  "spec_version": 1,
  "slug": "blauberg-s21-ahu",
  "manufacturer": "Blauberg",
  "model": "Air handling units with S21 automation (CIVIC EC LB and other S21 units)",
  "category": "HVAC controller",
  "supplier_url": "https://blaubergventilatoren.net/downloads/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 115200,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 2
    }
  },
  "coils": [
    {
      "address": 0,
      "count": 1,
      "name": "Unit on/off",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_POWER. 0 = off, 1 = on."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Main timer",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_TIMER. 0 = off, 1 = on."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Weekly schedule",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "L_WEEK. 0 = off, 1 = on."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Boost mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "CL_Boost_MODE. Read-only status."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Fireplace mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "L_FPLC_MODE. Read-only status."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Main humidity sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_IntRH_CTRL."
    },
    {
      "address": 6,
      "count": 1,
      "name": "External humidity sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_ExtRH_CTRL."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Main CO2 sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_IntCO2_CTRL."
    },
    {
      "address": 8,
      "count": 1,
      "name": "External CO2 sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_ExtCO2_CTRL."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Main PM2.5 sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_IntPM2_5_CTRL."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Main VOC sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_IntVOC_CTRL."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Fire alarm sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_FireALARM_CTRL."
    },
    {
      "address": 16,
      "count": 1,
      "name": "External 0-10 V control input activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_10V_SENSOR_CTRL."
    },
    {
      "address": 17,
      "count": 1,
      "name": "Reset filter timer",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_RESET_FILTER_TIMER. Write 1 to reset the filter countdown; reads back as 0."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Reset all alarms",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_RESET_ALARM. Write 1 to reset all alarms; reads back as 0."
    },
    {
      "address": 19,
      "count": 1,
      "name": "Restore everything to factory settings",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_RESTORE_FACTORY. Write 1 to restore the factory settings; the Pre-set column of the document's tables lists the values restored."
    },
    {
      "address": 21,
      "count": 1,
      "name": "Minimum room supply air temperature control",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_MinSuAirOutTEMP_CTRL."
    },
    {
      "address": 22,
      "count": 1,
      "name": "Heat medium water pressure sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_WaterPRESS_CTRL."
    },
    {
      "address": 23,
      "count": 1,
      "name": "Heat medium water flow sensor activation",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "CL_WaterFLOW_CTRL."
    },
    {
      "address": 25,
      "count": 1,
      "name": "Automatic air flow reduction if the main heater fails",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "L_AutoReductionAirFlow."
    }
  ],
  "discrete_inputs": [
    {
      "address": 0,
      "count": 1,
      "name": "Current input status, boost mode switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurBoostSWITCH."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Current input status, fireplace mode switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurFplcSWITCH."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Fire alarm sensor status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurFireALARM."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Humidity setpoint excess indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusRH."
    },
    {
      "address": 4,
      "count": 1,
      "name": "CO2 setpoint excess indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusCO2."
    },
    {
      "address": 5,
      "count": 1,
      "name": "PM2.5 setpoint excess indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusPM2_5."
    },
    {
      "address": 6,
      "count": 1,
      "name": "VOC setpoint excess indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusVOC."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Heater operation indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusHEATER."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Cooler operation indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusCOOLER."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Electric heater blowdown indication",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_StatusFanBLOWING."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Preheating thermostat input status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurPreHeaterThermostat."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Reheating thermostat input status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurMainHeaterThermostat."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Supply filter differential pressure switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurSuFilterPRESS."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Extract filter differential pressure switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurExFilterPRESS."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Heat medium water pressure sensor status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurWaterPRESS."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Heat medium water flow sensor status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurWaterFLOW."
    },
    {
      "address": 16,
      "count": 1,
      "name": "Supply fan differential pressure switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurSuFanPRESS."
    },
    {
      "address": 17,
      "count": 1,
      "name": "Extract fan differential pressure switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_CurExFanPRESS."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Return water preheating indicator before unit start-up",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "DI_WaterPreheatingStatus."
