  "spec_version": 1,
  "slug": "wilo-para-maxo",
  "manufacturer": "Wilo",
  "model": "Para MAXO / Stratos MAXO circulating pump",
  "category": "Pump controller",
  "supplier_url": "https://wilo.com/oem/en/Support/Technical-Documentation/Modbus/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 101,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [
    {
      "address": 1,
      "count": 1,
      "name": "Pressure",
      "data_type": "UInt16",
      "units": "cmH2O",
      "scale_factor": 10,
      "offset": 0,
      "access": "R",
      "description": "Register 300001 (Wilo register 1). Range 0-65534, 65535 = error value."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Flow (calculated)",
      "data_type": "UInt16",
      "units": "m3/h",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 300002. Range 0-65534, 65535 = error value and must not be read as 6553.5 m3/h."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Energy consumption",
      "data_type": "UInt16",
      "units": "kWh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300003."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Power input",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300004."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Operation time",
      "data_type": "UInt16",
      "units": "h",
      "scale_factor": 10,
      "offset": 0,
      "access": "R",
      "description": "Register 300005, scope 'master pump'."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Speed",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300007, scope 'master pump'."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Control function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300010, WORD; the active control function value (see the holding register 'Control Function' for the value list)."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Speed max-pres-value",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300018, speed at the maximum pressure value."
    },
    {
      "address": 19,
      "count": 1,
      "name": "Speed min-pres-value",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300019, speed at the minimum pressure value."
    },
    {
      "address": 24,
      "count": 1,
      "name": "Flow (calculated) max-pres-value",
      "data_type": "UInt16",
      "units": "m3/h",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 300024."
    },
    {
      "address": 25,
      "count": 1,
      "name": "Flow (calculated) min-pres-value",
      "data_type": "UInt16",
      "units": "m3/h",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Register 300025."
    },
    {
      "address": 200,
      "count": 1,
      "name": "Duty point (relative)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "R",
      "description": "Register 300200. Range -32768...32766, 32767 = error value."
    },
    {
      "address": 202,
      "count": 1,
      "name": "Duty point (relative) maximum output",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "R",
      "description": "Register 300202."
    },
    {
      "address": 204,
      "count": 1,
      "name": "Duty point (relative) minimum output",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "R",
      "description": "Register 300204."
    },
    {
      "address": 206,
      "count": 2,
      "name": "Duty point 100 % value",
      "data_type": "Float32",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300206, REAL (2 registers): the relative duty point that corresponds to 100 %."
    },
    {
      "address": 208,
      "count": 1,
      "name": "Duty point (relative) units",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300208, unit code of the relative duty point."
    },
    {
      "address": 400,
      "count": 1,
      "name": "Duty point (relative)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "R",
      "description": "Register 300400, the duty point actually applied by the pump system."
    },
    {
      "address": 404,
      "count": 1,
      "name": "Operation status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300404, WORD bit field; the trouble-reporting chapter lists its bits in the 'Reg 404 - Reg 940 Status' table together with the warning/error codes."
    },
    {
      "address": 700,
      "count": 1,
      "name": "Application version",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Register 300700, WORD application version."
    }
  ],
  "holding_registers": [
    {
      "address": 1,
      "count": 1,
      "name": "Duty point (relative)",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "RW",
      "description": "Register 400002, the relative duty point set-point. Range -32768...32766, 32767 = error value."
    },
    {
      "address": 40,
      "count": 1,
      "name": "Pump command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400041, WORD. Switches the pump ON (1) or OFF (0)."
    },
    {
      "address": 42,
      "count": 1,
      "name": "Control function",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400043, WORD. Selects the regulation mode; the document lists the values starting at 1 = n-const."
    },
    {
      "address": 400,
      "count": 1,
      "name": "Bus command timer timeout",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400401. Range 20-65534, 65535 = error value. Companion of the input register 'Bus Command Timer Time remain.'."
    },
    {
      "address": 402,
      "count": 1,
      "name": "Duty point (relative) preset",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.5,
      "offset": 0,
      "access": "RW",
      "description": "Register 400403, readback value of the relative duty point."
    },
    {
      "address": 403,
      "count": 1,
      "name": "Control function preset",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Register 400404, WORD. Range 0-140."
    }
  ],
  "combined_registers": [],
  "notes": "Source: Wilo 'Technical guide - MODBUS', version V01.01 (18/06/2024, rev. V01.01 13/02/2025), chapters 'Holding register data model', 'Input register data model' (1/2 and 2/2) and 'Modbus pump control' - vendor-hosted at wilo.com (SHA-256 92b7801d0721b7f79b3e69133e02b0f3567db1005c07e9f2a835ec2a71ee509f). Factory frame from the guide's own defaults box and addressing chapter: 19200 baud, 8 data bits, even parity, 1 stop bit, slave address 101. Addressing: the guide states 'Unlike the Modbus Standard, Wilo register numbers start from zero. So, the starting address is equal to the register number', so the seed stores the integers from the guide's 'Wilo Register' column and declares zero_based; its 'Register' column is the same number written as a 1-based 4xxxx/3xxxx reference (Wilo register 1 = 400002/300001) which the schema's 0-65535 address field cannot hold. Scale 0.5 is the guide's '0,5' in the Scale column for every relative duty-point row. Omitted on purpose: every row the guide types BYTE, USINT or UDINT (Pump Command active/preset, Bus Command Timer, interface device identifier, transmission serial speed and transmission serial frame, heartbeat count, bus-command-timer remaining time, warning/error message, parameter block acknowledge) because this schema has no 8-bit type and the guide states no word order or register width for its 32-bit values; the same reason leaves out Vendor ID (DWORD). Documents that extend the same map for other Wilo ranges are not covered by this seed."
}