EVVO · Solar inverter
EVVO utility PV inverter (350 kW class, Utility PV Inverter Communication Protocol V1.0) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- Low word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 40000 | 2 | Date settings 0–3155759999 Note see below | UInt32 | - | 1 | RW |
| 40002 | 1 | Reactive power regulation mode 0–5 0: No reactive power output 1: Power factor regulation 2: Reactive kVar regulation 3: Reactive power ratio regulation ratio regulation | UInt16 | - | 1 | RW |
| 40003 | 1 | Power factor regulation [-1, -0.8], [0.8, 1] For example, the register value is 10000, the power factor is 1.0000 | Int16 | - | 0.001 | RW |
| 40004 | 1 | Reactive power kVar regulation -60% to +60% Pn Pn indicates the rated power (unit: kW) For example, if the rated power is 100 kW, the Pn is 100. The range is -60 to +60 kVar. | Int16 | kvar | 0.1 | RW |
| 40005 | 1 | Reactive power ratio regulation -60% to + 60% For example: The register value is 5000, the ratio is 50.00%. | Int16 | % | 0.01 | RW |
| 40011 | 1 | Active power regulation mode Pn Indicates the rated power (unit: kW). For example, if the rated power is 100 kW, the Pn is 100. The range of Pn is from -60 to +60 kVar. | UInt16 | - | 1 | RW |
| 40012 | 1 | Active power value regulation 0–110% Pn. The document gives two gains for this row: 250 kW PV string, Pn 250 kW, range 0–247.5 kW, Gain 100 (register 10000 = 100 kW); 350 kW PV string, Pn 350 kW, range 0–385 kW, Gain 10 (register 1000 = 100 kW). The stored factor is 1/gain of the 350 kW row, which is the model this document covers; on a 250 kW unit read the register with Gain 100 instead. | Int16 | kW | 0.1 | RW |
| 40200 | 1 | Start command 0: Invalid 1: Start | UInt16 | - | 1 | RW |
| 40201 | 1 | Shutdown command 0: Invalid 1: Shutdown | UInt16 | - | 1 | RW |
| 40202 | 1 | Reset command 0: Invalid 1: Reset | UInt16 | - | 1 | RW |
| 40203 | 1 | SVG startup 0: Invalid 1: Valid | UInt16 | - | 1 | RW |
| 40300 | 1 | MPPT1 input voltage | Int16 | V | 0.1 | R |
| 40301 | 1 | MPPT2 input voltage | Int16 | V | 0.1 | R |
| 40302 | 1 | MPPT3 input voltage | Int16 | V | 0.1 | R |
| 40303 | 1 | MPPT4 input voltage | Int16 | V | 0.1 | R |
| 40304 | 1 | MPPT5 input voltage | Int16 | V | 0.1 | R |
| 40305 | 1 | MPPT6 input voltage | Int16 | V | 0.1 | R |
| 40306 | 1 | MPPT7 input voltage | Int16 | V | 0.1 | R |
| 40307 | 1 | MPPT8 input voltage | Int16 | V | 0.1 | R |
| 40308 | 1 | MPPT9 input voltage 350 kW string not involved | Int16 | V | 0.1 | R |
| 40309 | 1 | MPPT10 input voltage | Int16 | V | 0.1 | R |
| 40310 | 1 | MPPT11 input voltage | Int16 | V | 0.1 | R |
| 40311 | 1 | MPPT12 input voltage | Int16 | V | 0.1 | R |
| 40316 | 1 | String 01 input current | Int16 | A | 0.01 | R |
| 40317 | 1 | String 02 input current | Int16 | A | 0.01 | R |
| 40318 | 1 | String 03 input current | Int16 | A | 0.01 | R |
| 40319 | 1 | String 04 input current | Int16 | A | 0.01 | R |
| 40320 | 1 | String 05 input current | Int16 | A | 0.01 | R |
| 40321 | 1 | String 06 input current | Int16 | A | 0.01 | R |
| 40322 | 1 | String 07 input current | Int16 | A | 0.01 | R |
| 40323 | 1 | String 08 input current | Int16 | A | 0.01 | R |
| 40324 | 1 | String 09 input current | Int16 | A | 0.01 | R |
| 40325 | 1 | String 10 input current | Int16 | A | 0.01 | R |
| 40326 | 1 | String 11 input current | Int16 | A | 0.01 | R |
| 40327 | 1 | String 12 input current | Int16 | A | 0.01 | R |
| 40328 | 1 | String 13 input current | Int16 | A | 0.01 | R |
| 40329 | 1 | String 14 input current | Int16 | A | 0.01 | R |
| 40330 | 1 | String 15 input current | Int16 | A | 0.01 | R |