    }
  ],
  "input_registers": [
    {
      "address": 0,
      "count": 1,
      "name": "Current temperature of the selected control sensor",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurSelTEMP. Value 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Current outdoor air temperature before preheating",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_SuAirIn. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Current supply air temperature at unit outlet",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_SuAirOut. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Current extract air temperature at unit inlet",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_ExAirIn. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Current exhaust air temperature at unit outlet",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_ExAirOut. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Current outdoor air temperature of the control-panel sensor",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_Ext. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Current supply air temperature after preheating",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_AfterPreHeater. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Current supply air temperature upstream of the reheater",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_BeforeMainHeater. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Return heat medium temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurTEMP_Water. 250 = 25.0 degC; -32768 = no sensor, +32767 = short circuit."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Battery voltage for the RTC",
      "data_type": "UInt16",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurVBAT. 0...5000 mV."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Current humidity, main sensor",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurRH_Int. 0 = no sensor."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Current humidity, outdoor sensor",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurRH_Ext. 0 = no sensor."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Current CO2 level, main sensor",
      "data_type": "UInt16",
      "units": "ppm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurCO2_Int. 0 = no sensor."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Current CO2 level, external sensor",
      "data_type": "UInt16",
      "units": "ppm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurCO2_Ext. 0 = no sensor."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Current PM2.5 level, main sensor",
      "data_type": "UInt16",
      "units": "ug/m3",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurPM2_5_Int. 0 = no sensor."
    },
    {
      "address": 16,
      "count": 1,
      "name": "Current VOC level, main sensor",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurVOC_Int. 0 = no sensor."
    },
    {
      "address": 17,
      "count": 1,
      "name": "Current VOC level, external sensor",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurVOC_Ext. 0 = no sensor."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Current value of the 0-10 V sensor",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_Cur10V_SENSOR."
    },
    {
      "address": 21,
      "count": 1,
      "name": "Current pressure in the supply air duct",
      "data_type": "UInt16",
      "units": "Pa",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurSuPRESS. 0...10000 Pa."
    },
    {
      "address": 22,
      "count": 1,
      "name": "Current pressure in the exhaust air duct",
      "data_type": "UInt16",
      "units": "Pa",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurExPRESS. 0...10000 Pa."
    },
    {
      "address": 23,
      "count": 1,
      "name": "Supply fan speed",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_SuRPM. 0...5000 rpm."
    },
    {
      "address": 24,
      "count": 1,
      "name": "Extract fan speed",
      "data_type": "UInt16",
      "units": "rpm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_ExRPM. 0...5000 rpm."
    },
    {
      "address": 31,
      "count": 1,
      "name": "Filter condition",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_StateFILTER. 0...3."
    },
    {
      "address": 37,
      "count": 1,
      "name": "Device type (controller)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_DeviceTYPE. 1 = S21."
    },
    {
      "address": 38,
      "count": 1,
      "name": "Alarm/warning indicator",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_ALARM. 0 = normal, 1 = warning, 2 = alarm."
    },
    {
      "address": 39,
      "count": 1,
      "name": "Control signal from the PID humidity controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_RH_U. 0...100 %."
    },
    {
      "address": 40,
      "count": 1,
      "name": "Control signal from the PID CO2 controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CO2_U. 0...100 %."
    },
    {
      "address": 41,
      "count": 1,
      "name": "Control signal from the PID PM2.5 controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_PM2_5_U. 0...100 %."
    },
    {
      "address": 42,
      "count": 1,
      "name": "Control signal from the PID VOC controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_VOC_U. 0...100 %."
    },
    {
      "address": 43,
      "count": 1,
      "name": "Control signal from the PID preheating controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_PreHeater_U. 0...200 %."
    },
    {
      "address": 44,
      "count": 1,
      "name": "Control signal from the PID reheating controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_MainHeater_U. 0...200 %."
    },
    {
      "address": 45,
      "count": 1,
      "name": "Control signal from the PID bypass/rotary heat exchanger controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_BPS_ROTOR_U. 0...200 %."
