  "spec_version": 1,
  "slug": "evvo-utility-pv-inverter",
  "manufacturer": "EVVO",
  "model": "EVVO utility PV inverter (350 kW class, Utility PV Inverter Communication Protocol V1.0)",
  "category": "Solar inverter",
  "supplier_url": "https://evvosolar.com/",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "LowFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 9600,
      "parity": "None",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 40000,
      "count": 2,
      "name": "Date settings",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0–3155759999 Note see below"
    },
    {
      "address": 40002,
      "count": 1,
      "name": "Reactive power regulation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0–5 0: No reactive power output 1: Power factor regulation 2: Reactive kVar regulation 3: Reactive power ratio regulation ratio regulation"
    },
    {
      "address": 40003,
      "count": 1,
      "name": "Power factor regulation",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "RW",
      "description": "[-1, -0.8], [0.8, 1] For example, the register value is 10000, the power factor is 1.0000"
    },
    {
      "address": 40004,
      "count": 1,
      "name": "Reactive power kVar regulation",
      "data_type": "Int16",
      "units": "kvar",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "-60% to +60% Pn Pn indicates the rated power (unit: kW) For example, if the rated power is 100 kW, the Pn is 100. The range is -60 to +60 kVar."
    },
    {
      "address": 40005,
      "count": 1,
      "name": "Reactive power ratio regulation",
      "data_type": "Int16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "RW",
      "description": "-60% to + 60% For example: The register value is 5000, the ratio is 50.00%."
    },
    {
      "address": 40011,
      "count": 1,
      "name": "Active power regulation mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Pn Indicates the rated power (unit: kW). For example, if the rated power is 100 kW, the Pn is 100. The range of Pn is from -60 to +60 kVar."
    },
    {
      "address": 40012,
      "count": 1,
      "name": "Active power value regulation",
      "data_type": "Int16",
      "units": "kW",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "RW",
      "description": "0–110% Pn. The document gives two gains for this row: 250 kW PV string, Pn 250 kW, range 0–247.5 kW, Gain 100 (register 10000 = 100 kW); 350 kW PV string, Pn 350 kW, range 0–385 kW, Gain 10 (register 1000 = 100 kW). The stored factor is 1/gain of the 350 kW row, which is the model this document covers; on a 250 kW unit read the register with Gain 100 instead."
    },
    {
      "address": 40200,
      "count": 1,
      "name": "Start command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0: Invalid 1: Start"
    },
    {
      "address": 40201,
      "count": 1,
      "name": "Shutdown command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0: Invalid 1: Shutdown"
    },
    {
      "address": 40202,
      "count": 1,
      "name": "Reset command",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0: Invalid 1: Reset"
    },
    {
      "address": 40203,
      "count": 1,
      "name": "SVG startup",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0: Invalid 1: Valid"
    },
    {
      "address": 40300,
      "count": 1,
      "name": "MPPT1 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40301,
      "count": 1,
      "name": "MPPT2 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40302,
      "count": 1,
      "name": "MPPT3 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40303,
      "count": 1,
      "name": "MPPT4 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40304,
      "count": 1,
      "name": "MPPT5 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40305,
      "count": 1,
      "name": "MPPT6 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40306,
      "count": 1,
      "name": "MPPT7 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40307,
      "count": 1,
      "name": "MPPT8 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40308,
      "count": 1,
      "name": "MPPT9 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "350 kW string not involved"
    },
    {
      "address": 40309,
      "count": 1,
      "name": "MPPT10 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40310,
      "count": 1,
      "name": "MPPT11 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40311,
      "count": 1,
      "name": "MPPT12 input voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40316,
      "count": 1,
      "name": "String 01 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40317,
      "count": 1,
      "name": "String 02 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40318,
      "count": 1,
      "name": "String 03 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40319,
      "count": 1,
      "name": "String 04 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40320,
      "count": 1,
      "name": "String 05 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40321,
      "count": 1,
      "name": "String 06 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40322,
      "count": 1,
      "name": "String 07 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40323,
      "count": 1,
      "name": "String 08 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40324,
      "count": 1,
      "name": "String 09 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40325,
      "count": 1,
      "name": "String 10 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40326,
      "count": 1,
      "name": "String 11 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40327,
      "count": 1,
      "name": "String 12 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40328,
      "count": 1,
      "name": "String 13 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40329,
      "count": 1,
      "name": "String 14 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40330,
      "count": 1,
      "name": "String 15 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40331,
      "count": 1,
      "name": "String 16 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40332,
      "count": 1,
      "name": "String 17 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40333,
      "count": 1,
      "name": "String 18 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40334,
      "count": 1,
      "name": "String 19 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40335,
      "count": 1,
      "name": "String 20 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40336,
