Wilo · Pump controller
Para MAXO / Stratos MAXO circulating pump Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 101
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1 | 1 | Pressure Register 300001 (Wilo register 1). Range 0-65534, 65535 = error value. | UInt16 | cmH2O | 10 | R |
| 2 | 1 | Flow (calculated) Register 300002. Range 0-65534, 65535 = error value and must not be read as 6553.5 m3/h. | UInt16 | m3/h | 0.1 | R |
| 3 | 1 | Energy consumption Register 300003. | UInt16 | kWh | 1 | R |
| 4 | 1 | Power input Register 300004. | UInt16 | W | 1 | R |
| 5 | 1 | Operation time Register 300005, scope 'master pump'. | UInt16 | h | 10 | R |
| 7 | 1 | Speed Register 300007, scope 'master pump'. | UInt16 | rpm | 1 | R |
| 10 | 1 | Control function Register 300010, WORD; the active control function value (see the holding register 'Control Function' for the value list). | UInt16 | - | 1 | R |
| 18 | 1 | Speed max-pres-value Register 300018, speed at the maximum pressure value. | UInt16 | rpm | 1 | R |
| 19 | 1 | Speed min-pres-value Register 300019, speed at the minimum pressure value. | UInt16 | rpm | 1 | R |
| 24 | 1 | Flow (calculated) max-pres-value Register 300024. | UInt16 | m3/h | 0.1 | R |
| 25 | 1 | Flow (calculated) min-pres-value Register 300025. | UInt16 | m3/h | 0.1 | R |
| 200 | 1 | Duty point (relative) Register 300200. Range -32768...32766, 32767 = error value. | Int16 | % | 0.5 | R |
| 202 | 1 | Duty point (relative) maximum output Register 300202. | Int16 | % | 0.5 | R |
| 204 | 1 | Duty point (relative) minimum output Register 300204. | Int16 | % | 0.5 | R |
| 206 | 2 | Duty point 100 % value Register 300206, REAL (2 registers): the relative duty point that corresponds to 100 %. | Float32 | % | 1 | R |
| 208 | 1 | Duty point (relative) units Register 300208, unit code of the relative duty point. | UInt16 | - | 1 | R |
| 400 | 1 | Duty point (relative) Register 300400, the duty point actually applied by the pump system. | Int16 | % | 0.5 | R |
| 404 | 1 | Operation status Register 300404, WORD bit field; the trouble-reporting chapter lists its bits in the 'Reg 404 - Reg 940 Status' table together with the warning/error codes. | UInt16 | - | 1 | R |
| 700 | 1 | Application version Register 300700, WORD application version. | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Wilo 'Technical guide - MODBUS', version V01.01 (18/06/2024, rev. V01.01 13/02/2025), chapters 'Holding register data model', 'Input register data model' (1/2 and 2/2) and 'Modbus pump control' - vendor-hosted at wilo.com (SHA-256 92b7801d0721b7f79b3e69133e02b0f3567db1005c07e9f2a835ec2a71ee509f). Factory frame from the guide's own defaults box and addressing chapter: 19200 baud, 8 data bits, even parity, 1 stop bit, slave address 101. Addressing: the guide states 'Unlike the Modbus Standard, Wilo register numbers start from zero. So, the starting address is equal to the register number', so the seed stores the integers from the guide's 'Wilo Register' column and declares zero_based; its 'Register' column is the same number written as a 1-based 4xxxx/3xxxx reference (Wilo register 1 = 400002/300001) which the schema's 0-65535 address field cannot hold. Scale 0.5 is the guide's '0,5' in the Scale column for every relative duty-point row. Omitted on purpose: every row the guide types BYTE, USINT or UDINT (Pump Command active/preset, Bus Command Timer, interface device identifier, transmission serial speed and transmission serial frame, heartbeat count, bus-command-timer remaining time, warning/error message, parameter block acknowledge) because this schema has no 8-bit type and the guide states no word order or register width for its 32-bit values; the same reason leaves out Vendor ID (DWORD). Documents that extend the same map for other Wilo ranges are not covered by this seed.
Related devices
- Aquavar CPC centrifugal pump controller, software version 204 and laterGoulds Pumps (Xylem)
- Dedicated Controls CU 361 / CU 362 with CIM 200Grundfos
- Hydro MPC / Control MPC booster system with GENIECON controller (CIM 200 Modbus RTU)Grundfos
- MAGNA3 / TPE / NBE / CRE / CUE E-pumps with CIM 200 or CIM 500Grundfos