Sigenergy · Solar inverter
SigenStor EC / Sigen Hybrid / Sigen PV Max Modbus register map
Default configuration
- Protocol
- Modbus TCP
- Port
- 502
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 30500 | 15 | Model type Model designation of the inverter, packed as ASCII. | Ascii | - | 1 | R |
| 30515 | 10 | Serial number Serial number of the inverter, packed as ASCII. | Ascii | - | 1 | R |
| 30525 | 15 | Machine firmware version Firmware version of the inverter, packed as ASCII. | Ascii | - | 1 | R |
| 30540 | 2 | Rated active power | UInt32 | kW | 0.001 | R |
| 30542 | 2 | Maximum apparent power | UInt32 | kVA | 0.001 | R |
| 30544 | 2 | Maximum active power | UInt32 | kW | 0.001 | R |
| 30546 | 2 | Maximum absorption power Documented for hybrid inverters only. | UInt32 | kW | 0.001 | R |
| 30548 | 2 | Rated battery capacity Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 30550 | 2 | ESS rated charging power Documented for hybrid inverters only. | UInt32 | kW | 0.001 | R |
| 30552 | 2 | ESS rated discharging power Documented for hybrid inverters only. | UInt32 | kW | 0.001 | R |
| 30566 | 2 | ESS daily charge energy Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 30572 | 2 | ESS daily discharge energy Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 30578 | 1 | Inverter running state 0 = standby, 1 = running, 2 = fault, 3 = shutdown, 7 = environmental abnormality. | UInt16 | - | 1 | R |
| 30579 | 2 | Maximum active power adjustment value | Int32 | kW | 0.001 | R |
| 30581 | 2 | Minimum active power adjustment value Documented for hybrid inverters only. | Int32 | kW | 0.001 | R |
| 30583 | 2 | Maximum reactive power adjustment value fed to the AC terminal | UInt32 | kVar | 0.001 | R |
| 30585 | 2 | Maximum reactive power adjustment value absorbed from the AC terminal | UInt32 | kVar | 0.001 | R |
| 30587 | 2 | Inverter active power | Int32 | kW | 0.001 | R |
| 30589 | 2 | Inverter reactive power | Int32 | kVar | 0.001 | R |
| 30591 | 2 | ESS maximum battery charging power Documented for hybrid inverters only. | UInt32 | kW | 0.001 | R |
| 30593 | 2 | ESS maximum battery discharging power Documented for hybrid inverters only. | UInt32 | kW | 0.001 | R |
| 30595 | 2 | ESS available battery charging energy Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 30597 | 2 | ESS available battery discharging energy Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 30599 | 2 | ESS charge/discharge power Negative = discharging, positive = charging, the sign the document prints for the plant ESS power at 30037; it prints none for this row, and the evcc template negates the raw value for its own convention. Documented for hybrid inverters only. | Int32 | kW | 0.001 | R |
| 30601 | 1 | Battery state of charge Documented for hybrid inverters only. | UInt16 | % | 0.1 | R |
| 30602 | 1 | Battery state of health Documented for hybrid inverters only. | UInt16 | % | 0.1 | R |
| 30603 | 1 | Average cell temperature Documented for hybrid inverters only. | Int16 | °C | 0.1 | R |
| 30604 | 1 | Average cell voltage Documented for hybrid inverters only. | UInt16 | V | 0.001 | R |
| 30605 | 1 | Alarm 1 Bit field of PCS alarm codes; the document's appendix 2 lists codes 1001-1016 on bits 0-15. | UInt16 | - | 1 | R |
| 30606 | 1 | Alarm 2 Bit field of PCS alarm codes; the document's appendix 3 lists codes 1017 onwards on bits 0-15. | UInt16 | - | 1 | R |
| 30607 | 1 | Alarm 3 Bit field of ESS alarm codes; see the document's appendix 4. Documented for hybrid inverters only. | UInt16 | - | 1 | R |
| 30608 | 1 | Alarm 4 Bit field of gateway alarm codes; see the document's appendix 5. | UInt16 | - | 1 | R |
| 30609 | 1 | Alarm 5 Bit field of DC charger alarm codes; see the document's appendix 11. Documented for hybrid inverters only. | UInt16 | - | 1 | R |
| 30613 | 2 | Active power fixed-value adjustment feedback | Int32 | kW | 0.001 | R |
| 30615 | 2 | Reactive power fixed-value adjustment feedback | Int32 | kVar | 0.001 | R |
| 30617 | 1 | Active power percentage adjustment feedback | Int16 | % | 0.01 | R |
