Goulds Pumps (Xylem) · Pump controller

Aquavar CPC centrifugal pump controller, software version 204 and later Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
STOP
Control word bit 0. Write 1 to stop the drive; must be 0 to allow a start.
Binary-1RW
21
START
Control word bit 1. Write 1 to start the drive; STOP must be 0.
Binary-1RW
51
RESET
Control word bit 4. Write 1 to reset a fault.
Binary-1RW
61
EXT2
Control word bit 5. 1 = EXT2, 0 = EXT1.
Binary-1RW
331
Relay output 1
Relay output 1 command (not part of the control word).
Binary-1RW
341
Relay output 2
Relay output 2 command.
Binary-1RW
351
Relay output 3
Relay output 3 command.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Goulds Pumps (Xylem) "Aquavar CPC - Modbus Communications (Software Version 204 and later)", document ADAQCPC R1, addendum to installation and operation manual IM167 (https://d1pkofokfruj4.cloudfront.net/media/upload/resource/b/Goulds-Pumps-Aquavar-CPC-Centrifugal-Pump-Controller-Modbus-Instruction-Manual.pdf). Factory serial settings from the "Wiring" section: default baud rate 9.6 kb/s and default parity 8N2 (8 data bits, no parity, two stop bits); the station ID (parameter 3202, 1-247) has no documented factory value, so unit ID 1 is a placeholder. Addressing: the document prints 5-digit Modbus references (00001 coils, 10001 discrete inputs, 30001 input registers, 4xxxx holding registers); the seed stores the reference number after the data-area prefix (00002 -> 2, 40101 -> 101) and declares one-based, so the client sends reference minus one. Modbus RTU only (ASCII not supported), RS-485 two-wire. Modbus must be activated once (Group 30, option [1] STD MODBUS) and the application macro must be [1] Single Pump, [4] Constant Slv or [5] Speed Cntrl. Start/stop control over Modbus also requires parameter 1201 = [1] Fieldbus. Omitted on purpose: the group 1 and group 2 signal registers (40101-40209) and the selectable Actual 1-8 registers (40005-40012), because the document does not state their scaling (the Actual registers mirror whichever parameter is selected with 3210-3217 and the group 1/2 rows carry no scale); group 10/14/18/21/25/32 parameter rows are configuration values without documented units. Coils/interrupt bits whose reference is marked "Reserved (Not Used)" are omitted.