All devices

Sigenergy · Solar inverter

SigenStor EC / Sigen Hybrid / Sigen PV Max Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
3050015
Model type
Model designation of the inverter, packed as ASCII.
Ascii-1R
3051510
Serial number
Serial number of the inverter, packed as ASCII.
Ascii-1R
3052515
Machine firmware version
Firmware version of the inverter, packed as ASCII.
Ascii-1R
305402
Rated active power
UInt32kW0.001R
305422
Maximum apparent power
UInt32kVA0.001R
305442
Maximum active power
UInt32kW0.001R
305462
Maximum absorption power
Documented for hybrid inverters only.
UInt32kW0.001R
305482
Rated battery capacity
Documented for hybrid inverters only.
UInt32kWh0.01R
305502
ESS rated charging power
Documented for hybrid inverters only.
UInt32kW0.001R
305522
ESS rated discharging power
Documented for hybrid inverters only.
UInt32kW0.001R
305662
ESS daily charge energy
Documented for hybrid inverters only.
UInt32kWh0.01R
305722
ESS daily discharge energy
Documented for hybrid inverters only.
UInt32kWh0.01R
305781
Inverter running state
0 = standby, 1 = running, 2 = fault, 3 = shutdown, 7 = environmental abnormality.
UInt16-1R
305792
Maximum active power adjustment value
Int32kW0.001R
305812
Minimum active power adjustment value
Documented for hybrid inverters only.
Int32kW0.001R
305832
Maximum reactive power adjustment value fed to the AC terminal
UInt32kVar0.001R
305852
Maximum reactive power adjustment value absorbed from the AC terminal
UInt32kVar0.001R
305872
Inverter active power
Int32kW0.001R
305892
Inverter reactive power
Int32kVar0.001R
305912
ESS maximum battery charging power
Documented for hybrid inverters only.
UInt32kW0.001R
305932
ESS maximum battery discharging power
Documented for hybrid inverters only.
UInt32kW0.001R
305952
ESS available battery charging energy
Documented for hybrid inverters only.
UInt32kWh0.01R
305972
ESS available battery discharging energy
Documented for hybrid inverters only.
UInt32kWh0.01R
305992
ESS charge/discharge power
Negative = discharging, positive = charging, the sign the document prints for the plant ESS power at 30037; it prints none for this row, and the evcc template negates the raw value for its own convention. Documented for hybrid inverters only.
Int32kW0.001R
306011
Battery state of charge
Documented for hybrid inverters only.
UInt16%0.1R
306021
Battery state of health
Documented for hybrid inverters only.
UInt16%0.1R
306031
Average cell temperature
Documented for hybrid inverters only.
Int16°C0.1R
306041
Average cell voltage
Documented for hybrid inverters only.
UInt16V0.001R
306051
Alarm 1
Bit field of PCS alarm codes; the document's appendix 2 lists codes 1001-1016 on bits 0-15.
UInt16-1R
306061
Alarm 2
Bit field of PCS alarm codes; the document's appendix 3 lists codes 1017 onwards on bits 0-15.
UInt16-1R
306071
Alarm 3
Bit field of ESS alarm codes; see the document's appendix 4. Documented for hybrid inverters only.
UInt16-1R
306081
Alarm 4
Bit field of gateway alarm codes; see the document's appendix 5.
UInt16-1R
306091
Alarm 5
Bit field of DC charger alarm codes; see the document's appendix 11. Documented for hybrid inverters only.
UInt16-1R
306132
Active power fixed-value adjustment feedback
Int32kW0.001R
306152
Reactive power fixed-value adjustment feedback
Int32kVar0.001R
306171
Active power percentage adjustment feedback
Int16%0.01R
306181
Reactive power Q/S adjustment feedback
Int16%0.01R
306191
Power factor adjustment feedback
Int16-0.001R
306201
Maximum battery (cluster) temperature
Documented for hybrid inverters only.
Int16°C0.1R
306211
Minimum battery (cluster) temperature
Documented for hybrid inverters only.
Int16°C0.1R
306221
Maximum battery (cluster) cell voltage
Documented for hybrid inverters only.
UInt16V0.001R
306231
Minimum battery (cluster) cell voltage
Documented for hybrid inverters only.
UInt16V0.001R
310001
Rated grid voltage
UInt16V0.1R
310011
Rated grid frequency
UInt16Hz0.01R
310021
Grid frequency
UInt16Hz0.01R
310031
PCS internal temperature
Int16°C0.1R
310041
Output type
0 = L/N, 1 = L1/L2/L3, 2 = L1/L2/L3/N, 3 = L1/L2/N.
UInt16-1R
310052
A-B line voltage
Invalid when the output type is L/N, L1/L2/N.
UInt32V0.01R
310072
B-C line voltage
Invalid when the output type is L/N, L1/L2/N.
UInt32V0.01R
310092
C-A line voltage
Invalid when the output type is L/N, L1/L2/N.
UInt32V0.01R
310112
Phase A voltage
With output type L/N this is the phase-to-neutral voltage.
UInt32V0.01R
310132
Phase B voltage
Invalid when the output type is L/N, L1/L2/N.
UInt32V0.01R
310152
Phase C voltage
Invalid when the output type is L/N, L1/L2/N.
UInt32V0.01R
310172
Phase A current
With output type L/N this is the phase current.
Int32A0.01R
310192
Phase B current
Invalid when the output type is L/N, L1/L2/N.
Int32A0.01R
310212
Phase C current
Invalid when the output type is L/N, L1/L2/N.
