EVVO utility PV inverter (350 kW class, Utility PV Inverter Communication Protocol V1.0) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
400002
Date settings
0–3155759999 Note see below
UInt32-1RW
400021
Reactive power regulation mode
0–5 0: No reactive power output 1: Power factor regulation 2: Reactive kVar regulation 3: Reactive power ratio regulation ratio regulation
UInt16-1RW
400031
Power factor regulation
[-1, -0.8], [0.8, 1] For example, the register value is 10000, the power factor is 1.0000
Int16-0.001RW
400041
Reactive power kVar regulation
-60% to +60% Pn Pn indicates the rated power (unit: kW) For example, if the rated power is 100 kW, the Pn is 100. The range is -60 to +60 kVar.
Int16kvar0.1RW
400051
Reactive power ratio regulation
-60% to + 60% For example: The register value is 5000, the ratio is 50.00%.
Int16%0.01RW
400111
Active power regulation mode
Pn Indicates the rated power (unit: kW). For example, if the rated power is 100 kW, the Pn is 100. The range of Pn is from -60 to +60 kVar.
UInt16-1RW
400121
Active power value regulation
0–110% Pn. The document gives two gains for this row: 250 kW PV string, Pn 250 kW, range 0–247.5 kW, Gain 100 (register 10000 = 100 kW); 350 kW PV string, Pn 350 kW, range 0–385 kW, Gain 10 (register 1000 = 100 kW). The stored factor is 1/gain of the 350 kW row, which is the model this document covers; on a 250 kW unit read the register with Gain 100 instead.
Int16kW0.1RW
402001
Start command
0: Invalid 1: Start
UInt16-1RW
402011
Shutdown command
0: Invalid 1: Shutdown
UInt16-1RW
402021
Reset command
0: Invalid 1: Reset
UInt16-1RW
402031
SVG startup
0: Invalid 1: Valid
UInt16-1RW
403001
MPPT1 input voltage
Int16V0.1R
403011
MPPT2 input voltage
Int16V0.1R
403021
MPPT3 input voltage
Int16V0.1R
403031
MPPT4 input voltage
Int16V0.1R
403041
MPPT5 input voltage
Int16V0.1R
403051
MPPT6 input voltage
Int16V0.1R
403061
MPPT7 input voltage
Int16V0.1R
403071
MPPT8 input voltage
Int16V0.1R
403081
MPPT9 input voltage
350 kW string not involved
Int16V0.1R
403091
MPPT10 input voltage
Int16V0.1R
403101
MPPT11 input voltage
Int16V0.1R
403111
MPPT12 input voltage
Int16V0.1R
403161
String 01 input current
Int16A0.01R
403171
String 02 input current
Int16A0.01R
403181
String 03 input current
Int16A0.01R
403191
String 04 input current
Int16A0.01R
403201
String 05 input current
Int16A0.01R
403211
String 06 input current
Int16A0.01R
403221
String 07 input current
Int16A0.01R
403231
String 08 input current
Int16A0.01R
403241
String 09 input current
Int16A0.01R
403251
String 10 input current
Int16A0.01R
403261
String 11 input current
Int16A0.01R
403271
String 12 input current
Int16A0.01R
403281
String 13 input current
Int16A0.01R
403291
String 14 input current
Int16A0.01R
403301
String 15 input current
Int16A0.01R
403311
String 16 input current
Int16A0.01R
403321
String 17 input current
Int16A0.01R
403331
String 18 input current
Int16A0.01R
403341
String 19 input current
Int16A0.01R
403351
String 20 input current
Int16A0.01R
403361
String 21 input current
Int16A0.01R
403371
String 22 input current
Int16A0.01R
403381
String 23 input current
Int16A0.01R
403391
String 24 input current
Int16A0.01R
403401
String 25 input current
250 kW string not involved
Int16A0.01R
403411
String 26 input current
Int16A0.01R
403421
String 27 input current
Int16A0.01R
403431
String 28 input current
Int16A0.01R
403441
String 29 input current
Int16A0.01R
403451
String 30 input current
Int16A0.01R
403461
String 31 input current
Int16A0.01R
403471
String 32 input current
Int16A0.01R
403481
MPPT1 input power
UInt16kW0.01R
403491
MPPT2 input power
UInt16kW0.01R
403501
MPPT3 input power
UInt16kW0.01R
403511
MPPT4 input power
UInt16kW0.01R
403521
MPPT5 input power
UInt16kW0.01R
403531
MPPT6 input power
UInt16kW0.01R
403541
MPPT7 input power
UInt16kW0.01R
403551
MPPT8 input power
UInt16kW0.01R
403561
MPPT9 input power
350 kW string not involved
UInt16kW0.01R
403571
MPPT10 input power
UInt16kW0.01R
403581
MPPT11 input power
UInt16kW0.01R
403591
MPPT12 input power
UInt16kW0.01R
403641
Grid AB line voltage
Int16V0.1R
403651
Grid BC line voltage
Int16V0.1R
403661
Grid CA line voltage
Int16V0.1R
403671
Grid A-phase current (Ia)
Int16A0.1R
403681
Grid B-phase current (Ib)
Int16A0.1R
403691
Grid C-phase current (Ic)
Int16A0.1R
403701
Grid frequency
Int16Hz0.01R
403711
AC active power
The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01).