    },
    {
      "address": 46,
      "count": 1,
      "name": "Control signal from the PID condenser unit controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_KKB_U. 0...100 %."
    },
    {
      "address": 47,
      "count": 1,
      "name": "Control signal from the PID return heat medium controller",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_ReturnWater_U. 0...100 %."
    },
    {
      "address": 51,
      "count": 1,
      "name": "Bypass/rotor position",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_StatusBpsRotor. 100 means 100 % bypass."
    },
    {
      "address": 52,
      "count": 1,
      "name": "Current supply fan performance",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_CurSuFanSpeed. 0...100 %."
    },
    {
      "address": 53,
      "count": 1,
      "name": "Current extract fan performance",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "IR_ExFanSpeed. 0...100 %."
    }
  ],
  "holding_registers": [
    {
      "address": 0,
      "count": 1,
      "name": "Ventilation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_VENTILATION_MODE. Range 0...2, pre-set 1."
    },
    {
      "address": 1,
      "count": 1,
      "name": "Maximum permissible speed number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_MaxSPEED_MODE. Range 3...5, pre-set 3."
    },
    {
      "address": 2,
      "count": 1,
      "name": "Speed number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SPEED_MODE. Range 1...255, pre-set 1."
    },
    {
      "address": 3,
      "count": 1,
      "name": "Minimum possible fan speed",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_MinSPEED. 0...100 %, pre-set 30 %."
    },
    {
      "address": 4,
      "count": 1,
      "name": "Maximum possible fan speed",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_MaxSPEED. 0...100 %, pre-set 100 %."
    },
    {
      "address": 5,
      "count": 1,
      "name": "Supply fan speed in standby mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED0. Pre-set 0 %."
    },
    {
      "address": 6,
      "count": 1,
      "name": "Extract fan speed in standby mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED0. Pre-set 0 %."
    },
    {
      "address": 7,
      "count": 1,
      "name": "Supply fan speed, speed 1",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED1. Pre-set 40 %."
    },
    {
      "address": 8,
      "count": 1,
      "name": "Extract fan speed, speed 1",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED1. Pre-set 40 %."
    },
    {
      "address": 9,
      "count": 1,
      "name": "Supply fan speed, speed 2",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED2. Pre-set 70 %."
    },
    {
      "address": 10,
      "count": 1,
      "name": "Extract fan speed, speed 2",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED2. Pre-set 70 %."
    },
    {
      "address": 11,
      "count": 1,
      "name": "Supply fan speed, speed 3",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED3. Pre-set 100 %."
    },
    {
      "address": 12,
      "count": 1,
      "name": "Extract fan speed, speed 3",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED3. Pre-set 100 %."
    },
    {
      "address": 13,
      "count": 1,
      "name": "Supply fan speed, speed 4",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED4. Pre-set 100 %."
    },
    {
      "address": 14,
      "count": 1,
      "name": "Extract fan speed, speed 4",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED4. Pre-set 100 %."
    },
    {
      "address": 15,
      "count": 1,
      "name": "Supply fan speed, speed 5",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SuSPEED5. Pre-set 100 %."
    },
    {
      "address": 16,
      "count": 1,
      "name": "Extract fan speed, speed 5",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ExSPEED5. Pre-set 100 %."
    },
    {
      "address": 17,
      "count": 1,
      "name": "Fan speed in manual speed setting mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_ManualSPEED. Pre-set 50 %."
    },
    {
      "address": 18,
      "count": 1,
      "name": "Fan speed while blowing electric heaters",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_BlowingSPEED. Pre-set 50 %."
    },
    {
      "address": 19,
      "count": 1,
      "name": "Supply fan speed in boost mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_Boost_SuSPEED. Pre-set 100 %."
    },
    {
      "address": 20,
      "count": 1,
      "name": "Extract fan speed in boost mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_Boost_ExSPEED. Pre-set 100 %."
