EVVO PV grid-connected string inverters (EVVO V4 Modbus protocol, 36-110 kW class) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
400002
Date and time setting
UInt32-1RW
400021
Reactive power regulation mode
UInt16-1RW
400031
Power factor regulation
Int16-0.0001RW
400041
Reactive power kVar regulation
Int16kvar0.1RW
400051
Reactive power ratio regulation
Int16%0.01RW
400111
Active power regulation mode
UInt16-1RW
400121
Active power actual regulation
Int16kW0.01RW
400131
Active power ratio regulation
Int16%0.01RW
402001
Startup command
UInt16-1RW
402011
Shutdown command
UInt16-1RW
402021
Reset command
UInt16-1RW
402031
SVG startup
UInt16-1RW
405001
MPPT1 input voltage
Int16V0.1R
405011
MPPT2 input voltage
Int16V0.1R
405021
MPPT3 input voltage
Int16V0.1R
405031
MPPT4 input voltage
Int16V0.1R
405041
MPPT5 input voltage
Int16V0.1R
405051
MPPT6 input voltage
Int16V0.1R
405061
MPPT7 input voltage
Int16V0.1R
405071
MPPT8 input voltage
Int16V0.1R
405081
String 01 input current
Int16A0.01R
405091
String 02 input current
Int16A0.01R
405101
String 03 input current
Int16A0.01R
405111
String 04 input current
Int16A0.01R
405121
String 05 input current
Int16A0.01R
405131
String 06 input current
Int16A0.01R
405141
String 07 input current
Int16A0.01R
405151
String 08 input current
Int16A0.01R
405161
String 09 input current
Int16A0.01R
405171
String 10 input current
Int16A0.01R
405181
String 11 input current
Int16A0.01R
405191
String 12 input current
Int16A0.01R
405201
String 13 input current
Int16A0.01R
405211
String 14 input current
Int16A0.01R
405221
String 15 input current
Int16A0.01R
405231
String 16 input current
Int16A0.01R
405241
MPPT1 input power
UInt16kW0.01R
405251
MPPT2 input power
UInt16kW0.01R
405261
MPPT3 input power
UInt16kW0.01R
405271
MPPT4 input power
UInt16kW0.01R
405281
MPPT5 input power
UInt16kW0.01R
405291
MPPT6 input power
UInt16kW0.01R
405301
MPPT7 input power
UInt16kW0.01R
405311
MPPT8 input power
UInt16kW0.01R
405321
Power grid line AB voltage
Int16V0.1R
405331
Power grid line BC voltage
Int16V0.1R
405341
Power grid line AC voltage
Int16V0.1R
405351
Grid A-phase current (Ia)
Int16A0.1R
405361
Grid B-phase current (Ib)
Int16A0.1R
405371
Grid C-phase current (Ic)
Int16A0.1R
405381
Grid frequency (the document prints the name "Grid power" with unit Hz)
Int16Hz0.01R
405391
AC active power
Int16kW0.01R
405401
AC reactive power
Int16kvar0.01R
405411
DC input power
Int16kW0.01R
405421
Inverter efficiency
UInt16%0.01R
405431
Power factor
Int16-0.001R
405441
Internal machine temperature
Int16°C0.1R
405451
Insulation resistance
UInt16kΩ0.1R
405461
Inverter switch status
UInt16-1R
405471
Inverter status
UInt16-1R
405482
Energy genereated for the day
UInt32kWh0.01R
405502
Total generated energy
UInt32kWh0.01R
405522
CO2 emission reduction amount
UInt32kg0.01R
405541
Daily running time
Hours; the document prints the unit as Hour
UInt16h0.01R
405552
Total running time
Hours; the document prints the unit as Hour
UInt32h0.01R
405572
Inverter startup time
UInt32-1R
405592
Inverter shutdown time
UInt32-1R
405611
Inverter fault word 1
UInt16-1R
405621
Inverter fault word 2
UInt16-1R
405631
Inverter fault word 3
UInt16-1R
405641
Inverter fault word 4
UInt16-1R
405651
Inverter fault word 5
UInt16-1R
405661
Inverter fault word 6
UInt16-1R
405671
Inverter fault word 7
UInt16-1R
405681
Inverter fault word 8
UInt16-1R
405691
Inverter alarm word 1
UInt16-1R
405701
Inverter alarm word 2
UInt16-1R
405711
Inverter alarm word 3
UInt16-1R
405721
Inverter alarm word 4
UInt16-1R
405731
Inverter alarm word 5
UInt16-1R
405741
