  "spec_version": 1,
  "slug": "invt-goodrive350-ul",
  "manufacturer": "INVT",
  "model": "Goodrive350-UL series high-performance VFD",
  "category": "VFD",
  "supplier_url": "https://www.invt.com/product/goodrive350-ul-series-high-performance-vfd",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 8192,
      "count": 1,
      "name": "Communication-based control command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "2000H. 0001H forward run, 0002H reverse run, 0003H forward jogging, 0004H reverse jogging, 0005H stop, 0006H coast to stop, 0007H fault reset, 0008H jogging to stop. Requires P00.01 = 2 (communication) and P00.02 = 0 (Modbus)."
    },
    {
      "address": 8193,
      "count": 1,
      "name": "Communication-based frequency setting",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "2001H. 0 to Fmax, unit 0.01 Hz (fieldbus scale 100)."
    },
    {
      "address": 8194,
      "count": 1,
      "name": "PID setting",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "2002H. 0-1000, 1000 corresponds to 100.0 %. Requires the PID reference source P09.00 to select Modbus communication."
    },
    {
      "address": 8195,
      "count": 1,
      "name": "PID feedback",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "2003H. 0-1000, 1000 corresponds to 100.0 %."
    },
    {
      "address": 8196,
      "count": 1,
      "name": "Torque setting",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "2004H. -3000 to +3000, 1000 corresponds to 100.0 % of the rated motor current."
    },
    {
      "address": 8197,
      "count": 1,
      "name": "Upper limit of forward running frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "2005H. 0 to Fmax, unit 0.01 Hz."
    },
    {
      "address": 8198,
      "count": 1,
      "name": "Upper limit of reverse running frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "2006H. 0 to Fmax, unit 0.01 Hz."
    },
    {
      "address": 8199,
      "count": 1,
      "name": "Upper limit of electromotion torque",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "2007H. 0-3000, 1000 corresponds to 100.0 % of the rated VFD current."
    },
    {
      "address": 8200,
      "count": 1,
      "name": "Upper limit of brake torque",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "2008H. 0-3000, 1000 corresponds to 100.0 % of the rated motor current."
    },
    {
      "address": 8201,
      "count": 1,
      "name": "Special control command word",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "2009H. Bits 1-0 motor selection (00 motor 1 ... 11 motor 4), bit 2 torque control disabled, bit 3 power consumption reset, bit 4 pre-excitation, bit 5 DC brake."
    },
    {
      "address": 8202,
      "count": 1,
      "name": "Virtual input terminal command",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "200AH. 0x000-0x1FF. Virtual input terminal command bits; each bit acts as a digital input, for example a virtual forward-run or fault-reset terminal."
    },
    {
      "address": 8203,
      "count": 1,
      "name": "Virtual output terminal command",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "200BH. 0x00-0x0F. Virtual output terminal command bits (VDO1-VDO4), used when an output function is set to Modbus."
    },
    {
      "address": 8204,
      "count": 1,
      "name": "Voltage setting",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "200CH. 0-1000, 1000 corresponds to 100.0 % of the rated motor voltage; used with V/F separation."
    },
    {
      "address": 8205,
      "count": 1,
      "name": "AO output setting 1",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "200DH. -1000 to +1000, 1000 corresponds to 100.0 %."
    },
    {
      "address": 8206,
      "count": 1,
      "name": "AO output setting 2",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "200EH. -1000 to +1000, 1000 corresponds to 100.0 %."
    },
    {
      "address": 8448,
      "count": 1,
      "name": "VFD state word 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "2100H. 0001H forward running, 0002H reverse running, 0003H stopped, 0004H faulty, 0005H POFF, 0006H pre-excited."
    },
    {
      "address": 8449,
      "count": 1,
      "name": "VFD state word 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "2101H. Bit 0 ready to run, bits 2-1 motor selection, bit 3 asynchronous/synchronous machine, bit 4 overload alarm, bits 6-5 control source (00 keypad, 01 terminal, 10 communication), bit 8 speed/torque control, bit 9 position control, bits 11-10 control mode."
    },
    {
      "address": 8450,
      "count": 1,
      "name": "VFD fault code",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "2102H. Fault code of the active fault, see the fault-type description in the manual."
    },
    {
      "address": 8451,
      "count": 1,
      "name": "VFD identification code",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "2103H. Device identification code. The device-code table gives 01H for the GD series in the 8 most significant bits and a0H for the GD350-UL vector VFD in the 8 least significant bits (01A0H), while the state-word table itself prints GD350-UL as 0109H; the two statements conflict in the manual and 01A0H is the one the encoding table defines."
    },
    {
      "address": 12288,
      "count": 1,
      "name": "Running frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "3000H. 0 to Fmax, unit 0.01 Hz."
    },
    {
      "address": 12289,
      "count": 1,
      "name": "Set frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "3001H. 0 to Fmax, unit 0.01 Hz."
    },
    {
      "address": 12290,
      "count": 1,
      "name": "Bus voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3002H. 0.0-2000.0 V, unit 0.1 V."
    },
    {
      "address": 12291,
      "count": 1,
      "name": "Output voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3003H. 0-1200 V, unit 1 V."
    },
    {
      "address": 12292,
      "count": 1,
      "name": "Output current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3004H. 0.0-3000.0 A, unit 0.1 A."
    },
    {
      "address": 12293,
      "count": 1,
      "name": "Rotating speed",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3005H. 0-65535, unit 1 RPM."
    },
    {
      "address": 12294,
      "count": 1,
      "name": "Output power",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3006H. -300.0 to +300.0 %, unit 0.1 %."