    },
    {
      "address": 21,
      "count": 1,
      "name": "Supply fan speed in fireplace mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_FPLC_SuSPEED. Pre-set 60 %."
    },
    {
      "address": 22,
      "count": 1,
      "name": "Extract fan speed in fireplace mode",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_FPLC_ExSPEED. Pre-set 40 %."
    },
    {
      "address": 37,
      "count": 1,
      "name": "Minimum possible pressure in the air duct",
      "data_type": "UInt16",
      "units": "Pa",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_MinAirPRESS. 0...10000 Pa."
    },
    {
      "address": 38,
      "count": 1,
      "name": "Maximum possible pressure in the air duct",
      "data_type": "UInt16",
      "units": "Pa",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_MaxAirPRESS. 0...10000 Pa."
    },
    {
      "address": 43,
      "count": 1,
      "name": "Unit operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_OPERATION_MODE. Range 0...3, pre-set 3."
    },
    {
      "address": 45,
      "count": 1,
      "name": "Humidity threshold setpoint",
      "data_type": "UInt16",
      "units": "%RH",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetRH. 40...80 %RH, pre-set 60."
    },
    {
      "address": 46,
      "count": 1,
      "name": "CO2 threshold setpoint",
      "data_type": "UInt16",
      "units": "ppm",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetCO2. 400...2000 ppm, pre-set 1200."
    },
    {
      "address": 48,
      "count": 1,
      "name": "VOC threshold setpoint",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetVOC. 20...100 %, pre-set 40."
    },
    {
      "address": 49,
      "count": 1,
      "name": "Timer mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_TIMER_MODE. Range 0...5, pre-set 1."
    },
    {
      "address": 53,
      "count": 1,
      "name": "Temperature sensor selected for room temperature control",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SelTEMP_SENSOR. Range 0...2, pre-set 2."
    },
    {
      "address": 54,
      "count": 1,
      "name": "Main heater type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_MainHeater_TYPE. Range 0...2."
    },
    {
      "address": 55,
      "count": 1,
      "name": "Cooler control type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_COOLER_TYPE. Range 0...2."
    },
    {
      "address": 56,
      "count": 1,
      "name": "Heat exchanger freeze protection mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_DEF_MODE. Range 0...3."
    },
    {
      "address": 57,
      "count": 1,
      "name": "Bypass/rotary heat exchanger type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_BPS_ROTOR_TYPE. Range 0...4."
    },
    {
      "address": 58,
      "count": 1,
      "name": "Filter timer setpoint",
      "data_type": "UInt16",
      "units": "days",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetFILTER_TIMER. 0 switches the timer off, otherwise 70...365 days; pre-set 90 days."
    },
    {
      "address": 59,
      "count": 1,
      "name": "Boost mode turn-off delay",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_BoostDelaySwitchingOff. 0...60 min, pre-set 0."
    },
    {
      "address": 60,
      "count": 1,
      "name": "Boost mode turn-on delay",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_BoostDelaySwitchingOn. 0...15 min, pre-set 0."
    },
    {
      "address": 65,
      "count": 1,
      "name": "Maximum value of the main CO2 sensor",
      "data_type": "UInt16",
      "units": "ppm",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_MaxCO2_Int. 500...10000 ppm, pre-set 2000."
    },
    {
      "address": 68,
      "count": 1,
      "name": "Main heater operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_MainHeaterMODE. Range 1...2, pre-set 2."
    },
    {
      "address": 69,
      "count": 1,
      "name": "Manual control of the main heater",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetMainHeaterMANUAL. Pre-set 50 %."
    },
    {
      "address": 70,
      "count": 1,
      "name": "Cooler operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_CoolerMODE. Range 1...2, pre-set 2."
    },
    {
      "address": 71,
      "count": 1,
      "name": "Manual cooler control with analogue configuration",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetCoolerMANUAL. Pre-set 0 %."
    },
    {
      "address": 72,
      "count": 1,
      "name": "Preheating operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_PreHeaterMODE. Range 1...2, pre-set 2."
