  "spec_version": 1,
  "slug": "sigenergy-sigenstor-inverter",
  "manufacturer": "Sigenergy",
  "model": "SigenStor EC / Sigen Hybrid / Sigen PV Max",
  "category": "Solar inverter",
  "supplier_url": "https://www.sigenergy.com/",
  "default_configuration": {
    "protocol": "modbus_tcp",
    "port": 502,
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst"
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 30500,
      "count": 15,
      "name": "Model type",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Model designation of the inverter, packed as ASCII."
    },
    {
      "address": 30515,
      "count": 10,
      "name": "Serial number",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Serial number of the inverter, packed as ASCII."
    },
    {
      "address": 30525,
      "count": 15,
      "name": "Machine firmware version",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Firmware version of the inverter, packed as ASCII."
    },
    {
      "address": 30540,
      "count": 2,
      "name": "Rated active power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30542,
      "count": 2,
      "name": "Maximum apparent power",
      "data_type": "UInt32",
      "units": "kVA",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30544,
      "count": 2,
      "name": "Maximum active power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30546,
      "count": 2,
      "name": "Maximum absorption power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30548,
      "count": 2,
      "name": "Rated battery capacity",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30550,
      "count": 2,
      "name": "ESS rated charging power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30552,
      "count": 2,
      "name": "ESS rated discharging power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30566,
      "count": 2,
      "name": "ESS daily charge energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30572,
      "count": 2,
      "name": "ESS daily discharge energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30578,
      "count": 1,
      "name": "Inverter running state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = standby, 1 = running, 2 = fault, 3 = shutdown, 7 = environmental abnormality."
    },
    {
      "address": 30579,
      "count": 2,
      "name": "Maximum active power adjustment value",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30581,
      "count": 2,
      "name": "Minimum active power adjustment value",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30583,
      "count": 2,
      "name": "Maximum reactive power adjustment value fed to the AC terminal",
      "data_type": "UInt32",
      "units": "kVar",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30585,
      "count": 2,
      "name": "Maximum reactive power adjustment value absorbed from the AC terminal",
      "data_type": "UInt32",
      "units": "kVar",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30587,
      "count": 2,
      "name": "Inverter active power",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30589,
      "count": 2,
      "name": "Inverter reactive power",
      "data_type": "Int32",
      "units": "kVar",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30591,
      "count": 2,
      "name": "ESS maximum battery charging power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30593,
      "count": 2,
      "name": "ESS maximum battery discharging power",
      "data_type": "UInt32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30595,
      "count": 2,
      "name": "ESS available battery charging energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30597,
      "count": 2,
      "name": "ESS available battery discharging energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30599,
      "count": 2,
      "name": "ESS charge/discharge power",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Negative = discharging, positive = charging, the sign the document prints for the plant ESS power at 30037; it prints none for this row, and the evcc template negates the raw value for its own convention. Documented for hybrid inverters only."
    },
    {
      "address": 30601,
      "count": 1,
      "name": "Battery state of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30602,
      "count": 1,
      "name": "Battery state of health",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30603,
      "count": 1,
      "name": "Average cell temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30604,
      "count": 1,
      "name": "Average cell voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30605,
      "count": 1,
      "name": "Alarm 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field of PCS alarm codes; the document's appendix 2 lists codes 1001-1016 on bits 0-15."
    },
    {
      "address": 30606,
      "count": 1,
      "name": "Alarm 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field of PCS alarm codes; the document's appendix 3 lists codes 1017 onwards on bits 0-15."
    },
    {
      "address": 30607,
      "count": 1,
      "name": "Alarm 3",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field of ESS alarm codes; see the document's appendix 4. Documented for hybrid inverters only."
    },
    {
      "address": 30608,
      "count": 1,
      "name": "Alarm 4",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field of gateway alarm codes; see the document's appendix 5."
    },
    {
      "address": 30609,
      "count": 1,
      "name": "Alarm 5",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit field of DC charger alarm codes; see the document's appendix 11. Documented for hybrid inverters only."
