Belimo · HVAC controller

Air/water actuators ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD, ..H24A-MOD Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
38400
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Setpoint
Setpoint for the actuator, scaled between Min (register 105) and Max (register 106). Range 0...10000. Default 0.
UInt16%0.01RW
11
Override control
0 = none (default), 1 = open, 2 = close, 3 = min, 4 = mid, 5 = max, 6 = fast open, 7 = fast close. Overrides the setpoint with the defined value.
UInt16-1RW
21
Command
0 = none (default), 1 = adaption, 2 = test, 3 = sync, 4 = reset. After the command is sent the register returns to none; reset clears the malfunction and service information in register 104.
UInt16-1RW
31
Actuator type
0 = actuator not connected, 1 = air / water, 2 = VAV / EPIV, 3 = fire, 4 = energy valve, 5 = 6-way EPIV.
UInt16-1R
41
Relative position
Range 0...10000.
UInt16%0.01R
51
Absolute position
Degrees for actuators with rotary movement, millimetres for actuators with linear movement.
UInt16°1R
81
Sensor 1 value
Millivolts when sensor type 1 (register 107) is active, ohms for passive_1K / passive_20K, 0 / 1 for a switch, degrees Celsius or Fahrenheit x10 for the PT1000 / NI1000 / NTC10K2 types. Range 0...65535.
UInt16mV1R
121
Analog setpoint
Setpoint in percent when the actuator is controlled by the analog signal.
UInt16%0.01R
991
Bus termination
0 = inactive (default), 1 = active: the 120 ohm bus termination is enabled.
UInt16-1R
1001
Series number, 1st part
Parts 1, 2 and 4 of the four-part series number are readable; the example 00839-31324-064-008 is read as 00839 / 31324 / 008.
UInt16-1R
1011
Series number, 2nd part
UInt16-1R
1021
Series number, 4th part
UInt16-1R
1031
Firmware version
Communication module firmware, e.g. 302 for version 3.02.
UInt16-1R
1041
Malfunction and service information
Bit-coded. Bit 1 mechanical travel increased, bit 2 actuator cannot move, bit 8 internal activity, bit 9 gear train disengaged (manual override pressed), bit 10 bus watchdog triggered.
Binary-1R
1051
Min
Lower position limit, range 0...Max-20 percent. Default 0.
UInt16%0.01RW
1061
Max
Upper position limit, range Min+20...100 percent. Default 10000 (100 percent).
UInt16%0.01RW
1071
Sensor 1 type
0 = none (default), 1 = active / hybrid, 2 = passive_1K, 3 = passive_20K, 4 = switch, 5 = PT1000_C, 6 = NI1000_C, 7 = NTC10K2_C, 8 = PT1000_F, 9 = NI1000_F, 10 = NTC10K2_F. Restart the actuator after a change for correct sensor values.
UInt16-1RW
1081
Bus fail position
0 = none / last setpoint (default), 1 = fast close, 2 = fast open, 3 = mid position. Becomes active when the bus watchdog (register 109) expires.
UInt16-1RW
1091
Timeout for bus watchdog
0 = deactivated (default), range 0...3600 s. When a bus fail position is configured the document states a default of 120 s.
UInt16s1RW
1181
Setpoint source
0 = analog signal on wire 3, 1 = bus (default, setpoint from register 0).
UInt16-1RW
1891
Fail-safe bridging time
0...10 s. Time the actuator stays in its position after a power failure before moving to the fail-safe position. Only for electronic fail-safe actuators.
UInt16s1RW
1901
Fail-safe position
Position the actuator moves to after a power failure, respecting the bridging time. Range 0...10000. Only for electronic fail-safe actuators; the rotary knob must be in the tool position.
UInt16%0.01RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Belimo 'Modbus Interface Description - Air/water Actuators, General actuators for air and water', edition 2026-05 / V3.08, manufacturer date 05.09.2023 (belimo_Modbus-Register_AirWater_V3_8_en-gb.pdf). The vendor host www.belimo.com answers automated requests with HTTP 403, so the document was read from Belimo's own regional mirror https://www.belimo.ro/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_AirWater_V3_8_en-gb.pdf (same MAM document and edition); the URL above is the canonical vendor location. Covered actuator types: ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD - the spring-return, modulating and fail-safe damper and valve actuators of the air/water range. Factory Modbus settings from the document: 38400 Bd, 1-8-N-2 (8 data bits, no parity, 2 stop bits), address 1; 9600/19200/76800/115200 Bd and 1-8-N-1 / 1-8-E-1 / 1-8-O-1 are selectable, as are addresses 1...247. Addressing: the document prints 'addressed by 1..n (Register No.) or 0..n-1 (Address)' with both columns on every row; the values here are the Address column (one less than the Register No.), hence zero_based. All registers are unsigned 16-bit; there are no 32-bit values in this map, so word order only matters if a reader adds them later (Belimo stores 32-bit values LSW first, hence LowFirst). Deliberately left out: registers 6, 7, 9, 10, 11, 110 and 111-117, which the document prints as '–'. This map is not the VAV-Compact or PR map: it has no volumetric-flow or delta-pressure block, and instead carries the electronic fail-safe registers 190/191 that the other ranges do not have. Sensor 1 value is entered with the millivolt unit and no scaling because the unit and the scale follow register 107 (millivolt 1:1, ohm 1:1, switch 0/1, PT1000/NI1000/NTC10K2 in degrees x0.1).