Grundfos · Pump controller

Hydro MPC / Control MPC booster system with GENIECON controller (CIM 200 Modbus RTU) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
3011
Head
Actual system head/pressure, 0.001 bar.
UInt16bar0.001R
3021
Volume flow
Actual system flow, 0.1 m3/h.
UInt16m3/h0.1R
3031
Relative performance
Relative performance of the booster system, 0.01 %.
UInt16%0.01R
3061
Digital input
Logical value of the external digital input signals, one bit per input.
UInt16-1R
3071
Digital output
Logical value of the external digital output signals, one bit per output.
UInt16-1R
3081
Actual set-point
Actual set-point, 0.01 % of the set-point range.
UInt16%0.01R
3091
Motor current
Actual motor current, 0.1 A.
UInt16A0.1R
3151
Inlet pressure
Inlet pressure, 0.001 bar (sensor required).
UInt16bar0.001R
3171
Storage tank level
Storage-tank level, 0.01 m (sensor required).
UInt16m0.01R
3411
Outlet pressure
System outlet pressure, 0.001 bar (sensor required).
UInt16bar0.001R
3431
User set-point
Set-point entered by the user, 0.01 % of the set-point range; same scaling as control register 104.
UInt16%0.01R
3441
Analogue influence
Set-point attenuator, 0.01 %.
UInt16%0.01R
3461
Specific energy
Specific energy of the booster system, raw value in 0.1 Wh/m3 (document scale "0.1 Wh/m3").
UInt16Wh/m30.1R
3471
Average specific energy
Average specific energy, 0.1 Wh/m3.
UInt16Wh/m30.1R
4011
Pump 1 status
Bit0 AccessMode (0 = local control by pump buttons, 1 = remote control by the booster system), bit1 OnOff (0 = off, 1 = on), bit2 Alarm (0 = no alarm, 1 = alarm). Not available on Hydro Multi-E model G.
UInt16-1R
4021
Pump 1 alarm code
Grundfos-specific alarm code, see the alarm and warning code table.
UInt16-1R
4032
Pump 1 operating time
Operating time of the pump, 32-bit value (high word 403, low word 404), 1 hour.
UInt32h1R
4051
Pump 1 speed
Speed of the pump motor, 0.01 %. Not available on Hydro Multi-E model G.
UInt16%0.01R
4061
Pump 1 line current
Average value of the line currents on the pump, 0.1 A. Not available on Hydro Multi-E model G.
UInt16A0.1R
4071
Pump 1 power
Power consumption of the pump, 10 W. Not available on Hydro Multi-E model G.
UInt16W10R
4081
Pump 1 motor temperature
Motor temperature of the pump, 0.01 K. Not available on Hydro Multi-E model G.
UInt16K0.01R
4091
Pump 1 control source
0 = unknown, 1 = buttons on the pump, 2 = GENIbus (booster controller), 3 = GENIlink/GENIair (handheld controller), 4 = external control. Not available on Hydro Multi-E model G.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Grundfos "Modbus for Grundfos boosters - SoftCIM Modbus RTU, SoftCIM Modbus TCP, CIM/CIU 200 Modbus RTU, CIM/CIU 500 Ethernet for Modbus TCP", functional profile and user manual, document Grundfosliterature-6012934 (https://api.grundfos.com/literature/Grundfosliterature-6012934.pdf), applies to GENIECON MPC, Hydro MPC, CU 352 and Control MPC. This seed models the CIM 200 Modbus RTU path: section 4.2/5.1/5.2 document the default frame 19200 bps, even parity, 8 data bits, 1 stop bit (the CIM 200 default is even parity with 1 stop bit; 19200 is the default transmission speed). The slave address is set with the hexadecimal rotary switches SW6/SW7 (1-247) and the document states no factory value, so unit ID 1 is a placeholder. Section 10.1 states that registers numbered X are addressed in telegrams as X-1 (register 00104 setpoint is addressed as 00103), hence one-based. 32-bit values combine high word at the lower address (HI × 65536 + LO). Omitted on purpose: the CIM configuration and status blocks (00001-00021), the status register block (00201-00209), the remaining pump blocks (pump 2-6 start at 00411/00421/00431/00441/00451 with the same layout), the DDD remote sensors, alarm simulation and user registers, the 32-bit counters (operating time 1 hour, powered time 1 hour, energy 1 kWh, pumped volume 0.1 m3) and the remaining sensor rows, as a scope choice, and the model-dependent set-point tables for DDD sensors. Registers 00401-00409 are the pump 1 block.