Eastron · Energy meter

SDM120-Modbus Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
2400
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Voltage
Float32V1R
62
Current
Float32A1R
122
Power (Active)
Float32W1R
182
Power (Apparent)
Float32VA1R
242
Power (Reactive)
Float32VAr1R
302
Power Factor
Float32-1R
362
Phase Angle
Float32°1R
702
Frequency
Float32Hz1R
722
Imported Energy (Active)
Float32kWh1R
742
Exported Energy (Active)
Float32kWh1R
762
Imported Energy (Reactive)
Float32kVArh1R
782
Exported Energy (Reactive)
Float32kVArh1R
842
Total Demand Power (Active)
Float32W1R
862
Maximum Total Demand Power (Active)
Float32W1R
882
Import Demand Power (Active)
Float32W1R
902
Maximum Import Demand Power (Active)
Float32W1R
922
Export Demand Power (Active)
Float32W1R
942
Maximum Export Demand Power (Active)
Float32W1R
2582
Total Demand Current
Float32A1R
2642
Maximum Total Demand Current
Float32A1R
3422
Total Energy (Active)
Float32kWh1R
3442
Total Energy (Reactive)
Float32kVArh1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. Measurements are IEEE-754 Float32 values (high word first) read with function code 04; the configuration registers are read/written with function code 03.