Systemair · HVAC controller
SAVE VTC / VSR residential ventilation units (SAVECair control) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- None
- Data bits
- 8
- Stop bits
- 2
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 1001 | 1 | DEMC RH HIGHEST Symbol REG_DEMC_RH_HIGHEST. Documented range 0 100. Highest value of all RH sensors | UInt16 | - | 1 | R |
| 1002 | 1 | DEMC CO2 HIGHEST Symbol REG_DEMC_CO2_HIGHEST. Documented range 0 2000. Highest value of all CO2 sensors | UInt16 | - | 1 | R |
| 1011 | 1 | DEMC RH PI SP Symbol REG_DEMC_RH_PI_SP. Documented range 0 100. Set point for RH demand control | UInt16 | - | 1 | R |
| 1012 | 1 | DEMC RH PI FEEDBACK Symbol REG_DEMC_RH_PI_FEEDBACK. Documented range 0 100. Sensor value for RH demand control | UInt16 | - | 1 | R |
| 1019 | 1 | DEMC RH PI OUTPUT Symbol REG_DEMC_RH_PI_OUTPUT. Output value for RH demand control.(1): | UInt16 | - | 1 | R |
| 1021 | 1 | DEMC CO2 PI SP Symbol REG_DEMC_CO2_PI_SP. Documented range 0 2000. Set point for CO2 demand control | UInt16 | - | 1 | R |
| 1022 | 1 | DEMC CO2 PI FEEDBACK Symbol REG_DEMC_CO2_PI_FEEDBACK. Documented range 0 2000. Sensor value for CO2 demand control | UInt16 | - | 1 | R |
| 1029 | 1 | DEMC CO2 PI OUTPUT Symbol REG_DEMC_CO2_PI_OUTPUT. Output value for CO2 demand control | UInt16 | - | 1 | R |
| 1039 | 1 | SUMMER WINTER Symbol REG_SUMMER_WINTER. Documented range 0 1. Actual seasson for Demand Control | UInt16 | - | 1 | R |
| 1111 | 1 | USERMODE REMAINING TIME L Symbol REG_USERMODE_REMAINING_TIME_L. Remaining time for the state Holiday/ | UInt16 | - | 1 | R |
| 1112 | 1 | USERMODE REMAINING TIME H Symbol REG_USERMODE_REMAINING_TIME_H. Remaining time for the state Holiday/ | UInt16 | - | 1 | R |
| 1123 | 1 | IAQ LEVEL Symbol REG_IAQ_LEVEL. Documented range 0 2. Actual IAQ level: | UInt16 | - | 1 | R |
| 1161 | 1 | USERMODE MODE Symbol REG_USERMODE_MODE. Documented range 0 12. Active User mode. | UInt16 | - | 1 | R |
| 1221 | 1 | SPEED CDI1 SAF Symbol REG_SPEED_CDI1_SAF. SAF speed value for user mode Holiday.(1): | UInt16 | - | 1 | R |
| 1222 | 1 | SPEED CDI1 EAF Symbol REG_SPEED_CDI1_EAF. EAF speed value for user mode Holiday.(1): | UInt16 | - | 1 | R |
| 1223 | 1 | SPEED CDI2 SAF Symbol REG_SPEED_CDI2_SAF. SAF speed value for mode Cooker Hood.(1): | UInt16 | - | 1 | R |
| 1224 | 1 | SPEED CDI2 EAF Symbol REG_SPEED_CDI2_EAF. EAF speed value for mode Cooker Hood.(1): | UInt16 | - | 1 | R |
| 1225 | 1 | SPEED CDI3 SAF Symbol REG_SPEED_CDI3_SAF. SAF speed value for mode Vacuum Cleaner. | UInt16 | - | 1 | R |
| 1226 | 1 | SPEED CDI3 EAF Symbol REG_SPEED_CDI3_EAF. EAF speed value for mode Vacuum Cleaner. | UInt16 | - | 1 | R |
| 1227 | 1 | SPEED PRESSURE GUARD SAF Symbol REG_SPEED_PRESSURE_GUARD_SAF. SAF speed value for low fan speed.(1): | UInt16 | - | 1 | R |
| 1228 | 1 | SPEED PRESSURE GUARD EAF Symbol REG_SPEED_PRESSURE_GUARD_EAF. EAF speed value for low fan speed.(1): | UInt16 | - | 1 | R |
| 1301 | 1 | FAN LEVEL SAF MIN Symbol REG_FAN_LEVEL_SAF_MIN. SAF speed value for minimum fan speed. | UInt16 | - | 1 | R |