      "count": 1,
      "name": "String 21 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40337,
      "count": 1,
      "name": "String 22 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40338,
      "count": 1,
      "name": "String 23 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40339,
      "count": 1,
      "name": "String 24 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40340,
      "count": 1,
      "name": "String 25 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "250 kW string not involved"
    },
    {
      "address": 40341,
      "count": 1,
      "name": "String 26 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40342,
      "count": 1,
      "name": "String 27 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40343,
      "count": 1,
      "name": "String 28 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40344,
      "count": 1,
      "name": "String 29 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40345,
      "count": 1,
      "name": "String 30 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40346,
      "count": 1,
      "name": "String 31 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40347,
      "count": 1,
      "name": "String 32 input current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40348,
      "count": 1,
      "name": "MPPT1 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40349,
      "count": 1,
      "name": "MPPT2 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40350,
      "count": 1,
      "name": "MPPT3 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40351,
      "count": 1,
      "name": "MPPT4 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40352,
      "count": 1,
      "name": "MPPT5 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40353,
      "count": 1,
      "name": "MPPT6 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40354,
      "count": 1,
      "name": "MPPT7 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40355,
      "count": 1,
      "name": "MPPT8 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40356,
      "count": 1,
      "name": "MPPT9 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "350 kW string not involved"
    },
    {
      "address": 40357,
      "count": 1,
      "name": "MPPT10 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40358,
      "count": 1,
      "name": "MPPT11 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40359,
      "count": 1,
      "name": "MPPT12 input power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40364,
      "count": 1,
      "name": "Grid AB line voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40365,
      "count": 1,
      "name": "Grid BC line voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40366,
      "count": 1,
      "name": "Grid CA line voltage",
      "data_type": "Int16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40367,
      "count": 1,
      "name": "Grid A-phase current (Ia)",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40368,
      "count": 1,
      "name": "Grid B-phase current (Ib)",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40369,
      "count": 1,
      "name": "Grid C-phase current (Ic)",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40370,
      "count": 1,
      "name": "Grid frequency",
      "data_type": "Int16",
      "units": "Hz",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40371,
      "count": 1,
      "name": "AC active power",
      "data_type": "Int16",
      "units": "kW",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document's gain cell is merged across 40371, 40372 and 40373 and reads \"250 kW: 100 / 350 kW: 10\" with the note \"Model dependent\"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01)."
    },
    {
      "address": 40372,
      "count": 1,
      "name": "AC reactive power",
      "data_type": "Int16",
      "units": "kvar",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document's gain cell is merged across 40371, 40372 and 40373 and reads \"250 kW: 100 / 350 kW: 10\" with the note \"Model dependent\"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01)."
    },
    {
      "address": 40373,
      "count": 1,
      "name": "DC input power",
      "data_type": "Int16",
      "units": "kW",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The document's gain cell is merged across 40371, 40372 and 40373 and reads \"250 kW: 100 / 350 kW: 10\" with the note \"Model dependent\"; the seed stores the 350 kW gain 0.1 (a 250 kW unit needs 0.01)."
    },
    {
      "address": 40374,
      "count": 1,
      "name": "Inverter efficiency",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "9800 means the efficiency is 98.00%"
    },
    {
      "address": 40375,
      "count": 1,
      "name": "Power factor",
      "data_type": "Int16",
      "units": "",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40376,
      "count": 1,
      "name": "Internal temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40378,
      "count": 1,
      "name": "Inverter on/off status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Shutdown 1: Grid-connected running"
    },
    {
      "address": 40379,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Standby  Bit1: Standby self- test  Bit2: Start grid connection  Bit3: Grid-connected running  Bit4: Alarm running  Bit5: Limite power running  Bit6: Scheduling running  Bit7: Fault shutdown  Bit8: Command shutdown"
    },
    {
      "address": 40380,
      "count": 2,
      "name": "Daily power generation",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40382,
      "count": 2,
      "name": "Cumulative power generation",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40384,
      "count": 2,
      "name": "CO emission 2 reduction",
      "data_type": "UInt32",
      "units": "kg",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40386,
      "count": 1,
      "name": "Daily running time",
      "data_type": "UInt16",
      "units": "Hour",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R",
      "description": "Integer value, calculated by gain"
    },
    {
      "address": 40387,
      "count": 2,
      "name": "Cumulative running time",
      "data_type": "UInt32",
      "units": "Hour",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40389,
      "count": 2,
      "name": "Inverter startup time",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "1. The time_ t format is converted to time. 2. The base time for inverter time calculation is 1970.1.1–00:00:00, and the time zone of the current region should be considered when the server sets time."
