Air handling units with S21 automation (CIVIC EC LB and other S21 units) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
115200
Parity
None
Data bits
8
Stop bits
2

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Unit on/off
CL_POWER. 0 = off, 1 = on.
UInt16-1RW
11
Main timer
CL_TIMER. 0 = off, 1 = on.
UInt16-1RW
21
Weekly schedule
L_WEEK. 0 = off, 1 = on.
UInt16-1RW
31
Boost mode
CL_Boost_MODE. Read-only status.
UInt16-1R
41
Fireplace mode
L_FPLC_MODE. Read-only status.
UInt16-1R
51
Main humidity sensor activation
CL_IntRH_CTRL.
UInt16-1RW
61
External humidity sensor activation
CL_ExtRH_CTRL.
UInt16-1RW
71
Main CO2 sensor activation
CL_IntCO2_CTRL.
UInt16-1RW
81
External CO2 sensor activation
CL_ExtCO2_CTRL.
UInt16-1RW
91
Main PM2.5 sensor activation
CL_IntPM2_5_CTRL.
UInt16-1RW
111
Main VOC sensor activation
CL_IntVOC_CTRL.
UInt16-1RW
151
Fire alarm sensor activation
CL_FireALARM_CTRL.
UInt16-1RW
161
External 0-10 V control input activation
CL_10V_SENSOR_CTRL.
UInt16-1RW
171
Reset filter timer
CL_RESET_FILTER_TIMER. Write 1 to reset the filter countdown; reads back as 0.
UInt16-1RW
181
Reset all alarms
CL_RESET_ALARM. Write 1 to reset all alarms; reads back as 0.
UInt16-1RW
191
Restore everything to factory settings
CL_RESTORE_FACTORY. Write 1 to restore the factory settings; the Pre-set column of the document's tables lists the values restored.
UInt16-1RW
211
Minimum room supply air temperature control
CL_MinSuAirOutTEMP_CTRL.
UInt16-1RW
221
Heat medium water pressure sensor activation
CL_WaterPRESS_CTRL.
UInt16-1RW
231
Heat medium water flow sensor activation
CL_WaterFLOW_CTRL.
UInt16-1RW
251
Automatic air flow reduction if the main heater fails
L_AutoReductionAirFlow.
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Blauberg "Modbus table for connecting S21 automation to BMS" (no revision printed; copy read: blauberg-latam.com/en/download/civic-ec-lb-aus-manual-7438.pdf, SHA-256 79402d8f5e622c98fc41a6aba277cdff3e6e203c79b04bb00ef0118a5b7d9ac8). Covers air handling units built on the S21 automation (e.g. CIVIC EC LB); Vents sells the same automation as A21, so one map covers both brands. The MODBUS PARAMETERS table prints the factory frame: baud rate 115200 (by default), 8 data bits, stop bits 2 (by default), parity None (by default) and address 1 (by default, range 1...16) - 115200 8N2 at unit 1. The same table documents Modbus TCP as an alternative (port 502, DHCP by default); this seed describes the RS-485 factory setting. Addresses are the document's Address column, which restarts at 0 in each area, so the seed is zero_based. Coils use FC 1/5/15, discrete inputs FC 2, input registers FC 4 and holding registers FC 3/6/16. Omitted by scope after every row below was checked against the table: the weekly-schedule block (holding 126...181, one register per field), the RTC registers (holding 61/63), the timer rows (input 25/27/29, holding 51), the engineering password (holding 124, Ascii), the 53 alarm-code discrete inputs 19...71 (input register 38 summarises them), coils 10, 12, 13, 14, 20 and 24, input registers 15, 19, 20, 32, 33, 34 and 48...50, and holding registers 23...42, 44, 47, 50, 52, 66, 67, 76...102, 109, 112...117 and 120...123 (per-mode flow and pressure setpoints, PID coefficients, sensor corrections, water-temperature thresholds). Every row present carries the document's own unit, range and pre-set value.