| 1302 | 1 | FAN LEVEL EAF MIN Symbol REG_FAN_LEVEL_EAF_MIN. EAF speed value for minimum fan speed. | UInt16 | - | 1 | R |
| 1303 | 1 | FAN LEVEL SAF LOW Symbol REG_FAN_LEVEL_SAF_LOW. SAF speed value for low fan speed. | UInt16 | - | 1 | R |
| 1304 | 1 | FAN LEVEL EAF LOW Symbol REG_FAN_LEVEL_EAF_LOW. EAF speed value for low fan speed. | UInt16 | - | 1 | R |
| 1305 | 1 | FAN LEVEL SAF NORMAL Symbol REG_FAN_LEVEL_SAF_NORMAL. SAF speed value for normal fan speed. | UInt16 | - | 1 | R |
| 1306 | 1 | FAN LEVEL EAF NORMAL Symbol REG_FAN_LEVEL_EAF_NORMAL. EAF speed value for normal fan speed. | UInt16 | - | 1 | R |
| 1307 | 1 | FAN LEVEL SAF HIGH Symbol REG_FAN_LEVEL_SAF_HIGH. SAF speed value for high fan speed. | UInt16 | - | 1 | R |
| 1308 | 1 | FAN LEVEL EAF HIGH Symbol REG_FAN_LEVEL_EAF_HIGH. EAF speed value for high fan speed. | UInt16 | - | 1 | R |
| 1309 | 1 | FAN LEVEL SAF MAX Symbol REG_FAN_LEVEL_SAF_MAX. SAF speed value for maximum fan speed. | UInt16 | - | 1 | R |
| 1310 | 1 | FAN LEVEL EAF MAX Symbol REG_FAN_LEVEL_EAF_MAX. EAF speed value for maximum fan speed. | UInt16 | - | 1 | R |
| 1351 | 1 | SPEED FANS RUNNING Symbol REG_SPEED_FANS_RUNNING. Documented range 0 1. Indicates that both fans are running | UInt16 | - | 1 | R |
| 1352 | 1 | SPEED SAF DESIRED OFF Symbol REG_SPEED_SAF_DESIRED_OFF. Documented range 0 1. Indicates that the SAF shall be turned off | UInt16 | - | 1 | R |
| 1357 | 1 | SPEED ELECTRICAL HEATER HOT Symbol REG_SPEED_ELECTRICAL_HEATER_HOT_. Electrical Heater hot counter. Count down | UInt16 | - | 1 | R |
| 1358 | 1 | FAN SPEED AFTER HEATER Symbol REG_FAN_SPEED_AFTER_HEATER_. Documented range 0 100. Supply Air Fan Speed Level After Heater | UInt16 | - | 1 | R |
| 1359 | 1 | FAN SPEED AFTER HEATER Symbol REG_FAN_SPEED_AFTER_HEATER_. Documented range 0 100. Extract Air Fan Speed Level After Heater | UInt16 | - | 1 | R |
| 1621 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. Remaining time | UInt16 | - | 1 | R |
| 1622 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. | UInt16 | - | 1 | R |
| 1623 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. Remaining time | UInt16 | - | 1 | R |
| 1624 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. | UInt16 | - | 1 | R |
| 1625 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. Remaining time | UInt16 | - | 1 | R |
| 1626 | 1 | USERMODE REMAINING TIME Symbol REG_USERMODE_REMAINING_TIME_. | UInt16 | - | 1 | R |
| 2051 | 1 | TC EAT RAT SP Symbol REG_TC_EAT_RAT_SP. Documented range 120 400. EAT or RAT value, used for room/extract air | Int16 | - | 1 | R |
| 2053 | 1 | TC ROOM CTRL SP SATC Symbol REG_TC_ROOM_CTRL_SP_SATC. Documented range 120 400. Temperature set point for SATC, as | Int16 | - | 1 | R |
| 2054 | 1 | TC SP SATC Symbol REG_TC_SP_SATC. Documented range 120 300. Temperature setpoint for the supply air | Int16 | - | 1 | R |
| 2055 | 1 | SATC HEAT DEMAND Symbol REG_SATC_HEAT_DEMAND. Documented range 0 100. Output of the SATC (0-100%) | UInt16 | - | 1 | R |