Int16kW0.1R
403721
AC reactive power
The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01).
Int16kvar0.1R
403731
DC input power
The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01).
Int16kW0.1R
403741
Inverter efficiency
9800 means the efficiency is 98.00%
UInt16%0.01R
403751
Power factor
Int16-0.001R
403761
Internal temperature
Int16°C0.1R
403781
Inverter on/off status
0: Shutdown 1: Grid-connected running
UInt16-1R
403791
Inverter state
 Bit0: Standby  Bit1: Standby self- test  Bit2: Start grid connection  Bit3: Grid-connected running  Bit4: Alarm running  Bit5: Limite power running  Bit6: Scheduling running  Bit7: Fault shutdown  Bit8: Command shutdown
UInt16-1R
403802
Daily power generation
UInt32kWh0.01R
403822
Cumulative power generation
UInt32kWh0.01R
403842
CO emission 2 reduction
UInt32kg0.01R
403861
Daily running time
Integer value, calculated by gain
UInt16Hour0.01R
403872
Cumulative running time
UInt32Hour0.01R
403892
Inverter startup time
1. The time_ t format is converted to time. 2. The base time for inverter time calculation is 1970.1.1–00:00:00, and the time zone of the current region should be considered when the server sets time.
UInt32-1R
403912
Inverter shutdown time
UInt32-1R
403931
Inverter fault word 1
 Bit0: RAM self-test failed  Bit1: EEPROM parameters back to default values  Bit2: EEPROM read / write failure  Bit3: FPGA version mismatch  Bit5: Internal communication fault
UInt16-1R
403941
Inverter fault word 2
 Bit0: A-phase hardware overcurrent  Bit1: B-phase hardware overcurrent  Bit2: C-phase hardware overcurrent  Bit3: A-phase CBC timeout  Bit4: B-phase CBC timeout  Bit5: C-phase CBC timeout  Bit6: Busbar hardware overvoltage  Bit7: Bus neutral
UInt16-1R
403951
Inverter fault word 3
 Bit0: Uab overvoltage  Bit1: Ubc overvoltage  Bit2: Uca overvoltage  Bit3: Uab undervoltage  Bit4: Ubc undervoltage  Bit5: Uca undervoltage  Bit8: Grid overfrequency  Bit9: Grid underfrequency  Bit11: Anti-islanding protection  Bit12: AC i
UInt16-1R
403961
Inverter fault word 4
 Bit0: Module A-phase software overcurrent  Bit1: Module B-phase software overcurrent  Bit2: Module C-phase software overcurrent  Bit3: Module current imbalance  Bit4: Filter capacitor undervoltage  Bit5: Module overtemperature  Bit6: Internal
UInt16-1R
403971
Inverter fault word 5
 Bit0: Inverter synchronization overtime  Bit1: Bus short circuit  Bit5: Bus overvoltage  Bit6: Bus undervoltage  Bit7: Bus voltage imbalance
UInt16-1R
403981
Inverter fault word 6
 Bit0: AC relay open circuit  Bit1: AC relay short circuit
UInt16-1R
403991
Inverter fault word 7
 Bit0: Auxiliary power fault  Bit2: Bus hardware overvoltage  Bit3: Hardware overcurrent  Bit4: Unit hardware overcurrent  Bit12: CBC timeout
UInt16-1R
404001
Inverter fault word 8
 Bit0: AD sampling zero drift abnormal  Bit1: RAM self-test failed  Bit2: EEPROM parameters back to default values  Bit3: Historical fault storage failure  Bit4: CAN communication abnormal  Bit7: Bus software overvoltage  Bit8: Unit 1 software
UInt16-1R
404031
Inverter alarm word 3
 Bit6: Grid abnormal  Bit7: Grid voltage imbalance threshold exceeded  Bit10: Grid phase sequence reverse  Bit13: Grid voltage abnormal
UInt16-1R
404041
Inverter alarm word 4
 Bit12: Abnormal high efficiency
UInt16-1R
404051
Inverter alarm word 5
 Bit2: DC voltage detection abnormal  Bit8: DC input voltage high
UInt16-1R
404061
Inverter alarm word 6
 Bit4: AC SPD abnormal
UInt16-1R
404071
Inverter alarm word 7
 Bit0: DC SPD abnormal  Bit6: Booster side open circuit  Bit8: PV string abnormal
UInt16-1R
404091
PID status
0: Not running 1: Normal running
UInt16-1R
404101
Inverter state
0: Standby 1: Power generation 2: Self-derating power generation 3: Power rationing and derating power generation 4: Planned shutdown 5: Power cuts-caused shutdown 6: Fault shutdown Note: Applicable to Xinjiang power grid