| 40331 | 1 | String 16 input current | Int16 | A | 0.01 | R |
| 40332 | 1 | String 17 input current | Int16 | A | 0.01 | R |
| 40333 | 1 | String 18 input current | Int16 | A | 0.01 | R |
| 40334 | 1 | String 19 input current | Int16 | A | 0.01 | R |
| 40335 | 1 | String 20 input current | Int16 | A | 0.01 | R |
| 40336 | 1 | String 21 input current | Int16 | A | 0.01 | R |
| 40337 | 1 | String 22 input current | Int16 | A | 0.01 | R |
| 40338 | 1 | String 23 input current | Int16 | A | 0.01 | R |
| 40339 | 1 | String 24 input current | Int16 | A | 0.01 | R |
| 40340 | 1 | String 25 input current 250 kW string not involved | Int16 | A | 0.01 | R |
| 40341 | 1 | String 26 input current | Int16 | A | 0.01 | R |
| 40342 | 1 | String 27 input current | Int16 | A | 0.01 | R |
| 40343 | 1 | String 28 input current | Int16 | A | 0.01 | R |
| 40344 | 1 | String 29 input current | Int16 | A | 0.01 | R |
| 40345 | 1 | String 30 input current | Int16 | A | 0.01 | R |
| 40346 | 1 | String 31 input current | Int16 | A | 0.01 | R |
| 40347 | 1 | String 32 input current | Int16 | A | 0.01 | R |
| 40348 | 1 | MPPT1 input power | UInt16 | kW | 0.01 | R |
| 40349 | 1 | MPPT2 input power | UInt16 | kW | 0.01 | R |
| 40350 | 1 | MPPT3 input power | UInt16 | kW | 0.01 | R |
| 40351 | 1 | MPPT4 input power | UInt16 | kW | 0.01 | R |
| 40352 | 1 | MPPT5 input power | UInt16 | kW | 0.01 | R |
| 40353 | 1 | MPPT6 input power | UInt16 | kW | 0.01 | R |
| 40354 | 1 | MPPT7 input power | UInt16 | kW | 0.01 | R |
| 40355 | 1 | MPPT8 input power | UInt16 | kW | 0.01 | R |
| 40356 | 1 | MPPT9 input power 350 kW string not involved | UInt16 | kW | 0.01 | R |
| 40357 | 1 | MPPT10 input power | UInt16 | kW | 0.01 | R |
| 40358 | 1 | MPPT11 input power | UInt16 | kW | 0.01 | R |
| 40359 | 1 | MPPT12 input power | UInt16 | kW | 0.01 | R |
| 40364 | 1 | Grid AB line voltage | Int16 | V | 0.1 | R |
| 40365 | 1 | Grid BC line voltage | Int16 | V | 0.1 | R |
| 40366 | 1 | Grid CA line voltage | Int16 | V | 0.1 | R |
| 40367 | 1 | Grid A-phase current (Ia) | Int16 | A | 0.1 | R |
| 40368 | 1 | Grid B-phase current (Ib) | Int16 | A | 0.1 | R |
| 40369 | 1 | Grid C-phase current (Ic) | Int16 | A | 0.1 | R |
| 40370 | 1 | Grid frequency | Int16 | Hz | 0.01 | R |
| 40371 | 1 | AC active power The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01). | Int16 | kW | 0.1 | R |
| 40372 | 1 | AC reactive power The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01). | Int16 | kvar | 0.1 | R |
| 40373 | 1 | DC input power The document's gain cell is merged across 40371, 40372 and 40373 and reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01). | Int16 | kW | 0.1 | R |
| 40374 | 1 | Inverter efficiency 9800 means the efficiency is 98.00% | UInt16 | % | 0.01 | R |
| 40375 | 1 | Power factor | Int16 | - | 0.001 | R |
| 40376 | 1 | Internal temperature | Int16 | °C | 0.1 | R |
| 40378 | 1 | Inverter on/off status 0: Shutdown 1: Grid-connected running | UInt16 | - | 1 | R |
| 40379 | 1 | Inverter state Bit0: Standby Bit1: Standby self- test Bit2: Start grid connection Bit3: Grid-connected running Bit4: Alarm running Bit5: Limite power running Bit6: Scheduling running Bit7: Fault shutdown Bit8: Command shutdown | UInt16 | - | 1 | R |
| 40380 | 2 | Daily power generation | UInt32 | kWh | 0.01 | R |
| 40382 | 2 | Cumulative power generation | UInt32 | kWh | 0.01 | R |
| 40384 | 2 | CO emission 2 reduction | UInt32 | kg | 0.01 | R |
| 40386 | 1 | Daily running time Integer value, calculated by gain | UInt16 | Hour | 0.01 | R |
| 40387 | 2 | Cumulative running time | UInt32 | Hour | 0.01 | R |
