Eastron · Energy meter

SDM72D-M Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
L1 Voltage
Float32V1R
22
L2 Voltage
Float32V1R
42
L3 Voltage
Float32V1R
62
L1 Current
Float32A1R
82
L2 Current
Float32A1R
102
L3 Current
Float32A1R
122
L1 Power (Active)
Float32W1R
142
L2 Power (Active)
Float32W1R
162
L3 Power (Active)
Float32W1R
182
L1 Power (Apparent)
Float32VA1R
202
L2 Power (Apparent)
Float32VA1R
222
L3 Power (Apparent)
Float32VA1R
242
L1 Power (Reactive)
Float32VAr1R
262
L2 Power (Reactive)
Float32VAr1R
282
L3 Power (Reactive)
Float32VAr1R
302
L1 Power Factor
Float32-1R
322
L2 Power Factor
Float32-1R
342
L3 Power Factor
Float32-1R
422
L-N Voltage
Float32V1R
462
L-N Current
Float32A1R
482
Total Line Current
Float32A1R
522
Total Power
Float32W1R
562
Total Power (Apparent)
Float32VA1R
602
Total Power (Reactive)
Float32VAr1R
622
Total Power Factor
Float32-1R
702
Frequency
Float32Hz1R
722
Imported Energy (Active)
Float32kWh1R
742
Exported Energy (Active)
Float32kWh1R
2002
L1-L2 Voltage
Float32V1R
2022
L2-L3 Voltage
Float32V1R
2042
L3-L1 Voltage
Float32V1R
2062
L-L Voltage
Float32V1R
2242
Neutral Current
Float32A1R
3422
Total Energy (Active)
Float32kWh1R
3442
Total Energy (Reactive)
Float32kVArh1R
3842
Resettable Total Energy (Active)
Float32kWh1R
3882
Resettable Import Energy (Active)
Float32kWh1R
3902
Resettable Export Energy (Active)
Float32kWh1R
3962
Net kWh (Import - Export)
Float32kWh1R
12802
Total Import Power (Active)
Float32W1R
12822
Total Export Power (Active)
Float32W1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. Measurements are IEEE-754 Float32 values (high word first) read with function code 04; the configuration registers are read/written with function code 03.