All devices

Eastron · Energy meter

SDM54-M / SDM54-2T (SDM54 series, 100 A direct connection) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Voltage L1-N
Float32V1R
22
Voltage L2-N
Float32V1R
42
Voltage L3-N
Float32V1R
62
Current L1
Float32A1R
82
Current L2
Float32A1R
102
Current L3
Float32A1R
122
Active power L1
Float32W1R
142
Active power L2
Float32W1R
162
Active power L3
Float32W1R
182
Apparent power L1
Float32VA1R
202
Apparent power L2
Float32VA1R
222
Apparent power L3
Float32VA1R
242
Reactive power L1
Float32VAr1R
262
Reactive power L2
Float32VAr1R
282
Reactive power L3
Float32VAr1R
302
Power factor L1
Float32-1R
322
Power factor L2
Float32-1R
342
Power factor L3
Float32-1R
362
Phase angle L1
Float32°1R
382
Phase angle L2
Float32°1R
402
Phase angle L3
Float32°1R
422
Average line-to-neutral voltage
Float32V1R
462
Average line current
Float32A1R
482
Sum of line currents
Float32A1R
522
Total system active power
Float32W1R
562
Total system apparent power
Float32VA1R
602
Total system reactive power
Float32VAr1R
622
Total system power factor
Float32-1R
662
Total system phase angle
Float32°1R
702
Frequency
Float32Hz1R
722
Total imported active energy
Float32kWh1R
742
Total exported active energy
Float32kWh1R
762
Total imported reactive energy
Float32kVArh1R
782
Total exported reactive energy
Float32kVArh1R
802
Total apparent energy
Float32kVAh1R
822
Ampere-hours
Float32Ah1R
842
Total system power demand
Float32W1R
862
Maximum total system power demand
Float32W1R
1002
Total system apparent power demand
Float32VA1R
1022
Maximum total system apparent power demand
Float32VA1R
1042
Neutral current demand
Float32A1R
1062
Maximum neutral current demand
Float32A1R
2002
Line-to-line voltage L1-L2
Float32V1R
2022
Line-to-line voltage L2-L3
Float32V1R
2042
Line-to-line voltage L3-L1
Float32V1R
2062
Average line-to-line voltage
Float32V1R
2242
Neutral current
Float32A1R
2342
Voltage THD L1-N
Float32%1R
2362
Voltage THD L2-N
Float32%1R
2382
Voltage THD L3-N
Float32%1R
2402
Current THD L1
Float32%1R
2422
Current THD L2
Float32%1R
2442
Current THD L3
Float32%1R
2482
Average line-to-neutral voltage THD
Float32%1R
2502
Average line current THD
Float32%1R
2582
Current demand L1
Float32A1R
2602
Current demand L2
Float32A1R
2622
Current demand L3
Float32A1R
2642
Maximum current demand L1
Float32A1R
2662
Maximum current demand L2
Float32A1R
2682
Maximum current demand L3
Float32A1R
3342
Line-to-line voltage THD L1-L2
Float32%1R
3362
Line-to-line voltage THD L2-L3
Float32%1R
3382
Line-to-line voltage THD L3-L1
Float32%1R
3402
Average line-to-line voltage THD
Float32%1R
3422
Total active energy (import + export)
Float32kWh1R
3442
Total reactive energy (import + export)
Float32kVArh1R
3462
Imported active energy L1
Float32kWh1R
3482
Imported active energy L2
Float32kWh1R
3502
Imported active energy L3
Float32kWh1R
3522
Exported active energy L1
Float32kWh1R
3542
Exported active energy L2
Float32kWh1R
3562
Exported active energy L3
Float32kWh1R
3582
Total active energy L1
Float32kWh1R
3602
Total active energy L2
Float32kWh1R
3622
Total active energy L3
Float32kWh1R
3642
Imported reactive energy L1
Float32kVArh1R
3662
Imported reactive energy L2
Float32kVArh1R
3682
Imported reactive energy L3
Float32kVArh1R
3702
Exported reactive energy L1
Float32kVArh1R
3722
Exported reactive energy L2
Float32kVArh1R
3742
Exported reactive energy L3
Float32kVArh1R
3762
Total reactive energy L1
Float32kVArh1R
3782
Total reactive energy L2
Float32kVArh1R
3802
Total reactive energy L3
Float32kVArh1R
25662
Active power demand L1
Float32W1R
25682
Active power demand L2
Float32W1R
25702
Active power demand L3
Float32W1R
26102
Maximum active power demand L1
Float32W1R
26122
Maximum active power demand L2
Float32W1R
26142
Maximum active power demand L3
Float32W1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device read natively over Modbus RTU: connect it at the factory serial settings above. Sources: Eastron "SDM54-M/-2T Modbus Protocol Implementation V1.1" (2021), which prints every register with its 3X/4X number and the wire address in hex, and the "SDM54 Series Energy Meter User Manual" 2021 V1.2 (supplier_url). The factory frame is assembled from both documents: the manual's setup menu prints Baud default 9600, Parity default None and Stop default 1 (5.3.1 lists the same options), the protocol document's RTU framing prints "8 data bits, least significant bit sent first", and its Network Node register (40021) prints "1 to 247 for MODBUS Protocol, default 1". All values are IEEE-754 Float32, most significant register first (the protocol document's default register order); 3X rows are read with function code 04 and 4X rows with 03/16. The seed carries every 3X row the document prints except 30255, which names "Total system power factor" with the unit "Degrees" and contradicts 30063, and the SDM54-2T tariff and tariff-demand block 34877-35503, which is on the -2T variant only and repeats the total-energy rows. The address holes in the seed mirror holes in the document, which itself jumps 30043 to 30047, 30049 to 30053, 30057 to 30061, 30087 to 30101 and 30107 to 30201. Of the 15 holding rows the document prints the seed carries 14 and leaves out only the write-only Reset command at 0xF010 (61456) that clears the maximum demand. Overlap with eastron-sdm630 is large and disclosed: 89 of these 105 rows sit at the same address with the same type, unit and scale, because Eastron reuses the measurement map across the SDM series, and both seeds record the same 9600 8N1 frame - but they are different documents (the 630 prints maximum import apparent demand at 0x56 where this one prints total system power demand in W), the 630 seed reaches the meter through a gateway while this one reads it natively, and this seed adds per-phase demand and extra settings.