    },
    {
      "address": 73,
      "count": 1,
      "name": "Manual preheating control",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetPreHeaterMANUAL. Pre-set 50 %."
    },
    {
      "address": 74,
      "count": 1,
      "name": "Bypass/rotary heat exchanger operation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_BPS_ROTOR_MODE. Range 0...2, pre-set 2."
    },
    {
      "address": 75,
      "count": 1,
      "name": "Manual bypass/rotor control with analogue configuration",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetBpsRotorMANUAL. Pre-set 100 %."
    },
    {
      "address": 103,
      "count": 1,
      "name": "Fan alarm control type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_FanAlarmCTRL. Range 0...255, pre-set 2."
    },
    {
      "address": 104,
      "count": 1,
      "name": "Time for fan alarm detection",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_SetTimeDetectFanALARM. 5...120 s, pre-set 30."
    },
    {
      "address": 105,
      "count": 1,
      "name": "Damper opening time (fan turn-on delay)",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetTimeOpenVALVE. 0...240 s, pre-set 0."
    },
    {
      "address": 106,
      "count": 1,
      "name": "Electric heater blowdown time",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_SetTimeFanBLOWING. 20...240 s, pre-set 120."
    },
    {
      "address": 107,
      "count": 1,
      "name": "Minimum downtime of the condenser unit before restarting",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_KKB_MinTimeOFF. 0...20 min, pre-set 3."
    },
    {
      "address": 108,
      "count": 1,
      "name": "Minimum operating time of the condenser unit before shutdown",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_KKB_MinTimeON. 0...20 min, pre-set 1."
    },
    {
      "address": 110,
      "count": 1,
      "name": "Bypass location",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_BPS_Position. 0 = from outdoors, 1 = from indoors."
    },
    {
      "address": 111,
      "count": 1,
      "name": "Opening time of the bypass with three-point control",
      "data_type": "UInt16",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "HR_TimeOpenBPS. 2...300 s."
    },
    {
      "address": 118,
      "count": 1,
      "name": "Minimum position of the water heater valve in winter",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_WaterValveMinPos. 0...100 %, pre-set 0."
    },
    {
      "address": 119,
      "count": 1,
      "name": "Time for detecting return heat medium underheating alarm",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "HR_WaterMaxStartTime. 2...30 min, pre-set 5."
    }
  ],
  "combined_registers": [],
  "notes": "Source: Blauberg \"Modbus table for connecting S21 automation to BMS\" (no revision printed; copy read: blauberg-latam.com/en/download/civic-ec-lb-aus-manual-7438.pdf, SHA-256 79402d8f5e622c98fc41a6aba277cdff3e6e203c79b04bb00ef0118a5b7d9ac8). Covers air handling units built on the S21 automation (e.g. CIVIC EC LB); Vents sells the same automation as A21, so one map covers both brands. The MODBUS PARAMETERS table prints the factory frame: baud rate 115200 (by default), 8 data bits, stop bits 2 (by default), parity None (by default) and address 1 (by default, range 1...16) - 115200 8N2 at unit 1. The same table documents Modbus TCP as an alternative (port 502, DHCP by default); this seed describes the RS-485 factory setting. Addresses are the document's Address column, which restarts at 0 in each area, so the seed is zero_based. Coils use FC 1/5/15, discrete inputs FC 2, input registers FC 4 and holding registers FC 3/6/16. Omitted by scope after every row below was checked against the table: the weekly-schedule block (holding 126...181, one register per field), the RTC registers (holding 61/63), the timer rows (input 25/27/29, holding 51), the engineering password (holding 124, Ascii), the 53 alarm-code discrete inputs 19...71 (input register 38 summarises them), coils 10, 12, 13, 14, 20 and 24, input registers 15, 19, 20, 32, 33, 34 and 48...50, and holding registers 23...42, 44, 47, 50, 52, 66, 67, 76...102, 109, 112...117 and 120...123 (per-mode flow and pressure setpoints, PID coefficients, sensor corrections, water-temperature thresholds). Every row present carries the document's own unit, range and pre-set value."
}