| 2061 | 1 | SATC PI SP Symbol REG_SATC_PI_SP. Documented range 120 300. SATC setpoint value | Int16 | - | 1 | R |
| 2069 | 1 | SATC PI OUTPUT Symbol REG_SATC_PI_OUTPUT. Documented range 0 100. SATC output signal | Int16 | - | 1 | R |
| 2071 | 1 | ROOM CTRL PI SP Symbol REG_ROOM_CTRL_PI_SP. Documented range 120 300. RATC setpoint value | Int16 | - | 1 | R |
| 2079 | 1 | ROOM CTRL PI OUTPUT Symbol REG_ROOM_CTRL_PI_OUTPUT. Documented range 0 100. RATC output signal | Int16 | - | 1 | R |
| 2101 | 1 | INPUT EXTERNAL CTRL SAF Symbol REG_INPUT_EXTERNAL_CTRL_SAF. Documented range 0 100. Value from External Controller Input, SAF. In | UInt16 | - | 1 | R |
| 2102 | 1 | INPUT EXTERNAL CTRL EAF Symbol REG_INPUT_EXTERNAL_CTRL_EAF. Documented range 0 100. Value from External Controller Input, EAF. In | UInt16 | - | 1 | R |
| 2147 | 1 | HEAT EXCHANGER RH Symbol REG_HEAT_EXCHANGER_RH_. Indicates if RH trasnfer control shall be | UInt16 | - | 1 | R |
| 2149 | 1 | PWM TRIAC OUTPUT Symbol REG_PWM_TRIAC_OUTPUT. Documented range 0 100. TRIAC after manual override | UInt16 | - | 1 | R |
| 2311 | 1 | COOLER FROM SATC Symbol REG_COOLER_FROM_SATC. Documented range 0 100. Cooler signal | UInt16 | - | 1 | R |
| 2506 | 1 | ECO FUNCTION ACTIVE Symbol REG_ECO_FUNCTION_ACTIVE. Documented range 0 1. Indicates if conditions for ECO mode are | UInt16 | - | 1 | R |
| 3113 | 1 | FUNCTION ACTIVE HEATER COOL Symbol REG_FUNCTION_ACTIVE_HEATER_COOL_. Documented range 0 1. Active Heater Cool Down | UInt16 | - | 1 | R |
| 3114 | 1 | FUNCTION ACTIVE PRESSURE Symbol REG_FUNCTION_ACTIVE_PRESSURE_. Documented range 0 1. Indicates if function is active | UInt16 | - | 1 | R |
| 3115 | 1 | FUNCTION ACTIVE CDI 1 Symbol REG_FUNCTION_ACTIVE_CDI_1. Documented range 0 1. Indicates if function is active | UInt16 | - | 1 | R |
| 3116 | 1 | FUNCTION ACTIVE CDI 2 Symbol REG_FUNCTION_ACTIVE_CDI_2. Documented range 0 1. Indicates if function is active | UInt16 | - | 1 | R |
| 3117 | 1 | FUNCTION ACTIVE CDI 3 Symbol REG_FUNCTION_ACTIVE_CDI_3. Documented range 0 1. Indicates if function is active | UInt16 | - | 1 | R |
| 4111 | 1 | FREE COOLING ACTIVE Symbol REG_FREE_COOLING_ACTIVE. Documented range 0 1. Indicates if free cooling is being performed | UInt16 | - | 1 | R |
| 5059 | 1 | WS ACTIVE Symbol REG_WS_ACTIVE. Documented range 0 1. Indicates that the current time lays within | UInt16 | - | 1 | R |
| 6009 | 1 | DAY OF THE WEEK Symbol REG_DAY_OF_THE_WEEK. Documented range 0 6. Monday (0)...Sunday (6) | UInt16 | - | 1 | R |
| 6010 | 1 | DST PERIOD ACTIVE Symbol REG_DST_PERIOD_ACTIVE. Documented range 0 1. | UInt16 | - | 1 | R |
| 6011 | 1 | TIME RTC SECONDS L Symbol REG_TIME_RTC_SECONDS_L. Now time in seconds. Lower 16 bits. | UInt16 | - | 1 | R |
| 6012 | 1 | TIME RTC SECONDS H Symbol REG_TIME_RTC_SECONDS_H. Now time in seconds. Higher 16 bits. | UInt16 | - | 1 | R |
| 6021 | 1 | SYSTEM START UP TIME L Symbol REG_SYSTEM_START_UP_TIME_L. | UInt16 | - | 1 | R |
| 6022 | 1 | SYSTEM START UP TIME H Symbol REG_SYSTEM_START_UP_TIME_H. | UInt16 | - | 1 | R |
