Belimo · Energy meter

Thermal Energy Meter TEM DN 15...50 (version 4, 22PE..-1U.. / 22PF-..) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first

Register map

AddressCountNameTypeUnitScaleAccess
31
Device type
0 = device not connected, 1 = air / water, 2 = VAV / EPIV, 3 = fire, 4 = energy valve / energy meter, 5 = 6-way EPIV.
UInt16-1R
61
Relative volumetric flow
Relative to the nominal volumetric flow qp in register 110/111/112. Range 0...15000.
UInt16%0.01R
71
Absolute volumetric flow
Range 0...1576; the sensor reads up to 2.5 x qp.
UInt16l/s0.01R
81
Absolute volumetric flow
Range 0...2498; the sensor reads up to 2.5 x qp.
UInt16gpm0.1R
92
Absolute volumetric flow in the selected unit
Unit chosen by register 147, low word first.
UInt32UnitSel0.001R
121
Sensor 1 value
Additional sensor input; millivolts, a resistance or a 0/1 state depending on sensor type 1 (register 120).
UInt16mV1R
131
Sensor 1 temperature
Range -2000...15000 counts (x0.01 degrees).
Int16°C0.01R
141
Sensor 1 temperature
Range -400...30200 counts (x0.01 degrees).
Int16°F0.01R
191
Temperature 1 (remote)
Range -2000...15000 counts (x0.01 degrees).
Int16°C0.01R
201
Temperature 1 (remote)
Range -400...30200 counts (x0.01 degrees).
Int16°F0.01R
211
Temperature 2 (flow body)
Range -2000...15000 counts (x0.01 degrees).
Int16°C0.01R
221
Temperature 2 (flow body)
Range -400...30200 counts (x0.01 degrees).
Int16°F0.01R
231
Delta temperature
Int16K0.01R
241
Delta temperature
Int16°F0.01R
251
Glycol concentration
Range 0...6000 (x0.01 percent); the effective range depends on the device type.
UInt16%0.01R
272
Absolute power cooling
Low word first. Range 0...3990000 (x0.001 kW).
UInt32kW0.001R
292
Absolute power cooling
Low word first. Range 0...136140 (x0.001 kBTU/h).
UInt32kBTU/h0.001R
312
Absolute power cooling in the selected unit
Unit chosen by register 148, low word first.
UInt32UnitSel0.1R
332
Absolute power heating
Low word first. Range 0...3990000 (x0.001 kW).
UInt32kW0.001R
352
Absolute power heating
Low word first. Range 0...13614000 (x0.001 kBTU/h).
UInt32kBTU/h0.001R
372
Absolute power heating in the selected unit
Unit chosen by register 148, low word first.
UInt32UnitSel0.1R
592
Accumulated volume
Cannot be reset. Low word first. Range 0...2147483600 (x0.01 m3).
UInt32m30.01R
612
Accumulated volume
Cannot be reset. Low word first. Range 0...2147483647 gal.
UInt32gal1R
632
Accumulated volume in the selected unit
Unit chosen by register 149, low word first.
UInt32UnitSel1R
652
Absolute energy cooling
Low word first. Range 0...2147483647 kWh.
UInt32kWh1R
672
Absolute energy cooling
Low word first.
UInt32kBTU1R
692
Absolute energy cooling in the selected unit
Unit chosen by register 150, low word first.
UInt32UnitSel1R
712
Absolute energy heating
Low word first.
UInt32kWh1R
732
Absolute energy heating
Low word first.
UInt32kBTU1R
752
Absolute energy heating in the selected unit
Unit chosen by register 150, low word first.
UInt32UnitSel1R
991
Bus termination
0 = disabled (default), 1 = enabled: the 120 ohm bus termination is active.
UInt16-1R
1001
Series number, 1st part
Parts 1, 2 and 4 of the four-part series number are readable; the example 00839-31324-064-008 is read as 00839 / 31324 / 008.
UInt16-1R
1011
Series number, 2nd part
UInt16-1R
1021
Series number, 4th part
UInt16-1R
1031
Firmware version
Communication module firmware, e.g. 402 for version 4.02.
UInt16-1R
1041