    },
    {
      "address": 30613,
      "count": 2,
      "name": "Active power fixed-value adjustment feedback",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30615,
      "count": 2,
      "name": "Reactive power fixed-value adjustment feedback",
      "data_type": "Int32",
      "units": "kVar",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30617,
      "count": 1,
      "name": "Active power percentage adjustment feedback",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30618,
      "count": 1,
      "name": "Reactive power Q/S adjustment feedback",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30619,
      "count": 1,
      "name": "Power factor adjustment feedback",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 30620,
      "count": 1,
      "name": "Maximum battery (cluster) temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30621,
      "count": 1,
      "name": "Minimum battery (cluster) temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30622,
      "count": 1,
      "name": "Maximum battery (cluster) cell voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 30623,
      "count": 1,
      "name": "Minimum battery (cluster) cell voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 31000,
      "count": 1,
      "name": "Rated grid voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31001,
      "count": 1,
      "name": "Rated grid frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31002,
      "count": 1,
      "name": "Grid frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31003,
      "count": 1,
      "name": "PCS internal temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31004,
      "count": 1,
      "name": "Output type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = L/N, 1 = L1/L2/L3, 2 = L1/L2/L3/N, 3 = L1/L2/N."
    },
    {
      "address": 31005,
      "count": 2,
      "name": "A-B line voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31007,
      "count": 2,
      "name": "B-C line voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31009,
      "count": 2,
      "name": "C-A line voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31011,
      "count": 2,
      "name": "Phase A voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "With output type L/N this is the phase-to-neutral voltage."
    },
    {
      "address": 31013,
      "count": 2,
      "name": "Phase B voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31015,
      "count": 2,
      "name": "Phase C voltage",
      "data_type": "UInt32",
      "units": "V",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31017,
      "count": 2,
      "name": "Phase A current",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "With output type L/N this is the phase current."
    },
    {
      "address": 31019,
      "count": 2,
      "name": "Phase B current",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31021,
      "count": 2,
      "name": "Phase C current",
      "data_type": "Int32",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Invalid when the output type is L/N, L1/L2/N."
    },
    {
      "address": 31023,
      "count": 1,
      "name": "Power factor",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31024,
      "count": 1,
      "name": "Pack count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Number of battery packs. Documented for hybrid inverters only."
    },
    {
      "address": 31025,
      "count": 1,
      "name": "PV string count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31026,
      "count": 1,
      "name": "MPPT count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31027,
      "count": 1,
      "name": "PV1 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Present only when the model has this MPPT; the document's applicable-model table lists the string and MPPT counts per model."
    },
    {
      "address": 31028,
      "count": 1,
      "name": "PV1 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31029,
      "count": 1,
      "name": "PV2 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31030,
      "count": 1,
      "name": "PV2 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31031,
      "count": 1,
      "name": "PV3 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31032,
      "count": 1,
      "name": "PV3 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31033,
      "count": 1,
      "name": "PV4 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31034,
      "count": 1,
      "name": "PV4 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31035,
      "count": 2,
      "name": "PV power",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31037,
      "count": 1,
      "name": "Insulation resistance",
      "data_type": "UInt16",
      "units": "MΩ",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31038,
      "count": 2,
      "name": "Start-up time",
      "data_type": "UInt32",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31040,
      "count": 2,
      "name": "Shutdown time",
      "data_type": "UInt32",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31042,
      "count": 1,
      "name": "PV5 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31043,
      "count": 1,
      "name": "PV5 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31044,
      "count": 1,
      "name": "PV6 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31045,
      "count": 1,
      "name": "PV6 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31046,
      "count": 1,
      "name": "PV7 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31047,
      "count": 1,
      "name": "PV7 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31048,
      "count": 1,
      "name": "PV8 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31049,
      "count": 1,
      "name": "PV8 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31050,
      "count": 1,
      "name": "PV9 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document prints this row's label as \"PV8 current\" with unit V; its type, unit and position between PV8 current (31049) and PV9 current (31051) identify it as PV9 voltage, and the seed records that reading rather than copying the label."
    },
    {
      "address": 31051,
      "count": 1,
      "name": "PV9 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31052,
      "count": 1,
      "name": "PV10 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31053,
      "count": 1,
      "name": "PV10 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31054,
      "count": 1,
      "name": "PV11 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31055,
      "count": 1,
      "name": "PV11 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31056,
      "count": 1,
      "name": "PV12 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31057,
      "count": 1,
      "name": "PV12 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31058,
      "count": 1,
      "name": "PV13 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31059,
      "count": 1,
      "name": "PV13 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31060,
      "count": 1,
      "name": "PV14 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31061,
      "count": 1,
      "name": "PV14 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31062,
      "count": 1,
      "name": "PV15 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31063,
      "count": 1,
      "name": "PV15 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31064,
      "count": 1,
      "name": "PV16 voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31065,
      "count": 1,
      "name": "PV16 current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31500,
      "count": 1,
      "name": "DC charger vehicle battery voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Present when the unit has the integrated DC charger. Documented for hybrid inverters only."