| 30618 | 1 | Reactive power Q/S adjustment feedback | Int16 | % | 0.01 | R |
| 30619 | 1 | Power factor adjustment feedback | Int16 | - | 0.001 | R |
| 30620 | 1 | Maximum battery (cluster) temperature Documented for hybrid inverters only. | Int16 | °C | 0.1 | R |
| 30621 | 1 | Minimum battery (cluster) temperature Documented for hybrid inverters only. | Int16 | °C | 0.1 | R |
| 30622 | 1 | Maximum battery (cluster) cell voltage Documented for hybrid inverters only. | UInt16 | V | 0.001 | R |
| 30623 | 1 | Minimum battery (cluster) cell voltage Documented for hybrid inverters only. | UInt16 | V | 0.001 | R |
| 31000 | 1 | Rated grid voltage | UInt16 | V | 0.1 | R |
| 31001 | 1 | Rated grid frequency | UInt16 | Hz | 0.01 | R |
| 31002 | 1 | Grid frequency | UInt16 | Hz | 0.01 | R |
| 31003 | 1 | PCS internal temperature | Int16 | °C | 0.1 | R |
| 31004 | 1 | Output type 0 = L/N, 1 = L1/L2/L3, 2 = L1/L2/L3/N, 3 = L1/L2/N. | UInt16 | - | 1 | R |
| 31005 | 2 | A-B line voltage Invalid when the output type is L/N, L1/L2/N. | UInt32 | V | 0.01 | R |
| 31007 | 2 | B-C line voltage Invalid when the output type is L/N, L1/L2/N. | UInt32 | V | 0.01 | R |
| 31009 | 2 | C-A line voltage Invalid when the output type is L/N, L1/L2/N. | UInt32 | V | 0.01 | R |
| 31011 | 2 | Phase A voltage With output type L/N this is the phase-to-neutral voltage. | UInt32 | V | 0.01 | R |
| 31013 | 2 | Phase B voltage Invalid when the output type is L/N, L1/L2/N. | UInt32 | V | 0.01 | R |
| 31015 | 2 | Phase C voltage Invalid when the output type is L/N, L1/L2/N. | UInt32 | V | 0.01 | R |
| 31017 | 2 | Phase A current With output type L/N this is the phase current. | Int32 | A | 0.01 | R |
| 31019 | 2 | Phase B current Invalid when the output type is L/N, L1/L2/N. | Int32 | A | 0.01 | R |
| 31021 | 2 | Phase C current Invalid when the output type is L/N, L1/L2/N. | Int32 | A | 0.01 | R |
| 31023 | 1 | Power factor | UInt16 | - | 0.001 | R |
| 31024 | 1 | Pack count Number of battery packs. Documented for hybrid inverters only. | UInt16 | - | 1 | R |
| 31025 | 1 | PV string count | UInt16 | - | 1 | R |
| 31026 | 1 | MPPT count | UInt16 | - | 1 | R |
| 31027 | 1 | PV1 voltage Present only when the model has this MPPT; the document's applicable-model table lists the string and MPPT counts per model. | Int16 | V | 0.1 | R |
| 31028 | 1 | PV1 current | Int16 | A | 0.01 | R |
| 31029 | 1 | PV2 voltage | Int16 | V | 0.1 | R |
| 31030 | 1 | PV2 current | Int16 | A | 0.01 | R |
| 31031 | 1 | PV3 voltage | Int16 | V | 0.1 | R |
| 31032 | 1 | PV3 current | Int16 | A | 0.01 | R |
| 31033 | 1 | PV4 voltage | Int16 | V | 0.1 | R |
| 31034 | 1 | PV4 current | Int16 | A | 0.01 | R |
| 31035 | 2 | PV power | Int32 | kW | 0.001 | R |
| 31037 | 1 | Insulation resistance | UInt16 | MΩ | 0.001 | R |
| 31038 | 2 | Start-up time | UInt32 | s | 1 | R |
| 31040 | 2 | Shutdown time | UInt32 | s | 1 | R |
| 31042 | 1 | PV5 voltage | Int16 | V | 0.1 | R |
| 31043 | 1 | PV5 current | Int16 | A | 0.01 | R |
| 31044 | 1 | PV6 voltage | Int16 | V | 0.1 | R |
| 31045 | 1 | PV6 current | Int16 | A | 0.01 | R |
| 31046 | 1 | PV7 voltage | Int16 | V | 0.1 | R |
| 31047 | 1 | PV7 current | Int16 | A | 0.01 | R |
| 31048 | 1 | PV8 voltage | Int16 | V | 0.1 | R |
| 31049 | 1 | PV8 current | Int16 | A | 0.01 | R |
| 31050 | 1 | PV9 voltage The document prints this row's label as "PV8 current" with unit V; its type, unit and position between PV8 current (31049) and PV9 current (31051) identify it as PV9 voltage, and the seed records that reading rather than copying the label. | Int16 | V | 0.1 | R |
| 31051 | 1 | PV9 current | Int16 | A | 0.01 | R |
| 31052 | 1 | PV10 voltage | Int16 | V | 0.1 | R |
| 31053 | 1 | PV10 current | Int16 | A | 0.01 | R |
| 31054 | 1 | PV11 voltage | Int16 | V | 0.1 | R |
| 31055 | 1 | PV11 current | Int16 | A | 0.01 | R |
| 31056 | 1 | PV12 voltage | Int16 | V | 0.1 | R |
| 31057 | 1 | PV12 current | Int16 | A | 0.01 | R |
| 31058 | 1 | PV13 voltage | Int16 | V | 0.1 | R |
| 31059 | 1 | PV13 current | Int16 | A | 0.01 | R |