UInt16-1R
404111
Inverter state
0: Shutdown / Standby 1: Normal running 2: Maintenance Note: Applicable to Heilongjiang power grid
UInt16-1R
404121
Inverter state
1: Normal running 2: Shutdown 3: Maintenance 4: Standby Note: Applicable to Ningxia power grid
UInt16-1R
404131
Inverter state
0: Fault 1: Normal running 2: Standby 3: Controlled running Note: Applicable to Sichuan power grid
UInt16-1R
404141
Inverter state
1: Normal running 2: Standby 3: Out of service (faulty, maintenance, limited) Note: Applicable to Xibei power grid
UInt16-1R
404151
Inverter state
0: Grid-connected running 1: Standby 2: Limited power 3: Shutdown Note: Applicable to Tianjin power grid
UInt16-1R
404161
Inverter state
 Bit0: Standby  Bit1: Power generation  Bit2: Self-derating power generation  Bit3: Power rationing and derating generation  Bit4: Planned shutdown  Bit5: Power cuts- caused shutdown  Bit6: Fault shutdown Note: Applicable to Xinjiang power gri
UInt16-1R
404171
Inverter state
 Bit0: Standby Bit1: Power generation  Bit2: Self-derating generation  Bit3: Power rationing and derating generation  Bit4: Planned shutdown at the station  Bit5: Planned shutdown off the station  Bit6: Power cuts- caused shutdown
UInt16-1R
406312
Software version_DC_AC
UInt32-1R
406332
Software version_DC_DC
UInt32-1R
406352
Software version_FPGA
UInt32-1R
406372
Parameter version_DC_AC
UInt32-1R
406392
Software version_bootloader
UInt32-1R
406412
Communication protocol version
V000.000.000: Version 1 protocol V001.000.000: Version 2 protocol V002.000.000: Version 3 protocol V003.000.000: Version 4 protocol V004.000.000: Version 5 protocol V005.000.000: Version 6 Protocol V006.000.000: Version 7 protocol V007.000.000: Versi
UInt32-1R
406432
Parameter version_DC_DC
UInt32-1R
406461
Rated power
UInt16kW1R
406471
Rated voltage
UInt16V1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: EVVO "Utility PV Inverter Communication Protocol", V1.0, issue 2023-12-04, vendor-hosted at https://evvosolar.com/doc/Modbus/V4/350Modbus.pdf (SHA-256 81bc41771fa9839344d780ccacc9ba783ef6ede4b47d26d212373f8dc101ac00). Section 2 gives the factory frame: Modbus RTU (RS485) at 9600 bps (also 38400/57600/115200), default device address 1 (range 1-247), 8 data bits, no parity, 1 stop bit. Section 4.1 returns 32-bit values low word first, high word last, so the seed declares LowFirst; section 4.2 defines Gain as a divisor, so the stored factors are 1/gain. The printed addresses are wire addresses: section 7 reads "register address 40500" by sending 0x9E34 with function code 03, so the seed is zero-based and keeps them unchanged. Seeded: the section 6.1 telemetry block 40300-40417 (12 MPPT voltage/current/power inputs, 32 DC string currents, grid and inverter three-phase measurements, energy counters, fault and alarm words, and the per-grid-code state words 40410-40417), the section 6.2 remote-control commands 40200-40203, the section 6.3 remote-regulating block 40000-40013 and the section 6.4 device characteristics 40631-40647. This is the utility/central-inverter variant of the same EVVO protocol family as evvo-string-inverters: the telemetry base differs (40300 vs 40500) and the maps are not interchangeable. Scale decisions, all from the document's own cells: 40012 gives two gains (100 for the 250 kW string, 10 for the 350 kW string) and the seed stores the 350 kW gain 0.1; the gain cell of 40371-40373 is merged across those three rows and also reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent", so AC active power, AC reactive power and DC input power each carry 0.1 for the same reason. Not seeded: the serial number (40601, 30 character registers, no stated encoding). The document has no other register block.