| 6101 | 1 | TIME RTC Symbol REG_TIME_RTC. RTC value in seconds, highest 16 bits | UInt16 | - | 1 | R |
| 7004 | 1 | FILTER PERIOD SET Symbol REG_FILTER_PERIOD_SET. Indicates that the | UInt16 | - | 1 | R |
| 7005 | 1 | FILTER REMAINING TIME L Symbol REG_FILTER_REMAINING_TIME_L. Remaining filter time in seconds, lower 16 | UInt16 | - | 1 | R |
| 7006 | 1 | FILTER REMAINING TIME H Symbol REG_FILTER_REMAINING_TIME_H. Remaining filter time in seconds, higher 16 | UInt16 | - | 1 | R |
| 7007 | 1 | FILTER ALARM WAS DETECTED Symbol REG_FILTER_ALARM_WAS_DETECTED. Indicates if the filter warning alarm was | UInt16 | - | 1 | R |
| 12016 | 1 | INPUT ANALOG UI 6 Symbol REG_INPUT_ANALOG_UI_6. mV | UInt16 | - | 1 | R |
| 12026 | 1 | INPUT DIGITAL UI 6 Symbol REG_INPUT_DIGITAL_UI_6. State of UI6 | UInt16 | - | 1 | R |
| 12031 | 1 | INPUT DIGITAL DI 1 Symbol REG_INPUT_DIGITAL_DI_1. Documented range 0 1. Boolean | UInt16 | - | 1 | R |
| 12032 | 1 | INPUT DIGITAL DI 2 Symbol REG_INPUT_DIGITAL_DI_2. Documented range 0 1. Boolean | UInt16 | - | 1 | R |
| 12112 | 1 | SENSOR RGS Symbol REG_SENSOR_RGS. Documented range 0 1. Rotating guard Sensor input | UInt16 | - | 1 | R |
| 12156 | 1 | SENSOR CO2S 6 Symbol REG_SENSOR_CO2S_6. CO2 sensor value - UI6 (accessory) | UInt16 | - | 1 | R |
| 12166 | 1 | SENSOR RHS 6 Symbol REG_SENSOR_RHS_6. Documented range 0 100. RH sensor value - UI6 (accessory) | UInt16 | - | 1 | R |
| 12301 | 1 | SENSOR DI AWAY Symbol REG_SENSOR_DI_AWAY. Documented range 0 1. Value of physical Digital Input of Away | UInt16 | - | 1 | R |
| 12302 | 1 | SENSOR DI HOLIDAY Symbol REG_SENSOR_DI_HOLIDAY. Documented range 0 1. Value of physical Digital Input of Holiday | UInt16 | - | 1 | R |
| 12303 | 1 | SENSOR DI FIREPLACE Symbol REG_SENSOR_DI_FIREPLACE. Documented range 0 1. Value of physical Digital Input of Fireplace | UInt16 | - | 1 | R |
| 12304 | 1 | SENSOR DI REHRESH Symbol REG_SENSOR_DI_REHRESH. Documented range 0 1. Value of physical Digital Input of Refresh | UInt16 | - | 1 | R |
| 12305 | 1 | SENSOR DI CROWDED Symbol REG_SENSOR_DI_CROWDED. Documented range 0 1. Value of physical Digital Input of Crowded | UInt16 | - | 1 | R |
| 12306 | 1 | SENSOR DI COOKERHOOD Symbol REG_SENSOR_DI_COOKERHOOD. Documented range 0 1. Value of physical Digital Input of | UInt16 | - | 1 | R |
| 12307 | 1 | SENSOR DI VACUUMCLEANER Symbol REG_SENSOR_DI_VACUUMCLEANER. Documented range 0 1. Value of physical Digital Input of Vacuum | UInt16 | - | 1 | R |
| 12308 | 1 | SENSOR DI EXTERNAL STOP Symbol REG_SENSOR_DI_EXTERNAL_STOP. Documented range 0 1. External Stop input value | UInt16 | - | 1 | R |
| 12309 | 1 | SENSOR DI LOAD DETECTED Symbol REG_SENSOR_DI_LOAD_DETECTED. Documented range 0 1. Load Detected input value | UInt16 | - | 1 | R |
| 12310 | 1 | SENSOR DI EXTRA CONTROLLER Symbol REG_SENSOR_DI_EXTRA_CONTROLLER_. Documented range 0 1. Extra controller EMT input value | UInt16 | - | 1 | R |
| 12311 | 1 | SENSOR DI FIRE ALARM Symbol REG_SENSOR_DI_FIRE_ALARM. Documented range 0 1. Fire Alarm input value | UInt16 | - | 1 | R |