| 40389 | 2 | Inverter startup time 1. The time_ t format is converted to time. 2. The base time for inverter time calculation is 1970.1.1–00:00:00, and the time zone of the current region should be considered when the server sets time. | UInt32 | - | 1 | R |
| 40391 | 2 | Inverter shutdown time | UInt32 | - | 1 | R |
| 40393 | 1 | Inverter fault word 1 Bit0: RAM self-test failed Bit1: EEPROM parameters back to default values Bit2: EEPROM read / write failure Bit3: FPGA version mismatch Bit5: Internal communication fault | UInt16 | - | 1 | R |
| 40394 | 1 | Inverter fault word 2 Bit0: A-phase hardware overcurrent Bit1: B-phase hardware overcurrent Bit2: C-phase hardware overcurrent Bit3: A-phase CBC timeout Bit4: B-phase CBC timeout Bit5: C-phase CBC timeout Bit6: Busbar hardware overvoltage Bit7: Bus neutral | UInt16 | - | 1 | R |
| 40395 | 1 | Inverter fault word 3 Bit0: Uab overvoltage Bit1: Ubc overvoltage Bit2: Uca overvoltage Bit3: Uab undervoltage Bit4: Ubc undervoltage Bit5: Uca undervoltage Bit8: Grid overfrequency Bit9: Grid underfrequency Bit11: Anti-islanding protection Bit12: AC i | UInt16 | - | 1 | R |
| 40396 | 1 | Inverter fault word 4 Bit0: Module A-phase software overcurrent Bit1: Module B-phase software overcurrent Bit2: Module C-phase software overcurrent Bit3: Module current imbalance Bit4: Filter capacitor undervoltage Bit5: Module overtemperature Bit6: Internal | UInt16 | - | 1 | R |
| 40397 | 1 | Inverter fault word 5 Bit0: Inverter synchronization overtime Bit1: Bus short circuit Bit5: Bus overvoltage Bit6: Bus undervoltage Bit7: Bus voltage imbalance | UInt16 | - | 1 | R |
| 40398 | 1 | Inverter fault word 6 Bit0: AC relay open circuit Bit1: AC relay short circuit | UInt16 | - | 1 | R |
| 40399 | 1 | Inverter fault word 7 Bit0: Auxiliary power fault Bit2: Bus hardware overvoltage Bit3: Hardware overcurrent Bit4: Unit hardware overcurrent Bit12: CBC timeout | UInt16 | - | 1 | R |
| 40400 | 1 | Inverter fault word 8 Bit0: AD sampling zero drift abnormal Bit1: RAM self-test failed Bit2: EEPROM parameters back to default values Bit3: Historical fault storage failure Bit4: CAN communication abnormal Bit7: Bus software overvoltage Bit8: Unit 1 software | UInt16 | - | 1 | R |
| 40403 | 1 | Inverter alarm word 3 Bit6: Grid abnormal Bit7: Grid voltage imbalance threshold exceeded Bit10: Grid phase sequence reverse Bit13: Grid voltage abnormal | UInt16 | - | 1 | R |
| 40404 | 1 | Inverter alarm word 4 Bit12: Abnormal high efficiency | UInt16 | - | 1 | R |
| 40405 | 1 | Inverter alarm word 5 Bit2: DC voltage detection abnormal Bit8: DC input voltage high | UInt16 | - | 1 | R |
| 40406 | 1 | Inverter alarm word 6 Bit4: AC SPD abnormal | UInt16 | - | 1 | R |
| 40407 | 1 | Inverter alarm word 7 Bit0: DC SPD abnormal Bit6: Booster side open circuit Bit8: PV string abnormal | UInt16 | - | 1 | R |
| 40409 | 1 | PID status 0: Not running 1: Normal running | UInt16 | - | 1 | R |
| 40410 | 1 | Inverter state 0: Standby 1: Power generation 2: Self-derating power generation 3: Power rationing and derating power generation 4: Planned shutdown 5: Power cuts-caused shutdown 6: Fault shutdown Note: Applicable to Xinjiang power grid | UInt16 | - | 1 | R |
| 40411 | 1 | Inverter state 0: Shutdown / Standby 1: Normal running 2: Maintenance Note: Applicable to Heilongjiang power grid | UInt16 | - | 1 | R |
| 40412 | 1 | Inverter state 1: Normal running 2: Shutdown 3: Maintenance 4: Standby Note: Applicable to Ningxia power grid | UInt16 | - | 1 | R |
| 40413 | 1 | Inverter state 0: Fault 1: Normal running 2: Standby 3: Controlled running Note: Applicable to Sichuan power grid | UInt16 | - | 1 | R |