    },
    {
      "address": 40391,
      "count": 2,
      "name": "Inverter shutdown time",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40393,
      "count": 1,
      "name": "Inverter fault word 1",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: RAM self-test failed  Bit1: EEPROM parameters back to default values  Bit2: EEPROM read / write failure  Bit3: FPGA version mismatch  Bit5: Internal communication fault"
    },
    {
      "address": 40394,
      "count": 1,
      "name": "Inverter fault word 2",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: A-phase hardware overcurrent  Bit1: B-phase hardware overcurrent  Bit2: C-phase hardware overcurrent  Bit3: A-phase CBC timeout  Bit4: B-phase CBC timeout  Bit5: C-phase CBC timeout  Bit6: Busbar hardware overvoltage  Bit7: Bus neutral"
    },
    {
      "address": 40395,
      "count": 1,
      "name": "Inverter fault word 3",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Uab overvoltage  Bit1: Ubc overvoltage  Bit2: Uca overvoltage  Bit3: Uab undervoltage  Bit4: Ubc undervoltage  Bit5: Uca undervoltage  Bit8: Grid overfrequency  Bit9: Grid underfrequency  Bit11: Anti-islanding protection  Bit12: AC i"
    },
    {
      "address": 40396,
      "count": 1,
      "name": "Inverter fault word 4",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Module A-phase software overcurrent  Bit1: Module B-phase software overcurrent  Bit2: Module C-phase software overcurrent  Bit3: Module current imbalance  Bit4: Filter capacitor undervoltage  Bit5: Module overtemperature  Bit6: Internal"
    },
    {
      "address": 40397,
      "count": 1,
      "name": "Inverter fault word 5",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Inverter synchronization overtime  Bit1: Bus short circuit  Bit5: Bus overvoltage  Bit6: Bus undervoltage  Bit7: Bus voltage imbalance"
    },
    {
      "address": 40398,
      "count": 1,
      "name": "Inverter fault word 6",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: AC relay open circuit  Bit1: AC relay short circuit"
    },
    {
      "address": 40399,
      "count": 1,
      "name": "Inverter fault word 7",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Auxiliary power fault  Bit2: Bus hardware overvoltage  Bit3: Hardware overcurrent  Bit4: Unit hardware overcurrent  Bit12: CBC timeout"
    },
    {
      "address": 40400,
      "count": 1,
      "name": "Inverter fault word 8",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: AD sampling zero drift abnormal  Bit1: RAM self-test failed  Bit2: EEPROM parameters back to default values  Bit3: Historical fault storage failure  Bit4: CAN communication abnormal  Bit7: Bus software overvoltage  Bit8: Unit 1 software"
    },
    {
      "address": 40403,
      "count": 1,
      "name": "Inverter alarm word 3",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit6: Grid abnormal  Bit7: Grid voltage imbalance threshold exceeded  Bit10: Grid phase sequence reverse  Bit13: Grid voltage abnormal"
    },
    {
      "address": 40404,
      "count": 1,
      "name": "Inverter alarm word 4",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit12: Abnormal high efficiency"
    },
    {
      "address": 40405,
      "count": 1,
      "name": "Inverter alarm word 5",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit2: DC voltage detection abnormal  Bit8: DC input voltage high"
    },
    {
      "address": 40406,
      "count": 1,
      "name": "Inverter alarm word 6",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit4: AC SPD abnormal"
    },
    {
      "address": 40407,
      "count": 1,
      "name": "Inverter alarm word 7",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: DC SPD abnormal  Bit6: Booster side open circuit  Bit8: PV string abnormal"
    },
    {
      "address": 40409,
      "count": 1,
      "name": "PID status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Not running 1: Normal running"
    },
    {
      "address": 40410,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Standby 1: Power generation 2: Self-derating power generation 3: Power rationing and derating power generation 4: Planned shutdown 5: Power cuts-caused shutdown 6: Fault shutdown Note: Applicable to Xinjiang power grid"
    },
    {
      "address": 40411,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Shutdown / Standby 1: Normal running 2: Maintenance Note: Applicable to Heilongjiang power grid"
    },
    {
      "address": 40412,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "1: Normal running 2: Shutdown 3: Maintenance 4: Standby Note: Applicable to Ningxia power grid"