    },
    {
      "address": 12295,
      "count": 1,
      "name": "Output torque",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3007H. -250.0 to +250.0 %, unit 0.1 %."
    },
    {
      "address": 12296,
      "count": 1,
      "name": "Closed-loop setting",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3008H. -100.0 to +100.0 %, unit 0.1 %."
    },
    {
      "address": 12297,
      "count": 1,
      "name": "Closed-loop feedback",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3009H. -100.0 to +100.0 %, unit 0.1 %."
    },
    {
      "address": 12298,
      "count": 1,
      "name": "Input state",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "300AH. 000-1FF, the state of the digital inputs."
    },
    {
      "address": 12299,
      "count": 1,
      "name": "Output state",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "300BH. 000-1FF, the state of the digital and relay outputs."
    },
    {
      "address": 12300,
      "count": 1,
      "name": "Analog input 1",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "300CH. 0.00-10.00 V, unit 0.01 V."
    },
    {
      "address": 12301,
      "count": 1,
      "name": "Analog input 2",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "300DH. 0.00-10.00 V, unit 0.01 V."
    },
    {
      "address": 12302,
      "count": 1,
      "name": "Analog input 3",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "300EH. -10.00 to +10.00 V, unit 0.01 V."
    },
    {
      "address": 12303,
      "count": 1,
      "name": "Analog input 4",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "300FH. -10.00 to +10.00 V, unit 0.01 V."
    },
    {
      "address": 12304,
      "count": 1,
      "name": "High-speed pulse input 1",
      "data_type": "UInt16",
      "units": "kHz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "3010H. 0.00-50.00 kHz range, resolution 0.01 kHz; the manual prints the resolution suffix as 'unit: 0.01Hz' against this kHz range, which contradicts the range and is read as kHz."
    },
    {
      "address": 12305,
      "count": 1,
      "name": "High-speed pulse input 2",
      "data_type": "UInt16",
      "units": "kHz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "3011H. 0.00-50.00 kHz range, resolution 0.01 kHz; the manual prints the resolution suffix as 'unit: 0.01Hz' against this kHz range, which contradicts the range and is read as kHz."
    },
    {
      "address": 12306,
      "count": 1,
      "name": "Current step of multi-step speed",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3012H. 0-15."
    },
    {
      "address": 12307,
      "count": 1,
      "name": "External length",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3013H. 0-65535."
    },
    {
      "address": 12308,
      "count": 1,
      "name": "External count value",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3014H. 0-65535."
    },
    {
      "address": 12309,
      "count": 1,
      "name": "Torque setting (monitor)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "3015H. -300.0 to +300.0 %, unit 0.1 %."
    },
    {
      "address": 12310,
      "count": 1,
      "name": "Identification code (monitor)",
      "data_type": "Hex",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "3016H. Device identification code."
    },
    {
      "address": 20480,
      "count": 1,
      "name": "Fault code (monitor area)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "5000H. Fault code as exposed in the monitor area."
    },
    {
      "address": 1,
      "count": 1,
      "name": "P00.01 Running command channel",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Parameter P00.01 at 0001H: 0 keypad, 1 terminal, 2 communication. Set to 2 to let the drive accept run commands from Modbus."
    },
    {
      "address": 2,
      "count": 1,
      "name": "P00.02 Communication running command channel",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Parameter P00.02 at 0002H: 0 Modbus, 1 PROFIBUS/CANopen/DeviceNet, 2 Ethernet, 3 EtherCAT/PROFINET, 4 PLC card, 5 Bluetooth card. Set to 0 for Modbus control."
    },
    {
      "address": 3,
      "count": 1,
      "name": "P00.03 Maximum output frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "Parameter P00.03 at 0003H: unit 0.01 Hz, factory 60.00 Hz. The parameter list gives the range as P00.04-400.00 Hz and the detailed description as Max. (P00.04, 10.00)-630.00 Hz; the keypad figure prints a minimum and default of 50.00 Hz instead, which the parameter list contradicts."
    },
    {
      "address": 4,
      "count": 1,
      "name": "P00.04 Upper limit of running frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "Parameter P00.04 at 0004H: range P00.05-P00.03, unit 0.01 Hz, factory 60.00 Hz."
    }
  ],
  "combined_registers": [],
  "notes": "Addresses are the manual's hexadecimal function-code addresses used unchanged on the wire: control and setting words 2000H-200EH, state words 2100H-2103H, monitors 3000H-3016H, fault code 5000H, and parameters addressed as 0xGGNN where GG is the group and NN the index after the dot (P00.01 = 0001H, P10.01 = 0A01H). Factory serial settings are P14.00 local address = 1, P14.01 baud rate = 4 (19200 bps) and P14.02 data bit check = 1 (even parity, 8 data bits, 1 stop bit). Communication control additionally requires P00.01 Running command channel = 2 (communication) and P00.02 Communication running command channel = 0 (Modbus); PID setpoints need P09.00 to select Modbus. Every parameter carries a fieldbus scale of 10^n where n is the number of decimals printed for it, so a value with two decimals is sent multiplied by 100. Writing a parameter with the most significant address byte changed from 00 to 80 writes RAM only instead of EEPROM (for example 8007H instead of 0007H for P00.07). Source: INVT 'Goodrive350-UL Series High-performance Multi-function VFD' operation manual, change history V1.1 (Nov 2019), chapter 9 'Communication protocol' - section 9.4.5.1 address representation rules (page 274), 9.4.5.2 control, state and monitor addresses (pages 275-277), 9.4.6 fieldbus scale (page 278), and the P14 group serial communication parameters (pages 200-202); PDF at https://www.invt.com/uploads/file1/20200628/GD350-UL%20Series%20VFD%20Manual.pdf."
}