| 31060 | 1 | PV14 voltage | Int16 | V | 0.1 | R |
| 31061 | 1 | PV14 current | Int16 | A | 0.01 | R |
| 31062 | 1 | PV15 voltage | Int16 | V | 0.1 | R |
| 31063 | 1 | PV15 current | Int16 | A | 0.01 | R |
| 31064 | 1 | PV16 voltage | Int16 | V | 0.1 | R |
| 31065 | 1 | PV16 current | Int16 | A | 0.01 | R |
| 31500 | 1 | DC charger vehicle battery voltage Present when the unit has the integrated DC charger. Documented for hybrid inverters only. | UInt16 | V | 0.1 | R |
| 31501 | 1 | DC charger charging current Documented for hybrid inverters only. | UInt16 | A | 0.1 | R |
| 31502 | 2 | DC charger output power Documented for hybrid inverters only. | Int32 | kW | 0.001 | R |
| 31504 | 1 | DC charger vehicle state of charge Documented for hybrid inverters only. | UInt16 | % | 0.1 | R |
| 31505 | 2 | DC charger current charging capacity Energy of the present charging session. Documented for hybrid inverters only. | UInt32 | kWh | 0.01 | R |
| 31507 | 2 | DC charger current charging duration Duration of the present charging session. Documented for hybrid inverters only. | UInt32 | s | 1 | R |
| 31509 | 2 | PV daily generation | UInt32 | kWh | 0.01 | R |
| 31511 | 2 | PV total generation | UInt32 | kWh | 0.01 | R |
| 40500 | 1 | Inverter Start/Stop 0 = stop, 1 = start. | UInt16 | - | 1 | W |
| 41000 | 1 | DC charger Start/Stop 0 = start, 1 = stop - the opposite of the plant Start/Stop at 40000. Documented for hybrid inverters only. | UInt16 | - | 1 | W |
| 41500 | 1 | Remote EMS dispatch enable 0 = disabled, 1 = enabled. The enabled inverter then reacts only to the power control commands at 41501-41507. Documented for PV inverters only. | UInt16 | - | 1 | RW |
| 41501 | 2 | Active power fixed value adjustment Documented for PV inverters only. | Int32 | kW | 0.001 | R |
| 41503 | 2 | Reactive power fixed value adjustment Documented for PV inverters only. | Int32 | kVar | 0.001 | R |
| 41505 | 1 | Active power percentage adjustment Documented for PV inverters only. | Int16 | % | 0.01 | R |
| 41506 | 1 | Reactive power Q/S adjustment Documented for PV inverters only. | Int16 | % | 0.01 | R |
| 41507 | 1 | Power factor adjustment Documented for PV inverters only. | Int16 | - | 0.001 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: vendor document "Sigenergy Modbus Protocol", V2.7, 2025-05-23, https://www.sigenergy.com/uploads/us_download/1755488219226583.pdf, downloaded 2026-11-23, SHA-256 3b1fb31390a74773b76c6be1f56fad081197639c389ef25dd39289406e2232ce. This seed is the per-inverter block: table 5-3 running information (30500-31511) and table 5-4 parameter setting (40500, 41000, 41500-41507), which the document restricts to a valid inverter's Modbus slave address in the range 1-246. The plant block (30000-30194, 40000-40048), reached at plant address 247, is the separate seed sigenergy-sigenstor. The document prints no factory slave address for an inverter - it is set in the app and must be unique in the plant - so unit ID 1 here is a placeholder to set on site, not a cited default. Addresses are read as printed, so zero-based. The document contradicts itself on reads (4.1: RO answers only 0x04; 6.1 and the worked example 01 03 774C 0002 read a read-only register with 0x03), so the read-only rows stay in the holding area, which 0x03 addresses and the evcc template polls. Tables mark rows as hybrid-inverter only, PV-inverter only or both, and such rows say so in their description. No byte or word order is printed, so BigEndian/HighFirst is a declared convention. Left out: the 64-bit ESS charge and discharge counters 30568/30574, as the format has no 64-bit type and no 32-bit twin is printed (the daily counters 30566/30572 are seeded); the reserved rows 30554 and 30610; and the AC-charger block 32000-32014 with 42000, a separate device. Row 31050 is printed "PV8 current" with unit V and is seeded as PV9 voltage. Writable rows are those the document marks WO or RW with a printed range or enum; 41501-41507 print neither and are seeded read-only. No hardware test is claimed.