EVVO · Solar inverter
EVVO PV grid-connected string inverters (EVVO V4 Modbus protocol, 36-110 kW class) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- Low word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 40000 | 2 | Date and time setting | UInt32 | - | 1 | RW |
| 40002 | 1 | Reactive power regulation mode | UInt16 | - | 1 | RW |
| 40003 | 1 | Power factor regulation | Int16 | - | 0.0001 | RW |
| 40004 | 1 | Reactive power kVar regulation | Int16 | kvar | 0.1 | RW |
| 40005 | 1 | Reactive power ratio regulation | Int16 | % | 0.01 | RW |
| 40011 | 1 | Active power regulation mode | UInt16 | - | 1 | RW |
| 40012 | 1 | Active power actual regulation | Int16 | kW | 0.01 | RW |
| 40013 | 1 | Active power ratio regulation | Int16 | % | 0.01 | RW |
| 40200 | 1 | Startup command | UInt16 | - | 1 | RW |
| 40201 | 1 | Shutdown command | UInt16 | - | 1 | RW |
| 40202 | 1 | Reset command | UInt16 | - | 1 | RW |
| 40203 | 1 | SVG startup | UInt16 | - | 1 | RW |
| 40500 | 1 | MPPT1 input voltage | Int16 | V | 0.1 | R |
| 40501 | 1 | MPPT2 input voltage | Int16 | V | 0.1 | R |
| 40502 | 1 | MPPT3 input voltage | Int16 | V | 0.1 | R |
| 40503 | 1 | MPPT4 input voltage | Int16 | V | 0.1 | R |
| 40504 | 1 | MPPT5 input voltage | Int16 | V | 0.1 | R |
| 40505 | 1 | MPPT6 input voltage | Int16 | V | 0.1 | R |
| 40506 | 1 | MPPT7 input voltage | Int16 | V | 0.1 | R |
| 40507 | 1 | MPPT8 input voltage | Int16 | V | 0.1 | R |
| 40508 | 1 | String 01 input current | Int16 | A | 0.01 | R |
| 40509 | 1 | String 02 input current | Int16 | A | 0.01 | R |
| 40510 | 1 | String 03 input current | Int16 | A | 0.01 | R |
| 40511 | 1 | String 04 input current | Int16 | A | 0.01 | R |
| 40512 | 1 | String 05 input current | Int16 | A | 0.01 | R |
| 40513 | 1 | String 06 input current | Int16 | A | 0.01 | R |
| 40514 | 1 | String 07 input current | Int16 | A | 0.01 | R |
| 40515 | 1 | String 08 input current | Int16 | A | 0.01 | R |
| 40516 | 1 | String 09 input current | Int16 | A | 0.01 | R |
| 40517 | 1 | String 10 input current | Int16 | A | 0.01 | R |
| 40518 | 1 | String 11 input current | Int16 | A | 0.01 | R |
| 40519 | 1 | String 12 input current | Int16 | A | 0.01 | R |
| 40520 | 1 | String 13 input current | Int16 | A | 0.01 | R |
| 40521 | 1 | String 14 input current | Int16 | A | 0.01 | R |
| 40522 | 1 | String 15 input current | Int16 | A | 0.01 | R |
| 40523 | 1 | String 16 input current | Int16 | A | 0.01 | R |
| 40524 | 1 | MPPT1 input power | UInt16 | kW | 0.01 | R |
| 40525 | 1 | MPPT2 input power | UInt16 | kW | 0.01 | R |
| 40526 | 1 | MPPT3 input power | UInt16 | kW | 0.01 | R |
| 40527 | 1 | MPPT4 input power | UInt16 | kW | 0.01 | R |
| 40528 | 1 | MPPT5 input power | UInt16 | kW | 0.01 | R |
| 40529 | 1 | MPPT6 input power | UInt16 | kW | 0.01 | R |
| 40530 | 1 | MPPT7 input power | UInt16 | kW | 0.01 | R |
| 40531 | 1 | MPPT8 input power | UInt16 | kW | 0.01 | R |
| 40532 | 1 | Power grid line AB voltage | Int16 | V | 0.1 | R |
| 40533 | 1 | Power grid line BC voltage | Int16 | V | 0.1 | R |
| 40534 | 1 | Power grid line AC voltage | Int16 | V | 0.1 | R |
| 40535 | 1 | Grid A-phase current (Ia) | Int16 | A | 0.1 | R |
