All devices

Wilo · Pump controller

Para MAXO / Stratos MAXO circulating pump Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
101
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
Pressure
Register 300001 (Wilo register 1). Range 0-65534, 65535 = error value.
UInt16cmH2O10R
21
Flow (calculated)
Register 300002. Range 0-65534, 65535 = error value and must not be read as 6553.5 m3/h.
UInt16m3/h0.1R
31
Energy consumption
Register 300003.
UInt16kWh1R
41
Power input
Register 300004.
UInt16W1R
51
Operation time
Register 300005, scope 'master pump'.
UInt16h10R
71
Speed
Register 300007, scope 'master pump'.
UInt16rpm1R
101
Control function
Register 300010, WORD; the active control function value (see the holding register 'Control Function' for the value list).
UInt16-1R
181
Speed max-pres-value
Register 300018, speed at the maximum pressure value.
UInt16rpm1R
191
Speed min-pres-value
Register 300019, speed at the minimum pressure value.
UInt16rpm1R
241
Flow (calculated) max-pres-value
Register 300024.
UInt16m3/h0.1R
251
Flow (calculated) min-pres-value
Register 300025.
UInt16m3/h0.1R
2001
Duty point (relative)
Register 300200. Range -32768...32766, 32767 = error value.
Int16%0.5R
2021
Duty point (relative) maximum output
Register 300202.
Int16%0.5R
2041
Duty point (relative) minimum output
Register 300204.
Int16%0.5R
2062
Duty point 100 % value
Register 300206, REAL (2 registers): the relative duty point that corresponds to 100 %.
Float32%1R
2081
Duty point (relative) units
Register 300208, unit code of the relative duty point.
UInt16-1R
4001
Duty point (relative)
Register 300400, the duty point actually applied by the pump system.
Int16%0.5R
4041
Operation status
Register 300404, WORD bit field; the trouble-reporting chapter lists its bits in the 'Reg 404 - Reg 940 Status' table together with the warning/error codes.
UInt16-1R
7001
Application version
Register 300700, WORD application version.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Wilo 'Technical guide - MODBUS', version V01.01 (18/06/2024, rev. V01.01 13/02/2025), chapters 'Holding register data model', 'Input register data model' (1/2 and 2/2) and 'Modbus pump control' - vendor-hosted at wilo.com (SHA-256 92b7801d0721b7f79b3e69133e02b0f3567db1005c07e9f2a835ec2a71ee509f). Factory frame from the guide's own defaults box and addressing chapter: 19200 baud, 8 data bits, even parity, 1 stop bit, slave address 101. Addressing: the guide states 'Unlike the Modbus Standard, Wilo register numbers start from zero. So, the starting address is equal to the register number', so the seed stores the integers from the guide's 'Wilo Register' column and declares zero_based; its 'Register' column is the same number written as a 1-based 4xxxx/3xxxx reference (Wilo register 1 = 400002/300001) which the schema's 0-65535 address field cannot hold. Scale 0.5 is the guide's '0,5' in the Scale column for every relative duty-point row. Omitted on purpose: every row the guide types BYTE, USINT or UDINT (Pump Command active/preset, Bus Command Timer, interface device identifier, transmission serial speed and transmission serial frame, heartbeat count, bus-command-timer remaining time, warning/error message, parameter block acknowledge) because this schema has no 8-bit type and the guide states no word order or register width for its 32-bit values; the same reason leaves out Vendor ID (DWORD). Documents that extend the same map for other Wilo ranges are not covered by this seed.