All devices

CS Instruments · Flow meter

VA 500 / VA 520 / VA 550 / VA 570 compressed air and gas flow meter (VA 5xx) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
20011
Modbus ID
Slave address, range 1-247, default setting 1.
UInt16-1RW
20021
Baud rate
0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600, 4 = 19200, 5 = 38400, 6 = 57600, 7 = 115200. Default setting 4 (19200), which matches the 'Baud rate 19200' row of the factory-settings table.
UInt16-1RW
20031
Parity
0 = none, 1 = even, 2 = odd. Default setting 1 (even), which matches the 'Parity even' row of the factory-settings table.
UInt16-1RW
20041
Number of stop bits
0 = 1 stop bit, 1 = 2 stop bits. The register table leaves the default cell empty; the factory-settings table of the same manual prints 'Stop bit 1', which the seed's serial block stores.
UInt16-1RW
20051
Word order
0xABCD = Big Endian, 0xCDAB = Middle Endian; default setting 0xABCD, which is why the seed declares BigEndian + HighFirst. A site that reads wrong 32-bit values should try Middle Endian (LowFirst).
UInt16-1RW
20692
Pressure type (relative / absolute)
The document types this register float and gives its values as 0 = relative, 1 = absolute; it selects the reference of the system-pressure values.
Float32-1RW
10572
Delta P
Differential pressure, unit as defined in the sensor.
Float32-1R
11012
Flow in m3/h
Flow value in the unit printed in the description column of the value-register table.
Float32m3/h1R
11092
Flow in Nm3/h
Flow value normalised to standard conditions.
Float32Nm3/h1R
11172
Flow in m3/min
Flow value in m3/min.
Float32m3/min1R
11332
Flow in ltr/h
Flow value in litres per hour.
Float32l/h1R
11812
Flow in cfm
Flow value in cubic feet per minute.
Float32cfm1R
11972
Flow in kg/h
Mass flow value.
Float32kg/h1R
12212
Flow in kW
Thermal power derived from the mass flow.
Float32kW1R
12692
Consumption m3 before comma
Consumption counter, integer part in m3; the decimal places are served by the companion 'after comma' register of the same block in the document.
UInt32m31R
13112
Consumption kWh before comma
Energy consumption counter, integer part in kWh; the decimal places are served by the companion 'after comma' register of the same block in the document.
UInt32kWh1R
13472
Velocity m/s
Gas velocity through the pipe.
Float32m/s1R
14192
Gas temperature
Gas temperature in degrees Celsius; the same table also serves it in degF.
Float32°C1R
14752
System pressure mBar
System pressure; the value served depends on the pressure-type setting at register 2069.
Float32mbar1R
14812
System pressure Bar
System pressure in bar.
Float32bar1R
14872
System pressure PSIr
System pressure in psi.
Float32psi1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: CS Instruments 'Instruction manual VA 500' V2.02 EN, chapter 11.4 'Register assignment' (Tables 24-26) plus Table 6 factory settings (SHA-256 12193ae99b764d63c9b10a12e3cd948aeb4e2962bf36d4c6a03d3151811a8884), cross-checked against 'VA 5xx Modbus RTU Installation' V1.17 section 7.3.1 for the 2001-2005 settings registers (SHA-256 0ab5eb00cdc82d7551159574fd91779cc382ffe95d87d1ef1a368f3e39e8950d), both vendor-hosted. Factory frame: Modbus RTU, 19200 baud, even parity, 1 stop bit, address 1 (Table 6: ID 1, 19200, stop bit 1, parity even, data format ABCD/Big Endian). Data bits are not printed: neither manual has a data-bits setting (the 2001-2005 block holds ID, baud, parity, stop bits and word order) and both name 'Modbus over serial line V1.02' as the standard, which fixes RTU characters at 8 data bits. The register table prints a 1-based 'Register' column next to an 'Address' column that is always Register-1 (2001 -> 2000, 1101 -> 1100), so the seed stores the Register column and declares one_based. Seeded value rows: flow 1101 m3/h, 1109 Nm3/h, 1117 m3/min, 1133 ltr/h, 1181 cfm, 1197 kg/h, 1221 kW; consumption 1269 m3 and 1311 kWh (integer part, with the decimal part in the companion 'after comma' register); velocity 1347 m/s; gas temperature 1419 degC; the pressure option's 1057 Delta P and 1475/1481/1487 mbar/bar/psi; and the 2069 pressure-type setting. Omitted on purpose: the remaining unit aliases of the same quantities - flow 1125 Nm3/min, 1141 Nltr/h, 1149 ltr/min, 1157 Nltr/min, 1165 ltr/s, 1173 Nltr/s, 1189 Ncfm, 1205 kg/min, 1213 kg/s; consumption 1275 Nm3, 1281 ltr, 1287 Nltr, 1293 cf, 1299 Ncf, 1305 kg; velocity 1355 Nm/s, 1363 ft/min, 1371 Nft/min; temperature 1427 degF - plus every Min/Max/AV row and the display/device-settings blocks. 32-bit word order: the Word Order register (2005) defaults to 0xABCD = Big Endian, so BigEndian + HighFirst is what the device ships with, with 0xCDAB (LowFirst) as the documented alternative.