| 40536 | 1 | Grid B-phase current (Ib) | Int16 | A | 0.1 | R |
| 40537 | 1 | Grid C-phase current (Ic) | Int16 | A | 0.1 | R |
| 40538 | 1 | Grid frequency (the document prints the name "Grid power" with unit Hz) | Int16 | Hz | 0.01 | R |
| 40539 | 1 | AC active power | Int16 | kW | 0.01 | R |
| 40540 | 1 | AC reactive power | Int16 | kvar | 0.01 | R |
| 40541 | 1 | DC input power | Int16 | kW | 0.01 | R |
| 40542 | 1 | Inverter efficiency | UInt16 | % | 0.01 | R |
| 40543 | 1 | Power factor | Int16 | - | 0.001 | R |
| 40544 | 1 | Internal machine temperature | Int16 | °C | 0.1 | R |
| 40545 | 1 | Insulation resistance | UInt16 | kΩ | 0.1 | R |
| 40546 | 1 | Inverter switch status | UInt16 | - | 1 | R |
| 40547 | 1 | Inverter status | UInt16 | - | 1 | R |
| 40548 | 2 | Energy genereated for the day | UInt32 | kWh | 0.01 | R |
| 40550 | 2 | Total generated energy | UInt32 | kWh | 0.01 | R |
| 40552 | 2 | CO2 emission reduction amount | UInt32 | kg | 0.01 | R |
| 40554 | 1 | Daily running time Hours; the document prints the unit as Hour | UInt16 | h | 0.01 | R |
| 40555 | 2 | Total running time Hours; the document prints the unit as Hour | UInt32 | h | 0.01 | R |
| 40557 | 2 | Inverter startup time | UInt32 | - | 1 | R |
| 40559 | 2 | Inverter shutdown time | UInt32 | - | 1 | R |
| 40561 | 1 | Inverter fault word 1 | UInt16 | - | 1 | R |
| 40562 | 1 | Inverter fault word 2 | UInt16 | - | 1 | R |
| 40563 | 1 | Inverter fault word 3 | UInt16 | - | 1 | R |
| 40564 | 1 | Inverter fault word 4 | UInt16 | - | 1 | R |
| 40565 | 1 | Inverter fault word 5 | UInt16 | - | 1 | R |
| 40566 | 1 | Inverter fault word 6 | UInt16 | - | 1 | R |
| 40567 | 1 | Inverter fault word 7 | UInt16 | - | 1 | R |
| 40568 | 1 | Inverter fault word 8 | UInt16 | - | 1 | R |
| 40569 | 1 | Inverter alarm word 1 | UInt16 | - | 1 | R |
| 40570 | 1 | Inverter alarm word 2 | UInt16 | - | 1 | R |
| 40571 | 1 | Inverter alarm word 3 | UInt16 | - | 1 | R |
| 40572 | 1 | Inverter alarm word 4 | UInt16 | - | 1 | R |
| 40573 | 1 | Inverter alarm word 5 | UInt16 | - | 1 | R |
| 40574 | 1 | Inverter alarm word 6 | UInt16 | - | 1 | R |
| 40575 | 1 | Inverter alarm word 7 | UInt16 | - | 1 | R |
| 40576 | 1 | Inverter alarm word 8 | UInt16 | - | 1 | R |
| 40577 | 1 | PID status | UInt16 | - | 1 | R |
| 40578 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40579 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40580 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40581 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40582 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40583 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40584 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40585 | 1 | Running status of the inverter | UInt16 | - | 1 | R |
| 40586 | 1 | Busbar voltage | Int16 | V | 0.1 | R |
| 40587 | 1 | Positive bus voltage | Int16 | V | 0.1 | R |
| 40588 | 1 | String 17 input current | Int16 | A | 0.01 | R |
| 40589 | 1 | String 18 input current | Int16 | A | 0.01 | R |
| 40590 | 1 | String 19 input current | Int16 | A | 0.01 | R |
| 40591 | 1 | String 20 input current | Int16 | A | 0.01 | R |