| 12312 | 1 | SENSOR DI CHANGE OVER Symbol REG_SENSOR_DI_CHANGE_OVER_. Documented range 0 1. Change over feedback value | UInt16 | - | 1 | R |
| 12316 | 1 | SENSOR DI PRESSURE GUARD Symbol REG_SENSOR_DI_PRESSURE_GUARD. Documented range 0 1. Indicates if physical DI is active | UInt16 | - | 1 | R |
| 12317 | 1 | SENSOR DI CDI 1 Symbol REG_SENSOR_DI_CDI_1. Documented range 0 1. Indicates if physical DI is active | UInt16 | - | 1 | R |
| 12318 | 1 | SENSOR DI CDI 2 Symbol REG_SENSOR_DI_CDI_2. Documented range 0 1. Indicates if physical DI is active | UInt16 | - | 1 | R |
| 12319 | 1 | SENSOR DI CDI 3 Symbol REG_SENSOR_DI_CDI_3. Documented range 0 1. Indicates if physical DI is active | UInt16 | - | 1 | R |
| 12401 | 1 | SENSOR RPM SAF Symbol REG_SENSOR_RPM_SAF. Documented range 0 5000. Supply Air Fan RPM indication from TACHO | UInt16 | - | 1 | R |
| 12402 | 1 | SENSOR RPM EAF Symbol REG_SENSOR_RPM_EAF. Documented range 0 5000. Extract Air Fan RPM indication from TACHO | UInt16 | - | 1 | R |
| 12403 | 1 | SENSOR FLOW PIGGYBACK SAF Symbol REG_SENSOR_FLOW_PIGGYBACK_SAF. Flow value calculated from piggyback | UInt16 | - | 1 | R |
| 12404 | 1 | SENSOR FLOW PIGGYBACK EAF Symbol REG_SENSOR_FLOW_PIGGYBACK_EAF. Flow value calculated from piggyback | UInt16 | - | 1 | R |
| 12405 | 1 | SENSOR DI BYF Symbol REG_SENSOR_DI_BYF. Value from Bypass Damper Feedback input. | UInt16 | - | 1 | R |
| 13301 | 1 | DO1 AFTER MUX Symbol REG_DO1_AFTER_MUX. Documented range 0 1. Digital output after multiplexer | UInt16 | - | 1 | R |
| 13302 | 1 | DO2 AFTER MUX Symbol REG_DO2_AFTER_MUX. Documented range 0 1. Digital output after multiplexer | UInt16 | - | 1 | R |
| 13303 | 1 | DO3 AFTER MUX Symbol REG_DO3_AFTER_MUX. Documented range 0 1. Digital output after multiplexer | UInt16 | - | 1 | R |
| 13304 | 1 | DO4 AFTER MUX Symbol REG_DO4_AFTER_MUX. Documented range 0 1. Digital output after multiplexer | UInt16 | - | 1 | R |
| 13311 | 1 | AO1 AFTER MUX Symbol REG_AO1_AFTER_MUX. Documented range 0 100. Analog output after multiplexer | UInt16 | - | 1 | R |
| 13312 | 1 | AO2 AFTER MUX Symbol REG_AO2_AFTER_MUX. Documented range 0 100. Analog output after multiplexer | UInt16 | - | 1 | R |
| 13313 | 1 | AO3 AFTER MUX Symbol REG_AO3_AFTER_MUX. Documented range 0 100. Analog output after multiplexer | UInt16 | - | 1 | R |
| 13314 | 1 | AO4 AFTER MUX Symbol REG_AO4_AFTER_MUX. Documented range 0 100. Analog output after multiplexer | UInt16 | - | 1 | R |
| 13315 | 1 | AO5 AFTER MUX Symbol REG_AO5_AFTER_MUX. Documented range 0 100. Analog output after multiplexer | UInt16 | - | 1 | R |
| 14001 | 1 | OUTPUT SAF Symbol REG_OUTPUT_SAF. Documented range 0 100. SAF fan speed | UInt16 | - | 1 | R |
| 14002 | 1 | OUTPUT EAF Symbol REG_OUTPUT_EAF. Documented range 0 100. EAF fan speed | UInt16 | - | 1 | R |
| 14003 | 1 | OUTPUT ALARM Symbol REG_OUTPUT_ALARM. Documented range 0 1. Sum Alarm DO | UInt16 | - | 1 | R |
| 14004 | 1 | OUTPUT OUTDOOR EXTRACT Symbol REG_OUTPUT_OUTDOOR_EXTRACT_. Documented range 0 1. Indicates if Outdoor/Exhaust air damper | UInt16 | - | 1 | R |