    },
    {
      "address": 31501,
      "count": 1,
      "name": "DC charger charging current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 31502,
      "count": 2,
      "name": "DC charger output power",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 31504,
      "count": 1,
      "name": "DC charger vehicle state of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Documented for hybrid inverters only."
    },
    {
      "address": 31505,
      "count": 2,
      "name": "DC charger current charging capacity",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Energy of the present charging session. Documented for hybrid inverters only."
    },
    {
      "address": 31507,
      "count": 2,
      "name": "DC charger current charging duration",
      "data_type": "UInt32",
      "units": "s",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Duration of the present charging session. Documented for hybrid inverters only."
    },
    {
      "address": 31509,
      "count": 2,
      "name": "PV daily generation",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 31511,
      "count": 2,
      "name": "PV total generation",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40500,
      "count": 1,
      "name": "Inverter Start/Stop",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "0 = stop, 1 = start."
    },
    {
      "address": 41000,
      "count": 1,
      "name": "DC charger Start/Stop",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "W",
      "description": "0 = start, 1 = stop - the opposite of the plant Start/Stop at 40000. Documented for hybrid inverters only."
    },
    {
      "address": 41500,
      "count": 1,
      "name": "Remote EMS dispatch enable",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = disabled, 1 = enabled. The enabled inverter then reacts only to the power control commands at 41501-41507. Documented for PV inverters only."
    },
    {
      "address": 41501,
      "count": 2,
      "name": "Active power fixed value adjustment",
      "data_type": "Int32",
      "units": "kW",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for PV inverters only."
    },
    {
      "address": 41503,
      "count": 2,
      "name": "Reactive power fixed value adjustment",
      "data_type": "Int32",
      "units": "kVar",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for PV inverters only."
    },
    {
      "address": 41505,
      "count": 1,
      "name": "Active power percentage adjustment",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for PV inverters only."
    },
    {
      "address": 41506,
      "count": 1,
      "name": "Reactive power Q/S adjustment",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Documented for PV inverters only."
    },
    {
      "address": 41507,
      "count": 1,
      "name": "Power factor adjustment",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Documented for PV inverters only."
    }
  ],
  "combined_registers": [],
  "notes": "Source: vendor document \"Sigenergy Modbus Protocol\", V2.7, 2025-05-23, https://www.sigenergy.com/uploads/us_download/1755488219226583.pdf, downloaded 2026-11-23, SHA-256 3b1fb31390a74773b76c6be1f56fad081197639c389ef25dd39289406e2232ce. This seed is the per-inverter block: table 5-3 running information (30500-31511) and table 5-4 parameter setting (40500, 41000, 41500-41507), which the document restricts to a valid inverter's Modbus slave address in the range 1-246. The plant block (30000-30194, 40000-40048), reached at plant address 247, is the separate seed sigenergy-sigenstor. The document prints no factory slave address for an inverter - it is set in the app and must be unique in the plant - so unit ID 1 here is a placeholder to set on site, not a cited default. Addresses are read as printed, so zero-based. The document contradicts itself on reads (4.1: RO answers only 0x04; 6.1 and the worked example 01 03 774C 0002 read a read-only register with 0x03), so the read-only rows stay in the holding area, which 0x03 addresses and the evcc template polls. Tables mark rows as hybrid-inverter only, PV-inverter only or both, and such rows say so in their description. No byte or word order is printed, so BigEndian/HighFirst is a declared convention. Left out: the 64-bit ESS charge and discharge counters 30568/30574, as the format has no 64-bit type and no 32-bit twin is printed (the daily counters 30566/30572 are seeded); the reserved rows 30554 and 30610; and the AC-charger block 32000-32014 with 42000, a separate device. Row 31050 is printed \"PV8 current\" with unit V and is seeded as PV9 voltage. Writable rows are those the document marks WO or RW with a printed range or enum; 41501-41507 print neither and are seeded read-only. No hardware test is claimed."
}