PR actuator for butterfly valves (PR..A-BAC-..) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
38400
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Setpoint
Setpoint for the actuator, scaled between 0 and Max (register 106). Range 0...10000. Default 0.
UInt16%0.01RW
11
Override control
0 = none (default), 1 = open, 2 = close, 3 = min, 4 = mid, 5 = max, 6 = fast open, 7 = fast close.
UInt16-1RW
21
Command
0 = none (default). Actuator service and test functions; the register returns to none after the command has been sent.
UInt16-1RW
31
Actuator type
0 = actuator not connected, 1 = air / water, 2 = VAV / EPIV, 3 = fire, 4 = energy valve, 5 = 6-way EPIV.
UInt16-1R
41
Relative position
Range 0...10000.
UInt16%0.01R
51
Absolute position
Degrees for actuators with rotary movement, millimetres for actuators with linear movement.
UInt16°1R
81
Sensor 1 value
Millivolts when sensor type 1 (register 107) is active, ohms for passive_1K / passive_20K, 0 / 1 for a switch, degrees Celsius or Fahrenheit x0.1 for the PT1000 / NI1000 / NTC10K2 types. Range 0...65535.
UInt16mV1R
91
Sensor 2 value
Same conversion rules as sensor 1, following sensor type 2 (register 114). Range 0...65535.
UInt16mV1R
121
Analog setpoint
Setpoint in percent when the actuator is controlled by the analog signal.
UInt16%0.01R
991
Bus termination
0 = inactive (default), 1 = active: the 120 ohm bus termination is enabled.
UInt16-1R
1001
Series number, 1st part
Parts 1, 2 and 4 of the four-part series number are readable; the example 00839-31324-064-008 is read as 00839 / 31324 / 008.
UInt16-1R
1011
Series number, 2nd part
UInt16-1R
1021
Series number, 4th part
UInt16-1R
1031
Firmware version
Communication module firmware, e.g. 302 for version 3.02.
UInt16-1R
1041
Malfunction and service information
Bit-coded. Bit 1 mechanical travel increased, bit 2 actuator cannot move, bit 8 internal activity, bit 9 gear train disengaged (manual override pressed), bit 10 bus watchdog triggered.
Binary-1R
1061
Max
Upper position limit, range Min+3000...10000 (Max has to be at least Min + 30 percent). Default 10000. This range has no Min register.
UInt16%0.01RW
1071
Sensor 1 type
0 = none (default), 1 = active / hybrid, 2 = passive_1K, 3 = passive_20K, 4 = switch, 5 = PT1000_C, 6 = NI1000_C, 7 = NTC10K2_C, 8 = PT1000_F, 9 = NI1000_F, 10 = NTC10K2_F.
UInt16-1RW
1081
Bus fail position
0 = none / last setpoint (default), 1 = fast close, 2 = fast open, 3 = mid position. Becomes active when the bus watchdog (register 109) expires.
UInt16-1RW
1091
Timeout for bus watchdog
0 = deactivated (default), range 0...3600 s. When a bus fail position is configured the document states a default of 120 s.
UInt16s1RW
1141
Sensor 2 type
0 = none (default), 1 = active / hybrid, 2 = passive_1K, 3 = passive_20K, 4 = switch, 5 = PT1000_C, 6 = NI1000_C, 7 = NTC10K2_C, 8 = PT1000_F, 9 = NI1000_F, 10 = NTC10K2_F.
UInt16-1RW
1181
Setpoint source
0 = analog signal on wire 3, 1 = bus (default, setpoint from register 0).
UInt16-1RW
1891
Fail-safe bridging time
0...10 s. The actuator stays in position for this time after a power failure before moving to the fail-safe position. Only for electronic fail-safe actuators.
UInt16s1RW
1901
Fail-safe position
Position taken after a power failure, respecting the bridging time. Range 0...10000. The rotary knob must be in the tool position.
UInt16%0.01RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Belimo 'Modbus Interface Description - PR Actuator, Rotary actuator for butterfly valves', edition 2026-01 / V3.08, manufacturer date 01.12.2023 (belimo_Modbus-Register_PR_V3_8_en-gb.pdf). www.belimo.com refuses automated downloads (HTTP 403), so the document was read from Belimo's own regional mirror https://www.belimo.ro/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_PR_V3_8_en-gb.pdf (same MAM document and edition); the URL above is the canonical vendor location. Actuator type: PR..A-BAC-.. (butterfly valve actuators). Factory Modbus settings: 38400 Bd, 1-8-N-2 (8 data bits, no parity, 2 stop bits), address 1; 9600/19200/76800/115200 Bd and 1-8-N-1 / 1-8-E-1 / 1-8-O-1 are selectable, as are addresses 1...247. Addressing: 'addressed by 1..n (Register No.) or 0..n-1 (Address)' with both columns on every row, so the stored values are the Address column, i.e. zero_based. This map is not the air/water actuator map: the PR range has two sensor inputs (registers 8/9 with types 107 and 114), carries only a Max limit (register 106, at least 30 percent above an implicit minimum) and no Min register (register 105 is printed as '–'), and its fail-safe registers sit at 190/191 as on the air/water range. All values are unsigned 16-bit; there are no 32-bit rows, so word order only matters if a reader later adds them (Belimo stores 32-bit values LSW first, hence LowFirst). Left out: registers 6, 7, 10, 11, 105, 110-113, 115-117, all printed as '–'. Sensor values are entered with the millivolt unit and no scaling because the unit and the scale follow the configured sensor type (millivolt 1:1, ohm 1:1, switch 0/1, temperature types x0.1).