Inverter alarm word 6
UInt16-1R
405751
Inverter alarm word 7
UInt16-1R
405761
Inverter alarm word 8
UInt16-1R
405771
PID status
UInt16-1R
405781
Running status of the inverter
UInt16-1R
405791
Running status of the inverter
UInt16-1R
405801
Running status of the inverter
UInt16-1R
405811
Running status of the inverter
UInt16-1R
405821
Running status of the inverter
UInt16-1R
405831
Running status of the inverter
UInt16-1R
405841
Running status of the inverter
UInt16-1R
405851
Running status of the inverter
UInt16-1R
405861
Busbar voltage
Int16V0.1R
405871
Positive bus voltage
Int16V0.1R
405881
String 17 input current
Int16A0.01R
405891
String 18 input current
Int16A0.01R
405901
String 19 input current
Int16A0.01R
405911
String 20 input current
Int16A0.01R
405921
Fault code
UInt16-1R
405931
Alarm code
UInt16-1R
405941
AC apparent power
Int16kVA0.01R
406312
Software version _DC_AC
UInt32-1R
406332
Software version _DC_DC
UInt32-1R
406352
Software version _FPGA
UInt32-1R
406372
Parameter version _DC_AC
UInt32-1R
406392
Software version_ bootloader
UInt32-1R
406412
Communication protocol version
UInt32-1R
406432
Parameter version _DC_DC
UInt32-1R
406461
Rated power
UInt16kW1R
406471
Rated voltage
UInt16V1R
420002
Countercurrent active power
Int32kW0.001R
420022
Power taking active power of the grid
Int32kW0.001R
420042
Loads consumed active power
Int32kW0.001R
420062
Total backflow electricity
Int32kWh0.01R
420082
Total electricity taken from the grid
Int32kWh0.01R
420102
Total electricity consumed by the load
Int32kWh0.01R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: EVVO "Communication Protocol of PV Grid-Connected String Inverters" (EVVO V4 Modbus), V1.0, 2022-12-07, vendor-hosted at https://evvosolar.com/doc/Modbus/V4/36_110Modbus.pdf (SHA-256 4bdc090129af7fe3cd6fb4af43aa5341cfa62c478d64fa74f4707ac60a9b70e5). Section 2 gives the factory serial frame: 9600 bps (also settable to 38400/57600/115200), device address 1 (range 1-247), 1 start bit, 8 data bits, no parity, 1 stop bit. Section 3 reads with function code 0x03 (so every row is a holding register) and writes with 0x06/0x10; section 4.1 returns 32-bit values low word first, hence LowFirst; section 4.2 defines Gain as a divisor, so the stored factors are 1/gain. The printed addresses are wire addresses: section 8 reads "register address 40500" by sending 0x9E34 (= 40500) with function code 03, so the seed is zero-based and stores them unchanged. Seeded: the section 6.1 telemetry block 40500-40594 (MPPT and string inputs, grid and machine measurements, fault/alarm words, running status and energy counters), the 42000-42011 backflow counters, the section 6.2 remote-control commands 40200-40203, the section 6.3 remote-regulating block 40000-40013 and the section 6.4 device-characteristic block 40631-40647; 40000-40203 are writable and marked RW. Register 40538 keeps the document's own wording, which names it "Grid power" while giving the unit Hz: it is the grid frequency, and the row says so. Units follow the document apart from spellings normalised to the library (HZ/Hz, kVar/kvar, Hour/h). Not seeded: the serial number (40601, 30 character registers, no stated encoding), the unnamed "Data" filler rows (40595-40599, 40600, 40645, 40648-40650), the rows its page breaks repeat (40562/40564/40568/40585) and the section 7 APP protocol block (1080, 1082, 30000-30130, 31112/31114, 32000-32005), the vendor's app-setting surface. EVVO inverters are Hopewind OEM hardware: this is the EVVO-branded map, and no separate Hopewind seed was added for the same platform.