Malfunction and service information
Binary-1R
1101
Nominal volumetric flow (qp)
Range 0...10000 (x0.01 l/s).
UInt16l/s0.01R
1111
Nominal volumetric flow (qp)
Range 0...15850 (x0.1 gpm).
UInt16gpm0.1R
1122
Nominal volumetric flow (qp) in the selected unit
Unit chosen by register 147, low word first.
UInt32UnitSel0.001R
1201
Sensor 1 type
0 = none (default), 1 = active, 3 = passive, 4 = switch, 5 = switch (other state).
UInt16-1RW
1211
Sensor 1 passive type
0 = resistance measurement (default), further passive types follow register 120.
UInt16-1RW
1471
Unit selection flow
0 = m3/s, 1 = m3/h, 2 = l/s, 3 = l/min, 4 = l/h (default), 5 = gpm, 6 = cfm. Applies to the 32-bit flow registers 9 and 112.
UInt16-1RW
1481
Unit selection power
0 = W, 1 = kW (default), 2 = MW, 3 = BTU/h, 4 = kBTU/h, 5 = ton. Applies to the 32-bit power registers 31, 37 and 163.
UInt16-1RW
1491
Unit selection volume
0 = m3 (default), 1 = litre, 2 = gallon, 3 = cf. Applies to register 63.
UInt16-1RW
1501
Unit selection energy
0 = J, 1 = kJ, 2 = MJ, 3 = GJ, 4 = Wh, 5 = kWh (default), 6 = MWh, 7 = BTU, 8 = kBTU, 9 = ton. Applies to registers 69 and 75.
UInt16-1RW
1592
Nominal power
P'nom, low word first. Range 0...1330000 (x0.001 kW).
UInt32kW0.001R
1612
Nominal power
P'nom, low word first. Range 0...4538000 (x0.001 kBTU/h).
UInt32kBTU/h0.001R
1632
Nominal power in the selected unit
P'nom in the unit chosen by register 148, low word first.
UInt32UnitSel0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Belimo 'Modbus Interface Description - Thermal Energy Meter (TEM) DN 15...50 (Version 4)', edition 2025-11 / V4.2.0, manufacturer date 25.04.2024 (belimo_Modbus-Register_TEM_V4_2_en-gb.pdf), sections Flow, Power, Energy, Temperature and conversion of sensor signals. www.belimo.com refuses automated downloads (HTTP 403), so the document was read from Belimo's own regional mirror https://www.belimo.ro/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_TEM_V4_2_en-gb.pdf (same MAM document and edition); the URL above is the canonical vendor location. Model numbers in the header are 22PE..-1U.. (e.g. 22PEM-1UC) and 22PF-x1(X)Ux2(x3(x4))-(SG). The meter has both transports: Modbus RTU over RS-485 (38400 Bd default, 1-8-N-2 default, address 1, 9600/19200/76800/115200 Bd and 1-8-N-1 / 1-8-E-1 / 1-8-O-1 selectable) and Modbus TCP over Ethernet. This seed declares the TCP path, so no serial block is needed. Addressing: 'addressed by 1..n (Register No.) or 0..n-1 (Address)' with both columns on every row; the stored values are the Address column (Register No. minus 1) - zero_based. Values above 65535 are split over two registers with the LowWord first, so the two-register rows are entered as UInt32 with word order LowFirst (the document's example: high word at Register No. x+1, low word at x). This is not the Energy Valve map: the TEM has no setpoint, override, command, control-mode or limit registers at all - it only measures flow, temperatures, power, accumulated volume and energy, and sets its units through 147-150. Left out: the energy-meter serial and production order numbers (registers 200-203), register 105's bit list (carried as a bit-coded status word only), and the ranges of registers 110/111 which the table prints with the selected-unit alternatives. Unsupported readings are returned as 65535 and the meter applies its own DN-dependent size limitation inside the printed ranges.