| 14101 | 1 | OUTPUT Y1 ANALOG Symbol REG_OUTPUT_Y1_ANALOG. Documented range 0 100. Heater AO state. | UInt16 | - | 1 | R |
| 14102 | 1 | OUTPUT Y1 DIGITAL Symbol REG_OUTPUT_Y1_DIGITAL. Documented range 0 1. Heater DO state: | UInt16 | - | 1 | R |
| 14103 | 1 | OUTPUT Y2 ANALOG Symbol REG_OUTPUT_Y2_ANALOG. Documented range 0 100. Heat Exchanger AO state. | UInt16 | - | 1 | R |
| 14104 | 1 | OUTPUT Y2 DIGITAL Symbol REG_OUTPUT_Y2_DIGITAL. Documented range 0 1. Heat Exchanger DO state.0: Output not | UInt16 | - | 1 | R |
| 14201 | 1 | OUTPUT Y3 ANALOG Symbol REG_OUTPUT_Y3_ANALOG. Documented range 0 100. Cooler AO state. | UInt16 | - | 1 | R |
| 14202 | 1 | OUTPUT Y3 DIGITAL Symbol REG_OUTPUT_Y3_DIGITAL. Documented range 0 1. Cooler DO state: | UInt16 | - | 1 | R |
| 14203 | 1 | OUTPUT Y4 ANALOG Symbol REG_OUTPUT_Y4_ANALOG. Documented range 0 100. Extra controller AO state. | UInt16 | - | 1 | R |
| 14204 | 1 | OUTPUT Y4 DIGITAL Symbol REG_OUTPUT_Y4_DIGITAL. Documented range 0 1. Extra controller DO state: | UInt16 | - | 1 | R |
| 14301 | 1 | OUTPUT Y1 CIRC PUMP Symbol REG_OUTPUT_Y1_CIRC_PUMP. Heating circulation pump output | UInt16 | - | 1 | R |
| 14302 | 1 | OUTPUT Y3 CIRC PUMP Symbol REG_OUTPUT_Y3_CIRC_PUMP. Cooler circulation pump output | UInt16 | - | 1 | R |
| 14303 | 1 | OUTPUT Y1 Y3 CIRC PUMP Symbol REG_OUTPUT_Y1_Y3_CIRC_PUMP. Change-over circulation pump output | UInt16 | - | 1 | R |
| 14304 | 1 | OUTPUT Y4 CIRC PUMP Symbol REG_OUTPUT_Y4_CIRC_PUMP. Extra controller circulation pump output | UInt16 | - | 1 | R |
| 14351 | 1 | OUTPUT AO1 Symbol REG_OUTPUT_AO1. Voltage signal from AO1 | UInt16 | - | 1 | R |
| 14352 | 1 | OUTPUT AO2 Symbol REG_OUTPUT_AO2. Voltage signal from AO2 | UInt16 | - | 1 | R |
| 14353 | 1 | OUTPUT AO3 Symbol REG_OUTPUT_AO3. Voltage signal from AO3 | UInt16 | - | 1 | R |
| 14354 | 1 | OUTPUT AO4 Symbol REG_OUTPUT_AO4. Voltage signal from AO4 | UInt16 | - | 1 | R |
| 14355 | 1 | OUTPUT AO5 Symbol REG_OUTPUT_AO5. Voltage signal from AO5 | UInt16 | - | 1 | R |
| 14361 | 1 | OUTPUT DO1 Symbol REG_OUTPUT_DO1. Documented range 0 1. State of DO1 | UInt16 | - | 1 | R |
| 14362 | 1 | OUTPUT DO2 Symbol REG_OUTPUT_DO2. Documented range 0 1. State of DO2 | UInt16 | - | 1 | R |
| 14363 | 1 | OUTPUT DO3 Symbol REG_OUTPUT_DO3. Documented range 0 1. State of DO3 | UInt16 | - | 1 | R |
| 14364 | 1 | OUTPUT DO4 Symbol REG_OUTPUT_DO4. Documented range 0 1. State of DO4 | UInt16 | - | 1 | R |
| 14371 | 1 | OUTPUT FAN SPEED1 Symbol REG_OUTPUT_FAN_SPEED1. Documented range 0 100. Supply air fan control signal in % | UInt16 | - | 1 | R |
| 14372 | 1 | OUTPUT FAN SPEED2 Symbol REG_OUTPUT_FAN_SPEED2. Documented range 0 100. Extract air fan control signal in % | UInt16 | - | 1 | R |
| 14381 | 1 | OUTPUT TRIAC Symbol REG_OUTPUT_TRIAC. Documented range 0 1. TRIAC control signal | UInt16 | - | 1 | R |