Int32A0.01R
310231
Power factor
UInt16-0.001R
310241
Pack count
Number of battery packs. Documented for hybrid inverters only.
UInt16-1R
310251
PV string count
UInt16-1R
310261
MPPT count
UInt16-1R
310271
PV1 voltage
Present only when the model has this MPPT; the document's applicable-model table lists the string and MPPT counts per model.
Int16V0.1R
310281
PV1 current
Int16A0.01R
310291
PV2 voltage
Int16V0.1R
310301
PV2 current
Int16A0.01R
310311
PV3 voltage
Int16V0.1R
310321
PV3 current
Int16A0.01R
310331
PV4 voltage
Int16V0.1R
310341
PV4 current
Int16A0.01R
310352
PV power
Int32kW0.001R
310371
Insulation resistance
UInt16MΩ0.001R
310382
Start-up time
UInt32s1R
310402
Shutdown time
UInt32s1R
310421
PV5 voltage
Int16V0.1R
310431
PV5 current
Int16A0.01R
310441
PV6 voltage
Int16V0.1R
310451
PV6 current
Int16A0.01R
310461
PV7 voltage
Int16V0.1R
310471
PV7 current
Int16A0.01R
310481
PV8 voltage
Int16V0.1R
310491
PV8 current
Int16A0.01R
310501
PV9 voltage
The document prints this row's label as "PV8 current" with unit V; its type, unit and position between PV8 current (31049) and PV9 current (31051) identify it as PV9 voltage, and the seed records that reading rather than copying the label.
Int16V0.1R
310511
PV9 current
Int16A0.01R
310521
PV10 voltage
Int16V0.1R
310531
PV10 current
Int16A0.01R
310541
PV11 voltage
Int16V0.1R
310551
PV11 current
Int16A0.01R
310561
PV12 voltage
Int16V0.1R
310571
PV12 current
Int16A0.01R
310581
PV13 voltage
Int16V0.1R
310591
PV13 current
Int16A0.01R
310601
PV14 voltage
Int16V0.1R
310611
PV14 current
Int16A0.01R
310621
PV15 voltage
Int16V0.1R
310631
PV15 current
Int16A0.01R
310641
PV16 voltage
Int16V0.1R
310651
PV16 current
Int16A0.01R
315001
DC charger vehicle battery voltage
Present when the unit has the integrated DC charger. Documented for hybrid inverters only.
UInt16V0.1R
315011
DC charger charging current
Documented for hybrid inverters only.
UInt16A0.1R
315022
DC charger output power
Documented for hybrid inverters only.
Int32kW0.001R
315041
DC charger vehicle state of charge
Documented for hybrid inverters only.
UInt16%0.1R
315052
DC charger current charging capacity
Energy of the present charging session. Documented for hybrid inverters only.
UInt32kWh0.01R
315072
DC charger current charging duration
Duration of the present charging session. Documented for hybrid inverters only.
UInt32s1R
315092
PV daily generation
UInt32kWh0.01R
315112
PV total generation
UInt32kWh0.01R
405001
Inverter Start/Stop
0 = stop, 1 = start.
UInt16-1W
410001
DC charger Start/Stop
0 = start, 1 = stop - the opposite of the plant Start/Stop at 40000. Documented for hybrid inverters only.
UInt16-1W
415001
Remote EMS dispatch enable
0 = disabled, 1 = enabled. The enabled inverter then reacts only to the power control commands at 41501-41507. Documented for PV inverters only.
UInt16-1RW
415012
Active power fixed value adjustment
Documented for PV inverters only.
Int32kW0.001R
415032
Reactive power fixed value adjustment
Documented for PV inverters only.
Int32kVar0.001R
415051
Active power percentage adjustment
Documented for PV inverters only.
Int16%0.01R
415061
Reactive power Q/S adjustment
Documented for PV inverters only.
Int16%0.01R
415071
Power factor adjustment
Documented for PV inverters only.
Int16-0.001R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: vendor document "Sigenergy Modbus Protocol", V2.7, 2025-05-23, https://www.sigenergy.com/uploads/us_download/1755488219226583.pdf, downloaded 2026-11-23, SHA-256 3b1fb31390a74773b76c6be1f56fad081197639c389ef25dd39289406e2232ce. This seed is the per-inverter block: table 5-3 running information (30500-31511) and table 5-4 parameter setting (40500, 41000, 41500-41507), which the document restricts to a valid inverter's Modbus slave address in the range 1-246. The plant block (30000-30194, 40000-40048), reached at plant address 247, is the separate seed sigenergy-sigenstor. The document prints no factory slave address for an inverter - it is set in the app and must be unique in the plant - so unit ID 1 here is a placeholder to set on site, not a cited default. Addresses are read as printed, so zero-based. The document contradicts itself on reads (4.1: RO answers only 0x04; 6.1 and the worked example 01 03 774C 0002 read a read-only register with 0x03), so the read-only rows stay in the holding area, which 0x03 addresses and the evcc template polls. Tables mark rows as hybrid-inverter only, PV-inverter only or both, and such rows say so in their description. No byte or word order is printed, so BigEndian/HighFirst is a declared convention. Left out: the 64-bit ESS charge and discharge counters 30568/30574, as the format has no 64-bit type and no 32-bit twin is printed (the daily counters 30566/30572 are seeded); the reserved rows 30554 and 30610; and the AC-charger block 32000-32014 with 42000, a separate device. Row 31050 is printed "PV8 current" with unit V and is seeded as PV9 voltage. Writable rows are those the document marks WO or RW with a printed range or enum; 41501-41507 print neither and are seeded read-only. No hardware test is claimed.