Belimo · Refrigeration controller

xBALL 4.0 electronic expansion valve with integrated superheat controller Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
19
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Hardware alarm
Binary-1R
11
Gearbox alarm
Binary-1R
21
Bus Communication Alarm
Binary-1R
31
Evaporation Pressure Probe Alarm
Binary-1R
41
Suction Temperature Probe Alarm
Binary-1R
51
LSH (low superheat) Alarm
Binary-1R
61
LSU (low suction temperature) Alarm
Binary-1R
71
LOP (low evaporation temperature) Alarm
Binary-1R
81
MOP (high evaporation temperature) Alarm
Binary-1R
91
LSH (low superheat) Protection Activation Notification
Binary-1R
101
LOP (low evaporation temperature) Protection Activation Notification
Binary-1R
111
MOP (high evaporation temperature) Protection Activation Notification
Binary-1R
121
Digital Input Activation Notification
Binary-1R
1001
Regulation Enabling
Binary-1RW
1011
Evaporation Pressure Probe Alarm Enabling
Binary-1RW
1021
Suction Temperature Probe Alarm Enabling
Binary-1RW
1031
Start Adaption Procedure
Binary-1RW
1041
Manual Positioner Enabling
Binary-1RW
1051
Termination Resistor Enabling
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Belimo "ModBus Interface Description xBALL 4.0", edition 2026-09, document date 30.06.26, vendor document belimo_Modbus-Register_xBALL_V4_0_en-gb.pdf (belimo.com answers automated document requests with HTTP 403, so the identical Belimo MAM document was read from Belimo's regional mirror www.belimo.ro; the mirrored file's SHA-256 is f5a5f5a0ccae2852b33d58a6424813a39021ff65d244c527486b03ae238fc5be). The document states the transmission formats with default 1-8-N-2, the baud rates with default 19'200 Bd and the node address range 1...247 with default 19, which is what the serial block records. It also states that all data is addressed by 1..n (Register No.) or 0..n-1 (Address), so the "Address" column is stored and addressing is zero_based. Registers are holding registers read with function 03 and written with 06/16; the alarm and enabling bits are coils (01/05). All register values are signed integers except the rows the document marks **) as unsigned, which is the identity and serial block R101-R116, hence UInt16 there. Scaling and units are the document's own columns. The barg/psig and degC/degF register pairs (R401-R413, R501-R513) are both present and scaled 0.1; the measurement block R1-R13 and the configuration block R301-R341 carry the scaling the document prints next to each row. The refrigerant enumeration rows R303-R305 and the PIN entry register are not included: the enumeration rows are printed as ".." continuations of the R302 refrigerant table, and the PIN entry register's address is printed as "R206" in the source, which contradicts the register overview.