| 15002 | 1 | ALARM SAF CTRL ALARM Symbol REG_ALARM_SAF_CTRL_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15009 | 1 | ALARM EAF CTRL ALARM Symbol REG_ALARM_EAF_CTRL_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15016 | 1 | ALARM FROST PROT ALARM Symbol REG_ALARM_FROST_PROT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15023 | 1 | ALARM DEFROSTING ALARM Symbol REG_ALARM_DEFROSTING_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15030 | 1 | ALARM SAF RPM ALARM Symbol REG_ALARM_SAF_RPM_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15037 | 1 | ALARM EAF RPM ALARM Symbol REG_ALARM_EAF_RPM_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15058 | 1 | ALARM FPT ALARM Symbol REG_ALARM_FPT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15065 | 1 | ALARM OAT ALARM Symbol REG_ALARM_OAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15072 | 1 | ALARM SAT ALARM Symbol REG_ALARM_SAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15079 | 1 | ALARM RAT ALARM Symbol REG_ALARM_RAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15086 | 1 | ALARM EAT ALARM Symbol REG_ALARM_EAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15093 | 1 | ALARM ECT ALARM Symbol REG_ALARM_ECT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15100 | 1 | ALARM EFT ALARM Symbol REG_ALARM_EFT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15107 | 1 | ALARM OHT ALARM Symbol REG_ALARM_OHT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15114 | 1 | ALARM EMT ALARM Symbol REG_ALARM_EMT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15121 | 1 | ALARM RGS ALARM Symbol REG_ALARM_RGS_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15128 | 1 | ALARM BYS ALARM Symbol REG_ALARM_BYS_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15135 | 1 | ALARM SECONDARY AIR ALARM Symbol REG_ALARM_SECONDARY_AIR_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15142 | 1 | ALARM FILTER ALARM Symbol REG_ALARM_FILTER_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15149 | 1 | ALARM EXTRA CONTROLLER Symbol REG_ALARM_EXTRA_CONTROLLER_. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15156 | 1 | ALARM EXTERNAL STOP ALARM Symbol REG_ALARM_EXTERNAL_STOP_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15163 | 1 | ALARM RH ALARM Symbol REG_ALARM_RH_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15170 | 1 | ALARM CO2 ALARM Symbol REG_ALARM_CO2_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15177 | 1 | ALARM LOW SAT ALARM Symbol REG_ALARM_LOW_SAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15184 | 1 | ALARM BYF ALARM Symbol REG_ALARM_BYF_ALARM. Alarm active/inactive | UInt16 | - | 1 | R |
| 15502 | 1 | ALARM MANUAL OVERRIDE Symbol REG_ALARM_MANUAL_OVERRIDE_. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15509 | 1 | ALARM PDM RHS ALARM Symbol REG_ALARM_PDM_RHS_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15516 | 1 | ALARM PDM EAT ALARM Symbol REG_ALARM_PDM_EAT_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15523 | 1 | ALARM MANUAL FAN STOP Symbol REG_ALARM_MANUAL_FAN_STOP_. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15530 | 1 | ALARM OVERHEAT Symbol REG_ALARM_OVERHEAT_. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15537 | 1 | ALARM FIRE ALARM ALARM Symbol REG_ALARM_FIRE_ALARM_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15544 | 1 | ALARM FILTER WARNING ALARM Symbol REG_ALARM_FILTER_WARNING_ALARM. Documented range 0 3. Alarm active/inactive. | UInt16 | - | 1 | R |
