CS Instruments · Flow meter
VA 500 / VA 520 / VA 550 / VA 570 compressed air and gas flow meter (VA 5xx) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 1-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 2001 | 1 | Modbus ID Slave address, range 1-247, default setting 1. | UInt16 | - | 1 | RW |
| 2002 | 1 | Baud rate 0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200, 5 = 38400, 6 = 57600, 7 = 115200. Default setting 4 (19200), which matches the 'Baud rate 19200' row of the factory-settings table. | UInt16 | - | 1 | RW |
| 2003 | 1 | Parity 0 = none, 1 = even, 2 = odd. Default setting 1 (even), which matches the 'Parity even' row of the factory-settings table. | UInt16 | - | 1 | RW |
| 2004 | 1 | Number of stop bits 0 = 1 stop bit, 1 = 2 stop bits. The register table leaves the default cell empty; the factory-settings table of the same manual prints 'Stop bit 1', which the seed's serial block stores. | UInt16 | - | 1 | RW |
| 2005 | 1 | Word order 0xABCD = Big Endian, 0xCDAB = Middle Endian; default setting 0xABCD, which is why the seed declares BigEndian + HighFirst. A site that reads wrong 32-bit values should try Middle Endian (LowFirst). | UInt16 | - | 1 | RW |
| 2069 | 2 | Pressure type (relative / absolute) The document types this register float and gives its values as 0 = relative, 1 = absolute; it selects the reference of the system-pressure values. | Float32 | - | 1 | RW |
| 1057 | 2 | Delta P Differential pressure, unit as defined in the sensor. | Float32 | - | 1 | R |
| 1101 | 2 | Flow in m3/h Flow value in the unit printed in the description column of the value-register table. | Float32 | m3/h | 1 | R |
| 1109 | 2 | Flow in Nm3/h Flow value normalised to standard conditions. | Float32 | Nm3/h | 1 | R |
| 1117 | 2 | Flow in m3/min Flow value in m3/min. | Float32 | m3/min | 1 | R |
| 1133 | 2 | Flow in ltr/h Flow value in litres per hour. | Float32 | l/h | 1 | R |
| 1181 | 2 | Flow in cfm Flow value in cubic feet per minute. | Float32 | cfm | 1 | R |
| 1197 | 2 | Flow in kg/h Mass flow value. | Float32 | kg/h | 1 | R |
| 1221 | 2 | Flow in kW Thermal power derived from the mass flow. | Float32 | kW | 1 | R |
| 1269 | 2 | Consumption m3 before comma Consumption counter, integer part in m3; the decimal places are served by the companion 'after comma' register of the same block in the document. | UInt32 | m3 | 1 | R |
| 1311 | 2 | Consumption kWh before comma Energy consumption counter, integer part in kWh; the decimal places are served by the companion 'after comma' register of the same block in the document. | UInt32 | kWh | 1 | R |
| 1347 | 2 | Velocity m/s Gas velocity through the pipe. | Float32 | m/s | 1 | R |
| 1419 | 2 | Gas temperature Gas temperature in degrees Celsius; the same table also serves it in degF. | Float32 | °C | 1 | R |
| 1475 | 2 | System pressure mBar System pressure; the value served depends on the pressure-type setting at register 2069. | Float32 | mbar | 1 | R |
| 1481 | 2 | System pressure Bar System pressure in bar. | Float32 | bar | 1 | R |
| 1487 | 2 | System pressure PSIr System pressure in psi. | Float32 | psi | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: CS Instruments 'Instruction manual VA 500' V2.02 EN, chapter 11.4 'Register assignment' (Tables 24-26) plus Table 6 factory settings (SHA-256 12193ae99b764d63c9b10a12e3cd948aeb4e2962bf36d4c6a03d3151811a8884), cross-checked against 'VA 5xx Modbus RTU Installation' V1.17 section 7.3.1 for the 2001-2005 settings registers (SHA-256 0ab5eb00cdc82d7551159574fd91779cc382ffe95d87d1ef1a368f3e39e8950d), both vendor-hosted. Factory frame: Modbus RTU, 19200 baud, even parity, 1 stop bit, address 1 (Table 6: ID 1, 19200, stop bit 1, parity even, data format ABCD/Big Endian). Data bits are not printed: neither manual has a data-bits setting (the 2001-2005 block holds ID, baud, parity, stop bits and word order) and both name 'Modbus over serial line V1.02' as the standard, which fixes RTU characters at 8 data bits. The register table prints a 1-based 'Register' column next to an 'Address' column that is always Register-1 (2001 -> 2000, 1101 -> 1100), so the seed stores the Register column and declares one_based. Seeded value rows: flow 1101 m3/h, 1109 Nm3/h, 1117 m3/min, 1133 ltr/h, 1181 cfm, 1197 kg/h, 1221 kW; consumption 1269 m3 and 1311 kWh (integer part, with the decimal part in the companion 'after comma' register); velocity 1347 m/s; gas temperature 1419 degC; the pressure option's 1057 Delta P and 1475/1481/1487 mbar/bar/psi; and the 2069 pressure-type setting. Omitted on purpose: the remaining unit aliases of the same quantities - flow 1125 Nm3/min, 1141 Nltr/h, 1149 ltr/min, 1157 Nltr/min, 1165 ltr/s, 1173 Nltr/s, 1189 Ncfm, 1205 kg/min, 1213 kg/s; consumption 1275 Nm3, 1281 ltr, 1287 Nltr, 1293 cf, 1299 Ncf, 1305 kg; velocity 1355 Nm/s, 1363 ft/min, 1371 Nft/min; temperature 1427 degF - plus every Min/Max/AV row and the display/device-settings blocks. 32-bit word order: the Word Order register (2005) defaults to 0xABCD = Big Endian, so BigEndian + HighFirst is what the device ships with, with 0xCDAB (LowFirst) as the documented alternative.