| 40592 | 1 | Fault code | UInt16 | - | 1 | R |
| 40593 | 1 | Alarm code | UInt16 | - | 1 | R |
| 40594 | 1 | AC apparent power | Int16 | kVA | 0.01 | R |
| 40631 | 2 | Software version _DC_AC | UInt32 | - | 1 | R |
| 40633 | 2 | Software version _DC_DC | UInt32 | - | 1 | R |
| 40635 | 2 | Software version _FPGA | UInt32 | - | 1 | R |
| 40637 | 2 | Parameter version _DC_AC | UInt32 | - | 1 | R |
| 40639 | 2 | Software version_ bootloader | UInt32 | - | 1 | R |
| 40641 | 2 | Communication protocol version | UInt32 | - | 1 | R |
| 40643 | 2 | Parameter version _DC_DC | UInt32 | - | 1 | R |
| 40646 | 1 | Rated power | UInt16 | kW | 1 | R |
| 40647 | 1 | Rated voltage | UInt16 | V | 1 | R |
| 42000 | 2 | Countercurrent active power | Int32 | kW | 0.001 | R |
| 42002 | 2 | Power taking active power of the grid | Int32 | kW | 0.001 | R |
| 42004 | 2 | Loads consumed active power | Int32 | kW | 0.001 | R |
| 42006 | 2 | Total backflow electricity | Int32 | kWh | 0.01 | R |
| 42008 | 2 | Total electricity taken from the grid | Int32 | kWh | 0.01 | R |
| 42010 | 2 | Total electricity consumed by the load | Int32 | kWh | 0.01 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: EVVO "Communication Protocol of PV Grid-Connected String Inverters" (EVVO V4 Modbus), V1.0, 2022-12-07, vendor-hosted at https://evvosolar.com/doc/Modbus/V4/36_110Modbus.pdf (SHA-256 4bdc090129af7fe3cd6fb4af43aa5341cfa62c478d64fa74f4707ac60a9b70e5). Section 2 gives the factory serial frame: 9600 bps (also settable to 38400/57600/115200), device address 1 (range 1-247), 1 start bit, 8 data bits, no parity, 1 stop bit. Section 3 reads with function code 0x03 (so every row is a holding register) and writes with 0x06/0x10; section 4.1 returns 32-bit values low word first, hence LowFirst; section 4.2 defines Gain as a divisor, so the stored factors are 1/gain. The printed addresses are wire addresses: section 8 reads "register address 40500" by sending 0x9E34 (= 40500) with function code 03, so the seed is zero-based and stores them unchanged. Seeded: the section 6.1 telemetry block 40500-40594 (MPPT and string inputs, grid and machine measurements, fault/alarm words, running status and energy counters), the 42000-42011 backflow counters, the section 6.2 remote-control commands 40200-40203, the section 6.3 remote-regulating block 40000-40013 and the section 6.4 device-characteristic block 40631-40647; 40000-40203 are writable and marked RW. Register 40538 keeps the document's own wording, which names it "Grid power" while giving the unit Hz: it is the grid frequency, and the row says so. Units follow the document apart from spellings normalised to the library (HZ/Hz, kVar/kvar, Hour/h). Not seeded: the serial number (40601, 30 character registers, no stated encoding), the unnamed "Data" filler rows (40595-40599, 40600, 40645, 40648-40650), the rows its page breaks repeat (40562/40564/40568/40585) and the section 7 APP protocol block (1080, 1082, 30000-30130, 31112/31114, 32000-32005), the vendor's app-setting surface. EVVO inverters are Hopewind OEM hardware: this is the EVVO-branded map, and no separate Hopewind seed was added for the same platform.