| 15549 | 1 | ALARM FILTER WARNING Symbol REG_ALARM_FILTER_WARNING_. Counter for delay | UInt16 | - | 1 | R |
| 15901 | 1 | ALARM TYPE A Symbol REG_ALARM_TYPE_A. Documented range 0 1. Indicates if an alarm Type A is active | UInt16 | - | 1 | R |
| 15902 | 1 | ALARM TYPE B Symbol REG_ALARM_TYPE_B. Documented range 0 1. Indicates if an alarm Type B is active | UInt16 | - | 1 | R |
| 15903 | 1 | ALARM TYPE C Symbol REG_ALARM_TYPE_C. Documented range 0 1. Indicates if an alarm Type C is active | UInt16 | - | 1 | R |
| 16062 | 1 | PASSWD PC UNLOCKED Symbol REG_PASSWD_PC_UNLOCKED. Documented range 0 1. | UInt16 | - | 1 | R |
| 30105 | 1 | USER SAFE CONFIG VALID Symbol REG_USER_SAFE_CONFIG_VALID. | UInt16 | - | 1 | R |
| 30106 | 1 | SAFE CONFIG VALID Symbol REG_SAFE_CONFIG_VALID. | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Systemair "Modbus Variable List", release 20210301, Revision 36 (document 2.1, Systemair UAB); copy read: taphome.com/compatibility/devices/systemair-save-vtr-700/manufacturer/SAVE_MODBUS_VARIABLE_LIST_REV36.pdf, SHA-256 2027abe561f2b53ab3a6b0268d3b6b0bb397cdde9ad587cf4a086ebd6dd90c1b. The SAVE VTC/VSR units speak Modbus RTU on the connection board's RS-485 terminals and also offer Modbus/TCP through the Internet Access Module; this seed describes the RS-485 interface. Factory frame: the SAVE VTC 300 installation and service manual (211464 | A001, 6.7.6.6 "Communication") prints "Set Modbus address. Default setting is 1", "Set baud rate. Default setting is 19200", "Set parity. Default setting is None" and "Set stop bits. Default setting is 2. Range: 1-2" - 19200 8N2 at unit 1. The variable list contradicts the stop bits in 1.1 ("Stop bits: 1 (fixed)"); the manual is followed because it documents the controller's menu, states the default explicitly and gives 1-2 as a selectable range, so the field is not fixed. Neither document prints the number of data bits; 8 is the RTU framing both assume. Register numbers are the list's Modbus Adr. column, which restarts at 1001 in each area; no address base is stated, so zero_based is the declared convention. Input registers use FC 04 and holding registers FC 03/06/16, as the register-type column states, and 1.2 says all registers are 16-bit integers. Table 1 marks signed values I* (33 rows, stored Int16) and unsigned values I (UInt16). The list prints no unit and no scale statement anywhere, so every row carries scale 1 and no unit and each description quotes the printed raw range; several temperature rows are plainly in tenths (an offset printed -300...0), but nothing is applied the document does not state. Two addresses are printed twice in their area (holding 4101, input 12112) and the first definition is kept; symbols that wrap onto a second printed line are stored truncated, with the row name in the description.