    },
    {
      "address": 40413,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Fault 1: Normal running 2: Standby 3: Controlled running Note: Applicable to Sichuan power grid"
    },
    {
      "address": 40414,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "1: Normal running 2: Standby 3: Out of service (faulty, maintenance, limited) Note: Applicable to Xibei power grid"
    },
    {
      "address": 40415,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0: Grid-connected running 1: Standby 2: Limited power 3: Shutdown Note: Applicable to Tianjin power grid"
    },
    {
      "address": 40416,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Standby  Bit1: Power generation  Bit2: Self-derating power generation  Bit3: Power rationing and derating generation  Bit4: Planned shutdown  Bit5: Power cuts- caused shutdown  Bit6: Fault shutdown Note: Applicable to Xinjiang power gri"
    },
    {
      "address": 40417,
      "count": 1,
      "name": "Inverter state",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": " Bit0: Standby Bit1: Power generation  Bit2: Self-derating generation  Bit3: Power rationing and derating generation  Bit4: Planned shutdown at the station  Bit5: Planned shutdown off the station  Bit6: Power cuts- caused shutdown"
    },
    {
      "address": 40631,
      "count": 2,
      "name": "Software version_DC_AC",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40633,
      "count": 2,
      "name": "Software version_DC_DC",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40635,
      "count": 2,
      "name": "Software version_FPGA",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40637,
      "count": 2,
      "name": "Parameter version_DC_AC",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40639,
      "count": 2,
      "name": "Software version_bootloader",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40641,
      "count": 2,
      "name": "Communication protocol version",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "V000.000.000: Version 1 protocol V001.000.000: Version 2 protocol V002.000.000: Version 3 protocol V003.000.000: Version 4 protocol V004.000.000: Version 5 protocol V005.000.000: Version 6 Protocol V006.000.000: Version 7 protocol V007.000.000: Versi"
    },
    {
      "address": 40643,
      "count": 2,
      "name": "Parameter version_DC_DC",
      "data_type": "UInt32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40646,
      "count": 1,
      "name": "Rated power",
      "data_type": "UInt16",
      "units": "kW",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 40647,
      "count": 1,
      "name": "Rated voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    }
  ],
  "combined_registers": [],
  "notes": "Source: EVVO \"Utility PV Inverter Communication Protocol\", V1.0, issue 2023-12-04, vendor-hosted at https://evvosolar.com/doc/Modbus/V4/350Modbus.pdf (SHA-256 81bc41771fa9839344d780ccacc9ba783ef6ede4b47d26d212373f8dc101ac00). Section 2 gives the factory frame: Modbus RTU (RS485) at 9600 bps (also 38400/57600/115200), default device address 1 (range 1-247), 8 data bits, no parity, 1 stop bit. Section 4.1 returns 32-bit values low word first, high word last, so the seed declares LowFirst; section 4.2 defines Gain as a divisor, so the stored factors are 1/gain. The printed addresses are wire addresses: section 7 reads \"register address 40500\" by sending 0x9E34 with function code 03, so the seed is zero-based and keeps them unchanged. Seeded: the section 6.1 telemetry block 40300-40417 (12 MPPT voltage/current/power inputs, 32 DC string currents, grid and inverter three-phase measurements, energy counters, fault and alarm words, and the per-grid-code state words 40410-40417), the section 6.2 remote-control commands 40200-40203, the section 6.3 remote-regulating block 40000-40013 and the section 6.4 device characteristics 40631-40647. This is the utility/central-inverter variant of the same EVVO protocol family as evvo-string-inverters: the telemetry base differs (40300 vs 40500) and the maps are not interchangeable. Scale decisions, all from the document's own cells: 40012 gives two gains (100 for the 250 kW string, 10 for the 350 kW string) and the seed stores the 350 kW gain 0.1; the gain cell of 40371-40373 is merged across those three rows and also reads \"250 kW: 100 / 350 kW: 10\" with the note \"Model dependent\", so AC active power, AC reactive power and DC input power each carry 0.1 for the same reason. Not seeded: the serial number (40601, 30 character registers, no stated encoding). The document has no other register block."
}