| 40414 | 1 | Inverter state 1: Normal running 2: Standby 3: Out of service (faulty, maintenance, limited) Note: Applicable to Xibei power grid | UInt16 | - | 1 | R |
| 40415 | 1 | Inverter state 0: Grid-connected running 1: Standby 2: Limited power 3: Shutdown Note: Applicable to Tianjin power grid | UInt16 | - | 1 | R |
| 40416 | 1 | Inverter state Bit0: Standby Bit1: Power generation Bit2: Self-derating power generation Bit3: Power rationing and derating generation Bit4: Planned shutdown Bit5: Power cuts- caused shutdown Bit6: Fault shutdown Note: Applicable to Xinjiang power gri | UInt16 | - | 1 | R |
| 40417 | 1 | Inverter state Bit0: Standby Bit1: Power generation Bit2: Self-derating generation Bit3: Power rationing and derating generation Bit4: Planned shutdown at the station Bit5: Planned shutdown off the station Bit6: Power cuts- caused shutdown | UInt16 | - | 1 | R |
| 40631 | 2 | Software version_DC_AC | UInt32 | - | 1 | R |
| 40633 | 2 | Software version_DC_DC | UInt32 | - | 1 | R |
| 40635 | 2 | Software version_FPGA | UInt32 | - | 1 | R |
| 40637 | 2 | Parameter version_DC_AC | UInt32 | - | 1 | R |
| 40639 | 2 | Software version_bootloader | UInt32 | - | 1 | R |
| 40641 | 2 | Communication protocol version V000.000.000: Version 1 protocol V001.000.000: Version 2 protocol V002.000.000: Version 3 protocol V003.000.000: Version 4 protocol V004.000.000: Version 5 protocol V005.000.000: Version 6 Protocol V006.000.000: Version 7 protocol V007.000.000: Versi | UInt32 | - | 1 | R |
| 40643 | 2 | Parameter version_DC_DC | UInt32 | - | 1 | R |
| 40646 | 1 | Rated power | UInt16 | kW | 1 | R |
| 40647 | 1 | Rated voltage | UInt16 | V | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: EVVO "Utility PV Inverter Communication Protocol", V1.0, issue 2023-12-04, vendor-hosted at https://evvosolar.com/doc/Modbus/V4/350Modbus.pdf (SHA-256 81bc41771fa9839344d780ccacc9ba783ef6ede4b47d26d212373f8dc101ac00). Section 2 gives the factory frame: Modbus RTU (RS485) at 9600 bps (also 38400/57600/115200), default device address 1 (range 1-247), 8 data bits, no parity, 1 stop bit. Section 4.1 returns 32-bit values low word first, high word last, so the seed declares LowFirst; section 4.2 defines Gain as a divisor, so the stored factors are 1/gain. The printed addresses are wire addresses: section 7 reads "register address 40500" by sending 0x9E34 with function code 03, so the seed is zero-based and keeps them unchanged. Seeded: the section 6.1 telemetry block 40300-40417 (12 MPPT voltage/current/power inputs, 32 DC string currents, grid and inverter three-phase measurements, energy counters, fault and alarm words, and the per-grid-code state words 40410-40417), the section 6.2 remote-control commands 40200-40203, the section 6.3 remote-regulating block 40000-40013 and the section 6.4 device characteristics 40631-40647. This is the utility/central-inverter variant of the same EVVO protocol family as evvo-string-inverters: the telemetry base differs (40300 vs 40500) and the maps are not interchangeable. Scale decisions, all from the document's own cells: 40012 gives two gains (100 for the 250 kW string, 10 for the 350 kW string) and the seed stores the 350 kW gain 0.1; the gain cell of 40371-40373 is merged across those three rows and also reads "250 kW: 100 / 350 kW: 10" with the note "Model dependent", so AC active power, AC reactive power and DC input power each carry 0.1 for the same reason. Not seeded: the serial number (40601, 30 character registers, no stated encoding). The document has no other register block.