0xGGNN where GG is the group and NN the index after the dot (P00.01 = 0001H, P10.01 = 0A01H). Factory serial settings are P14.00 local address = 1, P14.01 baud rate = 4 (19200 bps) and P14.02 data bit check = 1 (even parity, 8 data bits, 1 stop bit). Communication control additionally requires P00.01 Running command channel = 2 (communication) and P00.02 Communication running command channel = 0 (Modbus); PID setpoints need P09.00 to select Modbus. Every parameter carries a fieldbus scale of 10^n where n is the number of decimals printed for it, so a value with two decimals is sent multiplied by 100. Writing a parameter with the most significant address byte changed from 00 to 80 writes RAM only instead of EEPROM (for example 8007H instead of 0007H for P00.07). Source: INVT 'Goodrive350-UL Series High-performance Multi-function VFD' operation manual, change history V1.1 (Nov 2019), chapter 9 'Communication protocol' - section 9.4.5.1 address representation rules (page 274), 9.4.5.2 control, state and monitor addresses (pages 275-277), 9.4.6 fieldbus scale (page 278), and the P14 group serial communication parameters (pages 200-202); PDF at https://www.invt.com/uploads/file1/20200628/GD350-UL%20Series%20VFD%20Manual.pdf.